BOXER SERIES 10-20 KVA
EXPLANATIONS OF LOGGING
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
41
BYPASS Thyristor
L2 Short Circuit
UPS has detected short circuit at bypass L2 thyristor. UPS will
shut down.
42
BYPASSThyristorL3
Short Circuit
UPS has detected short circuit at bypass L3 thyristor. UPS will
shut down.
43
UPS ThyristorL1
Short Circuit
UPS has detected short circuit at inverter L1 thyristor. UPS will
shut down.
44
UPS Thyristor L2
Short Circuit
UPS has detected short circuit at inverter L2 thyristor. UPS will
shut down.
45
UPS Thyristor L3
Short Circuit
UPS has detected short circuit at inverter L3 thyristor. UPS will
shut down.
46
UPS ThyristorL1
Open Circuit
UPS has detected that inverter L1 thyristor cannot be activated.
Load will be transferred to bypass line.
47
UPS Thyristor L2
Open Circuit
UPS has detected that inverter L2 thyristor cannot be activated.
Load will be transferred to bypass line.
48
UPS Thyristor L3
Open Circuit
UPS has detected that inverter L3 thyristor cannot be activated.
Load will be transferred to bypass line.
49
BYPASS
ThyristorL1 Open
Circuit
UPS has detected that bypass L1 thyristor cannot be activated.
Load will be transferred to inverter line.
50
BYPASS
ThyristorL2Open
Circuit
UPS has detected that bypass L2 thyristor cannot be activated.
Load will be transferred to inverter line.
51
BYPASS
ThyristorL3 Open
Circuit
UPS has detected that bypass L3 thyristor cannot be activated.
Load will be transferred to inverter line.
52
Parallel System
Phase Sequence
Error
One or more of UPSs which operate in parallel mode do not match
in phase sequence.
53
Battery Start
UPS was given the command to start from the battery.
54
Parallel Start Error
One or more of UPSs which operate in parallel mode could not be
prepared to operate.
55
Inverter Error
UPS couldn't prepare the inverter voltage when it was started.
56
Output Off
Static transfer switches all disabled. The loads cannot be
energized.
57
Normal Mode
UPS is operating in the normal mode, loads are energized through
rectifier – inverter line.
58
Battery Mode
UPS is operating in the battery mode, loads are energized through
battery – inverter line.
59
Bypass Mode
UPS is operating in the bypass mode, loads are energized through
bypass line.
60
Maintenance Bypass
Mode
UPS is operating in the maintenance bypass mode, loads are
energized through maintenance bypass line.
61
Parallel Mode
2 or more UPS are operating in power sharing mode. Load is fed
through UPSs’ inverter lines.