background image

29

  Before commissioning the dampers and during their subsequent operational checks, it is necessary to check and

functionally test all the designs, including the operation of any electronic elements. Upon commissioning, these
operational  checks  must  be  completed  at  least  twice  a  year.  If  no  defect  is  found  during  two  consecutive
operational checks, then operational checks may be completed once a year.

   Prior  to  the  commissioning  of  the  dampers  and  subsequent  operational  checks,  the  following  checks  must  be

completed with all the designs:

 

Visual  inspection  for  proper  damper  installation,  damper  interior,  damper  blade,  blade  seating  surfaces,  and
silicone seal.
Removing the inspection opening cover:  Turn the wing nut to loosen the cover and move the cover left or right to

 

 

release it from the locking bracket. Then tilt the lid back from its original

 

position.

For dampers with mechanical control (designs .01, .11, .80), the following checks must be carried out:

Move the damper blade to "CLOSED" position as follows:

 

• 

The damper is in "OPEN" position.

 

• 

Press the control button of the mechanism to move the damper to "CLOSED" position.

 

• 

Check the damper blade shift to "CLOSED" position.

 

• 

Damper closing shall be sharp, the control lever shall be in „CLOSED“ position.

Move the damper blade to "OPEN" position as follows:

 

• 

Turn the control lever by 90°.

 

• 

The lever will automatically lock in "OPEN" position.

 

• 

Check the damper blade shift to "OPEN" position.

 

• 

To check the function and the status of the fuse is possible to remove whole mechanism from the body of fire

 

 

damper - mechanism is attached to the dampers body with four screws M6.

 

• 

Removing the thermal fuse from the fuse holder of initiation device, check its correct functionality.

 

• 

The mechanism is identified as M1 to M4, depending on the closing spring strongness.

The actuator design must be checked as follows:

 

The blade turn to its breakdown “CLOSED” position may be checked upon cutting off the actuator power supply
(e.g. by pressing the RESET button at the thermoelectric starting mechanism BAT or by cutting off the fire alarm
power supply). The blade turn back to its “OPEN” operating position may be checked upon restoration of power
supply (e.g. by releasing the RESET button or restoration of the fire alarm power supply).

Actuator control without electric voltage:

 

A special lever (part of the actuator) may be used to manually set the dampers to any position. When the lever is
turned  in  the  direction  of  the  arrow,  the  damper  blade  turns  to  its  open  position.    As  the  blade  movement  is
stopped, in every position, the actuator will be locked. Unlocking is possible even manually as per instructions on
the actuator, or by the activation of the supply voltage.

   Installation, maintenance, and operational checks of the dampers may only be completed by persons qualified for

these activities, i.e. “AUTHORIZED PERSONS: trained by the manufacturer.

 

The dampers must be installed in compliance with all the applicable safety standards and regulations.

Actuator reset after the fuses activation:

 

If the thermal protection fuse Tf1 (for the temperature around the fire damper) is burned, it is necessary to replace
the actuator, including the thermoelectric trigger.

 

If the thermal protection fuse Tf2 (for the temperature inside the piping) is burned, separate spare part ZBAT72 or
ZBAT95 may be replaced (according to the starting temperature).

Summary of Contents for FDMB

Page 1: ......

Page 2: ...eral stone wool min density 140 kg m 4 Fire protection mastic min thickness 1 mm 5 Duct Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 75...

Page 3: ...rials example 3 HILTI CFS F FX EIS 60 PROMAFOAM C EIS 45 SOUDAL Soudafoam FR B1 EIS 30 DenBraven Fire protection foam EIS 30 Position 1 Fire damper 2 Solid wall construction 3 Fire protection foam 4 S...

Page 4: ...n density 140 kg m 4 Fire protection mastic min thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Duct 100 Screws has to be fixed in wall ceiling construction If it is need...

Page 5: ...5 100 100 Position 1 Fire damper 2 Installation frame 3 Solid wall construction 100...

Page 6: ...terials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Position 1 Fire damper 2 Solid wall construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Duct D 60 to 800 max 2050 D 60 to...

Page 7: ...not limited 100 80 80 100 Insulation materials can be replaced by another approved fire sealing system with equivalent properties The maximum distance of the fire damper from the structure is not lim...

Page 8: ...s Depends on the distance of the flap from the construction when the maximum distance from the construct is not limited and according to EN 15882 2 must use the required number of hinges according to...

Page 9: ...5 Promastop P K Hilti CFS CT Installation opening has to be reinforced by steel U profile Profile is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm 100 75 Position 1...

Page 10: ...re protection foam EIS 30 Position 1 Fire damper 2 Gypsum plate 3 Mineral wool type depending on the type of construction 4 Fire protection foam 5 Stucco plaster 6 Duct Installation opening has to be...

Page 11: ...n density 870 kg m 7 Duct Around the perimeter 300 300 25 25 Screw min 4x50 Screws has to be fixed in wall ceiling construction If it is needed use steel bracket Used materials example 4 Promapyr Rock...

Page 12: ...ofile is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm Installation opening has to be reinforced by steel U profile Profile is fixed by screws 3 5 mm with corre spon...

Page 13: ...t board 5 Fire stop coating thickness 1 mm 6 Duct D 60 to 800 max 2050 D 60 to 800 max 1650 Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT 100 Installation opening has to be reinforc...

Page 14: ...80 mm ALU1 Position 1 Fire damper 2 Gypsum plate 3 Mineral wool type depending on the type of construction 4 Stuffing box mineral stone wool min density 140 kg m 5 Fire protection mastic min thickness...

Page 15: ...materials can be replaced by another approved fire sealing system for damper installation with equivalent material properties Depends on the distance of the flap from the construction when the maximu...

Page 16: ...tic min thickness 1 mm 5 Duct Around the perimeter min 110 Concrete min 125 Aerated concrete Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS C...

Page 17: ...ol Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 5 Promatect H Position 1 Fire damper 2 Solid ceiling construction 3 Stuffing box mineral stone wool min density 140 kg m 4 Fire pro...

Page 18: ...18 min 110 Concrete min 125 Aerated concrete Position 1 Fire damper 2 Installation frame 3 Solid ceiling construction...

Page 19: ...ncrete min 125 Aerated concrete Position 1 Fire damper 2 Solid ceiling construction 3 Fire resistant board 4 Fire stop coating thickness 1 mm 5 Duct Used materials example 3 Hilti CFS CT B 1S 140 50 4...

Page 20: ...nce from the construct is not limited and according to EN 15882 2 must use the required number of hinges according to EN 1366 1 2014 Reinforcement fixing VRM Installation of profile U25x40x25 When usi...

Page 21: ...21 30 100 75 750 Position 1 Fire damper 2 Solid ceiling construction 3 Concrete B20 4 Rebar 5 Duct Around the perimeter min 110 Concrete min 125 Aerated concrete 100 100...

Page 22: ...to be done on each corner of VRM For dampers with A 800 and damper placement outside wall construction is necessary to use reinforcement VRM 35 Screw 4 2x50 max 350 100 1 Cut the groove for profil U25...

Page 23: ...500x400 X 36 AxB 500x400 123 110 B B 60 A A 60 375 B X B 60 A X A 60 60 X 2 60 X 2 37 5 Position 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical...

Page 24: ...24 1 Damper 2 Mounting plate 3 Sealing cover 4 Seal plates 5 Mounting plate cover 6 Thermal fuse 7 Mechanics 8 Actuator 9 Temperature sensor 10 Sensor sticker...

Page 25: ...re the distance between the adjacent dampers must be at least 200 mm The damper blade in its closed position must be inside of the fire separating structure The fire damper may also be installed outsi...

Page 26: ...from the damper control parts At least one inspection hole must be accessible The damper body must not get deformed during its installation process Once the damper is built installed its blade must n...

Page 27: ...of dampers c a 16 5 30 16 5 10 2 0 10 20 10 8 5 10 10 8 5 20 X 2 16 5 30 X 2 16 5 10 2 0 X 23 AxB 500x400 X 36 AxB 500x400 140 165 190 5 215 15 220 20 240 30 255 40 265 52 5 290 65 295 80 15 315 90 4...

Page 28: ...ED 1 2 S3 S1 S2 S5 S4 S6 N L1 5 80 BAT Tf Tf LED AC 230V 5A IP 67 25 C 120 C 1 COM black wire 2 NC gray wire 4 NO blue wire This limit switch is possible to connect in following two versions a if the...

Page 29: ...pers body with four screws M6 Removing the thermal fuse from the fuse holder of initiation device check its correct functionality The mechanism is identified as M1 to M4 depending on the closing sprin...

Page 30: ...stos free fire resistant mineral fibre boards The damper control devices are made of galvanized materials alternatively of stainless steel without any additional surface finish The springs are galvani...

Page 31: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: