SEDM - Smoke extraction damper - multi
Page 8
Version 2022-12-20
TPM 156/22
Actuator SCHISCHEK InMax 50.75-S
Actuator SCHISCHEK InMax 50.75-S
Actuator SCHISCHEK
InMax 50.75-S
Power voltage
24-240 VAC/DC
50/60Hz
Power consumption - motoring
- heating
10 W
16 W (start at -20°C)
Protection class
I
Degree of protection
IP 66
Adjustment time for 95°
< 60 s
Ambient temperature
Storage temperature
-40°C … +50°C
-40°C … +70°C
Connection
Cable 1 m, 0,5 mm
2
SCH
ISCH
EK-
50 /
75
N.m
1
2
3
4
24...230 VAC/DC
~
+
-
1 2 3 4 5 6
heater
PA
~
>85°
<5°
PE
Integrated aux. switches
max 24V/3A, 240V/0,25A switching
at 5° and 85°.
Extended leads are not possible with smoke control dampers
as the belimo cabls are not fire rated to a high Field wiring must
be brought into and terminated within the damper housing.
For more detail