Page 9
Version 2022-12-20
SEDM - Smoke extraction damper - multi
TPM 156/22
■
The MDCM damper control module is connected on a bi
directional communication loop back to a control panel, typically
located at the FCC.
■
Each MDCM has a 230v local spur to power the damper actuator.
■
Up to 96x MDCM's can be connected on one loop and multiple
loops can be incorporated.
■
With an MA or AA system the MDCM's are mounted in a fire
rated and tested Ca-Si housing to BS EN1366-10.
■
The MDPM damper control module is a combined control
module and damper positioning module to provide a
balanced/3R position.
■
It is connected on a bi directional communication loop back to a
control panel.
■
Each MDPM has a 230v local spur for powering the damper
actuator, located at the FCC.
■
Up to 96x MDPM's can be connected on one loop and multiple
loops can be incorporated.
■
With an MA or AA system the MDPM's are mounted in a fire
rated and tested Ca-Si housing to BS EN1366-10.
OVERRIDE
MDCM
6 5 4 3 2 1 L N
N L
+ +
MOTOR
POWER
COMMS
S S - -
F1
S
5
S
6
S
4
S
3
S
2
S
1
C
O
M
M
S
O
P
E
N
C
L
O
S
E
D
C
O
M
M
A
N
D
L
L
N
L
+
S90C CONTROLLER
S90 mounted in an addressablesmoke
control damper control panel to BS
ISO 21927-9
Cable glands
Comms cable
Damper control module PCB mounted on plastic rail
Earth stud
230v 50hz 3A fused supply (by others)
Switches 6 core
Drive open / close 230v
Damper actuator
Power 3 core
Comms IN
Comms OUT
Communications loop cable CAT 3 or equivalent 1.5mm
2
2 core screened
MDCM
160mm x 160mm x 62mm deep steel
enclosure powder coated red - IP54
-
5
6
+
-
7
8
S
E
N
L L E
INSULATED
TERMINAL
USEAN
N
N
NCNO
6 5 4 3 2 1 L L
J7
N
NCNO
J7
OVERRIDE
MDPM
6 5 4 3 2 1 L L
+ +
J5
J1- COMMS
S S - -
F1
S
5
S
6
S
4
S
3
S
2
S
1
C
O
M
M
S
O
P
E
N
C
L
O
S
E
D
C
O
M
M
A
N
D
O
P
E
N
C
L
O
S
E
D
C
O
M
M
A
N
D
OVERRIDE
Cable glands
Comms cable
Switches 6 core
Drive open / close 230v
Damper actuator
Power 3 core
Comms IN
Comms OUT
Damper control module PCB
mounted on plastic rail
+
S90C CONTROLLER
S90 mounted in an addressablesmoke
control damper control panel to BS
ISO 21927-9
-
5
6
+
-
7
8
S
E
Earth stud
230v 50hz 3A fused
supply (by others)
Communications loop cable CAT 3 or equivalent 1.5mm
2
2 core screened
MDPM
230mm x 160mm x 62mm deep steel
enclosure powder coated red - IP54
Details of connection of the control module
interfaces inside protection box
Details of connection of the control module
interfaces inside protection box
Communication and control module MDCM
Communication and control module MDPM