FW752, FW752C Non-addressable Manual Station
FW752 FW752C
DESCRIPTION
The FW752 and FW752C Non-addressable Manual
Stations are UL listed devices according to UL 38 and
ULC-S528 for Fire Protective Signaling Systems for
indoor use, and also meet ADA 5lb. maximum
manual-force. It is normally open initiating device
made from durable materials and solid parts for long
lasting performance. In case of fire, an alarm signal is
generated by lifting the cover and pushing the
button. A red LED is visible on the station when the
fire alarm signal is activated. A switch key (included)
resets the station.
ATTENTION
The products must be installed in
accordance with the National Electrical
Code NFPA 70, the National Fire Alarm
and Signaling Code NFPA 72, the Canadian
codes CAN/ULC-S524 (Installation of Fire Alarm
Systems), and CSA C22.1 Sec. 32 (Canadian Electrical
Code), local codes, and the Local Authorities Having
Jurisdiction. Prior to installing bases, make sure the
product will have sufficient margin and wiring room.
Do not over tighten the mounting screws to avoid
base deformation, which may affect the device
efficiency. Check information of equipment used in
the system by other manufacturers for any
guidelines or restrictions.
The product must be used within its published
specifications and properly installed, operated, and
maintained, in accordance with these instructions.
Not following these instructions may result in no
alarm or false alarm. Maple Armor is not responsible
for devices that are improperly installed, maintained
or tested.
NOTE
Do not paint this device.
Any material extrapolated from this document or
from Maple Armor’s instructions or other
documents describing the product for use in
promotional or advertising claims, or for any other
use, including description of the product’s
application, operation, installation, and testing is the
sole responsibility of the user. Maple Armor will not
assume any liability for such use. In no case will
Maple Armor’s liability exceed the purchase price
paid for a product.
SPECIFICATION
Operating Voltage
12 to 33VDC
Quiescent Current
0mA
Operating Current
150mA max.
Operating
Temperature
32° to 120°F (0° to 49°C )
Operating Humidity
0% to 93% RH
Dimension (with base)
120 mm (L) x 120 mm (W) x 54 mm (H)
Weight (with base)
8.4 oz (237 g)
Mounting
FW700 Base
Wiring Gauge
12 to 18 AWG
INSTALLATION
1.
Base and electrical box are optional for
installation, as illustrated in Figure 1.
Figure 1. Manual Station Installation