D00729EN - v2 

DDS-SSENSOR 

- INSTALLATION MANUAL 

 

2.3 SAFETY FIELD SETTING - INFRARED 

Press twice to activate the  
visible spot. 

If necessary, adjust the angle of the 
infrared curtains (from -7º to +4º) 

Part of the emitted field can be covered in order to reduce the detection field.  

The position of the arrow determines the field width. 

Always check the field width with a 
piece of paper and not with the 
Spotfinder, that detects the entire 
emitted field. 

Possible 
additional 
settings 
through 
the LCD. 

≤ 9 cm 

*Visibility depends on external conditions. If the spots are not visible, the Spotfinder helps to locate the position of the curtains. 
**The distance between the inner curtain of the inside door sensor and the inner curtain of the outside door sensor should always be 
less than 20cm 
The distance up to the door leaf depends therefore on the thickness of the door leaf. 

CLOSER 

FARTHER 

 

2.4 OTHER SETTINGS 

Set the sensor by LCD or choose one of the presettings: 

1.- STANDARD

: indoor mounting 

 

2.– CRITICAL ENVIRONMENT

: critical or outside installations 

 

3.– SHOPPING STREET

: Installations in narrow streets with pedestrian traffic 

Presettings 

Standard 

Presettings

 

Critical env. 

Presettings 

Shopping str. 

A

N

G

LE

 

WI

DTH

 

x2 

The size of the detection fields varies depending on the mounting height and the settings of the sensor. The sensor should 
cover the whole travel path of the door leaf/leaves. To verify, use the reference body as per EN 16005 (reference body 
dimensions: 700x300x200mm). 
 
 

Cuerpo de referencia 

Summary of Contents for DDS-S

Page 1: ...1 D00729EN v2 DDS SSENSOR INSTALLATION MANUAL Installation Manual DDS S SENSOR ...

Page 2: ...is manual includes all the necessary information required to install the product Keep this manual in a safe place for future reference 1 DESCRIPTION The AIR DPS Sensor is an electro sensitive device for the detection of individuals specifically designed to provide safety to Manusa sliding doors This sensor complies with all the requirements specified in the Standard EN 16005 4 LCD screen Infrared ...

Page 3: ...r should only be carried out by manusa Any other use of the device different from its intended purpose shall be excluded from the manufacturer s guarantee This device may only be operated with protective low voltage SELV with safe electrical insulation The installing company shall be responsible for the correct installation of the sensor and the door safety elements The manufacturer shall not be l...

Page 4: ...gative adjustable Impedance Positive pulse 2K to earth 470R to the of the power source Pulse voltage from 6V to 30V Pulse duration from 4µs to 500µs Work cycle Max 50 Output Pulse polarity negative Level No detection Pulse between the of the power source and 0V Detection the of the power source Topology open collector with 4 7K to 3 3V Maximum sink current 25mA with 1K external resistance towards ...

Page 5: ... start up and settings 2 1 MOUNTING Max 5cm 2 1 2 SURFACE MOUNTING OPTIONAL 136 mm 2 1 1 STANDARD MOUNTING Slide 1 Clip 2 Unclip 1 Presionar 1 1 1 1 1 2 MOUNT DISMOUNT 1 Remove the protective cover 2 Connect the cable 3 Position the drilling template 4 Drill the holes and remove the template 5 Pass the cable through and install the sensor ...

Page 6: ...6 D00729EN v2 DDS SSENSOR INSTALLATION MANUAL Cut 1 Screw together 2 Clip 3 Clip 4 Unclip 5 Clip 6 Unclip 7 Clip 8 2 1 4 MOUNTING WITH RAIN PROTECTION OPTIONAL 2 1 3 CEILING MOUNTING OPTIONAL ...

Page 7: ...connect to 12V VERDE MARRÓN AMARILLO BLANCO ROSA GRIS VIOLET SENSOR 12 30V AC DC 2 2 1 CONNECTION TO VISIO OPERATOR FOR OPENING PROTECTION Brown Green Pink Grey Note Configure the following parameter PULSE INPUT positive Sensor 1 Brown Green Pink Grey DDS S 2 2 1 b Connecting two sensors Note Configure the following parameters Sensor 1 PULSE INPUT positive Sensor 2 PULSE INPUT negative Sensor 2 Br...

Page 8: ...positive Violet 2 2 4 CONNECTION TO ACTIVA OPERATOR FOR CLOSING PROTECTION Sensor Gris Note Configure the following parameters PULSE INPUT positive 2 2 2 CONNECTION TO VISIO OPERATOR FOR CLOSING PROTECTION Sensor Brown Green Pink Grey DDS S Note Configure the following parameter PULSE INPUT positive DDS S DDS S Brown Green Pink Grey Sensor Brown Green Pink ...

Page 9: ...ce between the inner curtain of the inside door sensor and the inner curtain of the outside door sensor should always be less than 20cm The distance up to the door leaf depends therefore on the thickness of the door leaf CLOSER FARTHER 2 4 OTHER SETTINGS Set the sensor by LCD or choose one of the presettings 1 STANDARD indoor mounting 2 CRITICAL ENVIRONMENT critical or outside installations 3 SHOP...

Page 10: ...sensor is ready for use 3 The door performs an opening manoeuvre 3 The door performs an closing manoeuvre 4 OK When the LED switches off the sensor is ready for use 5 2 5 1 QUICK SETUP 2 5 2 ASSISTED SETUP After SETUP check that the installation operates correctly before signing off on the setup process IMPORTANT After DDS S setup do a self learning procedure for door automation Visio ...

Page 11: ...ve output 2 6 2 FACTORY VALUE vs SAVED VALUE Displayed value Factory value Displayed value Saved value 2 6 3 NAVIGATING THE MENUS 2 6 4 CHANGING VALUES Press to access the menu 1 Enter password if required Not during the first minute after the detector comes ON 2 Scroll through the menu items 4 Select BACK to return to the previous menu or display 5 Select MORE to continue to the next level Basic ...

Page 12: ...l reset Standard factory values Critical Environment increased immunity IR FREQUENCY A B Detectors installed close together should have different frequencies Next ADVANCED MENU Back Back IR NUMBER Service mode 1 2 IR TPOMAXP Motion 15s 30s 1min 2 min 5 min 10 min 20 min 60 min infinite Next Back For conformity with EN 16005 DIN 18650 use values 6 y 7 at a mounting height 2 8m BS7036 for a mounting...

Page 13: ...witch the power supply OFF and ON again 2 If the LED comes on again replace the sensor RED Flashes rapidly after assisted setup The sensor sees the door during assisted SETUP 1 Check the angle of the infrared curtains 2 Perform another assisted SETUP Vacate the detection field Turns on sporadically The sensor vibrates 1 Check that the sensor is correctly installed 2 Check the position of the cable...

Page 14: ...TRICTED TO THE MANUFACTURER It is recommended to clean the optical parts whenever necessary and in any case at least once a year with a slightly damp cloth DO NOT use aggressive cleaning products 5 INSTALLATION CHECKLIST Check that the sensor has been firmly installed to avoid external vibrations Do not cover the sensor There are no moving objects or light sources in the detection field There are ...

Page 15: ...egulation 2004 108 CE Electromagnetic Compatibility Directive 2006 95 CE Low voltage Equipment Directive 2011 65 CE RoHS2 Directive It has also applied the following harmonised standards and technical specifications EN 16005 UNE EN 12978 AS 5007 DIN 18650 BS 7036 UNE EN ISO 13849 Performance level PL c Authorised representative MANUSA DOOR SYSTEMS Av Vía Augusta 85 87 6th Floor 08174 Sant Cugat de...

Page 16: ... Barcelona España Tel 34 902 321 400 Fax 34 902 321 450 www manusa com NOTE The characteristics detailed in this document are for information only and do not represent any contractu al obligation The manufacturer reserves the right to make modifications without prior warning Last revision July 2015 42 8445 V1 03 2015 ...

Reviews: