Fire damper - FDMQ
Page 42
Version 2023-07-27
TPM 103/14
≥
100
A-A
4
0
..
.1
5
0
≥
150
⑤
A
A
50...150
5
0
..
.1
5
0
m
in
.
B
+
1
0
0
m
a
x
.
B
+
3
0
0
B
⑤
min. A+100
max. A+300
A
⑤
40...150
1
FDMQ
2
Gypsum wall construction
3
Solid ceiling construction
4
Mortar or gypsum
5
Mineral wool board - min. density 140 kg/m
3
(e.g. PROMAPYR-T150, ROCKWOOL HARDROCK / STEPROCK HD)
6
Duct
In gypsum wall construction - installation next to the wall/ceiling - mortar or mineral wool
■
For connection of following duct
Conditions of this installation are also valid for the installation in
Solid ceiling construction
■
Penetration is filled with mortar or mineral wool (shape, according to the location of the damper). Fix the mineral wool with
glue (e.g. Promat K84 or equivalent) to the construction and damper casing
EIS 90