Discharge Pressure High Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist” on
Restricted Condenser Air Flow
• High inlet air temperature
• Condenser discharge air re-circulation
• Dirty condenser fins
• Defective fan cycling control
• Defective fan motor
Improper Refrigerant Charge
• Overcharged
• Non-condensable in system
• Wrong type of refrigerant
Other
• Non-Manitowoc components in system
• High side refrigerant lines/component restricted
(before mid-condenser)
Freeze Cycle Discharge Pressure Low Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist” on
Improper Refrigerant Charge
• Undercharged
• Wrong type of refrigerant
Other
• Non-Manitowoc components in system
• High side refrigerant lines/component restricted
(before mid-condenser)
• Defective fan cycle control
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.
Summary of Contents for STH042 4/16
Page 2: ......
Page 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 145: ......