VCDM

Volume control damper

Technical Documentation

Installation, Commissioning, Operation, Maintenance and Service Manual

TPM 167/23

Version 2023-02-14

Summary of Contents for VCDM

Page 1: ...dik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4UB United Kingdom Tel 44 117 4526376 E Mail help mandik co uk Authorized representative VCDM Volume control damper Technical Documentation Installation Commissioning Operation Maintenance and Service Manual TPM 167 23 Version 2023 02 14 ...

Page 2: ...Description 3 Design 4 Design with manual control 4 Dimensions 5 Technical parameters 6 Placement and Assembly 7 II TECHNICAL DATA 8 Pressure loss 8 Noise data level of acoustic output corrected with filter A 9 III MATERIAL FINISHING 10 Material 10 IV INSPECTION TESTING 10 V TRANSPORTATION AND STORAGE 10 Logistic terms 10 VI ASSEMBLY ATTENDANCE AND MAINTENANCE 11 Assembly 11 Entry into service and...

Page 3: ...es Dampers are suitable for systems without abrasive chemical and adhesive particles Dampers are designed for macroclimatic areas with mild climate according to EN IEC 60 721 3 3 ed 2 class 3K22 Temperature in the place of installation is permitted to range from 20 C to 50 C The Mandik VCDM is a volume control damper suitable for use at high temperatures The VCDM can be used to control and balance...

Page 4: ... damper VCDM Page 4 Version 2023 02 14 TPM 167 23 Design Design with manual control Design with manual control with which actuates the shutting device Design 01 Design 01 Damper blades is closed Damper blades is open ...

Page 5: ...ge 5 Version 2023 02 14 Volume control damper VCDM TPM 167 23 Dimensions 1 Damper body 2 Damper blade 3 Manual control Flange with corner hole Flanges of dampers are 30 mm wide with oval hole Damper VCDM ...

Page 6: ...0 4 38 0 0 2349 800 4 30 7 0 1413 800 4 40 5 0 2759 900 5 36 5 0 1575 900 5 44 5 0 3075 1000 5 38 5 0 1785 1000 5 47 0 0 3485 1100 6 41 6 0 1947 1100 6 50 9 0 3801 1200 6 43 6 0 2157 1200 6 53 4 0 4211 300 x 200 1 15 9 0 0369 500 x 200 1 19 2 0 0653 250 2 18 3 0 0439 250 2 22 2 0 0777 300 2 19 4 0 0569 300 2 23 5 0 1007 350 2 20 5 0 0699 350 2 24 8 0 1237 400 2 21 5 0 0829 400 2 26 1 0 1467 450 3 ...

Page 7: ...4 400 2 39 9 0 3381 450 3 36 8 0 2630 450 3 47 2 0 3668 500 3 38 4 0 3010 500 3 49 2 0 4198 600 3 41 7 0 3770 600 3 53 2 0 5258 700 4 49 8 0 4355 700 4 59 9 0 6074 800 4 53 1 0 5115 800 4 63 8 0 7134 900 5 58 5 0 5700 900 5 70 5 0 7950 1000 5 61 8 0 6460 1000 5 74 5 0 9010 1100 6 67 2 0 7045 1100 6 81 1 0 9826 1200 6 70 5 0 7805 1200 6 85 1 1 0886 900 x 200 1 25 8 0 1221 1200 x 200 1 30 8 0 1647 2...

Page 8: ... 120 2 3 4 5 6 7 8 9 10 11 12 B 200 400 600 800 1000 1200mm B 250mm B 300 450mm B 350 500 700 900 1100mm w m s Δps Pa II TECHNICAL DATA Pressure loss Determination of pressure loss by using diagram ρ 1 2 kg m3 Δps static pressure drop w air velocity in the free cross section AxB B height of the damper ...

Page 9: ...00 Total w m s 2 15 23 28 28 27 25 22 8 34 3 24 32 37 37 36 34 31 17 43 4 31 39 44 44 43 41 38 24 50 5 36 44 49 49 48 46 43 29 55 6 41 49 54 54 53 51 48 34 60 7 45 53 58 58 57 55 52 38 64 8 48 56 61 61 60 58 55 41 67 9 49 57 62 62 61 59 56 42 68 10 51 59 64 64 63 61 58 44 70 11 53 61 66 66 65 63 60 46 72 12 55 63 68 68 67 65 62 48 74 w air velocity in the free cross section AxB i e before blades f...

Page 10: ...lastic foil for protection during transport and must not be used for long term storage of the equipment Changes in temperature during transport may cause condensation of water vapour inside the packaging and thereby condisitions may arise inside the packaging that are suitable for corrosion of materials used in the equipment e g white corrosion on zinc coated items or mould on calcium silicate The...

Page 11: ...ns Before entering the dampers into operation after assembly and after sequential revisions checks and functionality tests After entering into operation these revisions must be done according to requirement set by national regulations In case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure that the damper is put in...

Page 12: ...ual product information see www mandik co uk MANDÍK a s Dobříšská 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4UB United Kingdom Tel 44 117 4526376 E Mail help mandik co uk Authorized representative ...