3-2
Selecting the components
ECODRIVE DKC01.1/DKC11.1 Drive Controllers
DOK-ECODRV-DKC01/11.1*-PRJ3-EN-P
3.2 Selection
procedure
⇒
Dimension the drive according to how it is to be used. A document for
this is under preparation.
⇒
Select motor/drive combination (DKC + MKD) using the "Selection
Data" documentation (see pg. 3, supplementary documentation)."
⇒
Enter the values obtained from dimensioning and enter the drives se-
lected into table Fig. 3-2 .
⇒
Calculate the continuous regenerative power according to the specifi-
cations in Chapter 5 and enter them in table Fig. 3-2 .
⇒
Use firmware "FWA-ECODRV-ASE-02VRS-MS" for DKC01.1-*** and
DKC11.1-*** (no selection required at this time)
⇒
"Select ready-made cables for the connection between the DKC and
MKD by using the document "MKD Servomotors - Project Planning
Manual" (see pg. 3 of supplementary documentation)."
⇒
Select fuse protector Q1 (see Chapter 11.2).
⇒
Select line contactor K1 (see Chapter 11.2).
⇒
Check the rated line voltage.
•
If, in the case of the DKC**.*-040-7, the rated line voltage falls below
or exceeds 3xAC (380-460)V
±
10%, select a DST transformer (see
Chap. 9.2).
•
If, in the case of the DKC**.*-030-3, the rated line voltage falls below
or exceeds 3xAC230V
±
10%, select a DST transformer (see Chap.
9.3).
⇒
Check the DC24V control voltage supply for the DKC. If a voltage of
DC24 Volt
±
20 % is not available, select a suitable NTM power supply
(see Chap. 7).
⇒
Check the DC24V voltage for the motor holding brake. If a voltage of
DC24 Volt
±
10 % is not available, then select a suitable NTM power
supply (see Chap. 7).
⇒
Check the continuous regenerative power. If it exceeds 0.15 kW, then
consider option with BZM auxiliary bleeder module (see Chap. 5).
⇒
Check the peak regenerative power. If it exceeds 5 kW, then consider
option with DKC**.*-040-7 and if needed, the BZM auxiliary bleeder
module (see chapter 5).
⇒
If the continuous regenerative power exceeds approx. 0.1 kW and the
drive system energy content is less than 200W, the use of an auxiliary
capacitance module CZM can be economical. This makes it possible
to reduce the dissipated energy for the control cabinet by an amount
equal to the continuous regenerative power (see Chap. 6).
⇒
Check the EMC conditions. INDRAMAT recommends the use of NFD
or NFE mains filters to maintain EMC limiting values (see Chap. 8).
Dimensioning and selecting the
servo drive
Compiling the required data
Selecting the required
components
Determining components which
may be additionally required