10-6
Mounting and installation
DKR Drive Controllers
DOK-DIAX03-DKR********-PR02-EN-P
10.2 Mounting the drive
DANGER
Lethal electric shock caused by live parts with
more than 50 V!
⇒
Switch power off to the control cabinet before
beginning work. Make sure that the power supply
switch cannot be unintentionally or inadvertently
switched back on.
⇒
Before starting work, an electrician must check,
using appropriate measuring equipment, whether
there is any residual voltage in the cabinet or in any
of the parts, e.g., from capacitors. Wait their
discharge time!
Before mounting the drive controller make the necessary dispositions,
such as:
•
threaded holes in mounting panel or back wall of cabinet and
•
matching fixing bolts.
•
Cooling with air outside:
vents in the back of the mounting.
•
cooling with duct:
vents in the back of the mounting. supports and flange, duct with 80
respectively 125 mm inside diameter.
Note:
Ducts are not included in the order. They must be ordered
separately and can be ordered from Rexroth Indramat upon
request.
•
Also make an appropriate lifting device available [for the respective
weight of the drive controller please see the technical data (chapter
4)].
1.
DKR04 only:
Anchor the mounting frame to the back wall of the
cabinet or the mounting frame using the included screws (see page 5-
15).
2. Screw the mounting screws into the mounting panel/back wall of
cabinet about 2/3 of the way in.
3. Hang the drive onto the mounting screws.
4. Tighten the screws. Note the maximum torque given for this
procedure.
5.
Only applies to the cooling method with duct:
Mount the supports and
flange for the duct connection to the cabinet at location indicated.
Secure the ducts.
Prerequisites
Mounting
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01