![Mannesmann Rexroth Indramat ECODRIVE DKC01.1 Project Planning Manual Download Page 97](http://html1.mh-extra.com/html/mannesmann-rexroth/indramat-ecodrive-dkc01-1/indramat-ecodrive-dkc01-1_project-planning-manual_701723097.webp)
ECODRIVE DKC01.1/DKC11.1 Drive Controllers
Power connection
11-5
DOK-ECODRV-DKC01/11.1*-PRJ3-EN-P
11.4 Protection against indirect contact
As a result of the high capacitive leakage currents via the cable insulation,
it is not possible to install a GFCB device in the power input line
(compliant to DIN VDE 0160, section 6.5).
Thus, protection against indirect contact must be achieved by other
means.
The drive system components have a protective grounded housing. This
makes protection against indirect contact possible by grounding.
Buy: www.ValinOnline.com | Phone: 844-385-3099 | Email: [email protected]