5. POWER SUPPLY OPERATION

Mains fault (normal source) :

 signalled locally by a yellow LED and remotely by dry contact with delay (failsafe).

•  If the mains is not present or < 195 V.

•  If the mains fuse is blown or not present.

•  If the product is out of service.

Battery fault (emergency power) :

 signalled locally by a yellow LED and remotely by dry contact with delay (fail-

safe).

• 

If the battery is not present : The battery test is performed in the following manner: every 30 seconds for the first 20 

minutes after commissioning : every 15 minutes after the first 20 minutes. If a fault is detected, the test is performed 

every 30 seconds up to 20 minutes after the fault disappears. 

• 

If the internal impedance is too high (test every 4 hours maximum on a charged battery).The impedance limit 

value is :

•  If the battery voltage :

No voltage on one of the Outputs :

 signalled locally by a yellow LED and remotely by dry contact with delay (fail-

safe).

5.1 ALARMS

5.2 SUMMARY OF AVAILABLE EQUIPMENT

Temperature compensation :

A battery voltage compensation system maintains the charge characteristics within the limits specified by the

battery manufacturer across the entire operational temperature range.

Battery low voltage cut-out :

The cut-out threshold is :

The element causing the cut-out will be in the + position.

AES24V MS40

AES24V MS150

21.6V ±3 %

1.8 V/cell ±3 %

AES24V MS40

AES24V MS150

< 21.6V+/-3%.

< 1.8V/élt+/-3%.

AES24V MS40

AES24V MS150

50m

Ω

+/-10%.

13m

Ω

+/-10%

Summary of Contents for AES24V MS40

Page 1: ...l a Fl a mb re 31300 To u l o u s e FR ANCE T l 33 0 5 61 31 86 87 Fax 33 0 5 61 31 87 73 co mmerc i a l ma j o rco m fr w w w majorcom fr User manual AES24V MS40 AES24V MS150 POWER SUPPLY UNITS USER...

Page 2: ...d EMC directives immunity and emission It is compliant with standards EN60950 1 2006 EN61000 6 1 2007 EN61000 6 2 2006 EN61000 6 3 2007 EN61000 6 4 2007 and EN 55022 class B 2007 It is also compliant...

Page 3: ...tage Default 1 2 3 Model AES24V MS40 AES24V MS150 Power voltage 195 264VAC 50 60Hz Primary Current 1A 195VAC 2A 195VAC Breaker Circuit D curve need to be provided Upstream Model AES24V MS40 AES24V MS1...

Page 4: ...e battery mesh every 4 hours The trigger threshold of the fault is 50 m 10 The trigger threshold of the fault is 13 m 10 Exceeding this threshold is signalled by a battery fault and means that the pow...

Page 5: ...User manual User manual 4 COMMISSIONING Connect the battery wires to the terminal strip but do not connect the battery terminals After the electrical connections are made mains loads and batteries 1...

Page 6: ...ry test is performed in the following manner every 30 seconds for the first 20 minutes after commissioning every 15 minutes after the first 20 minutes If a fault is detected the test is performed ever...

Page 7: ...ed clean and ensure that it is installed in a dry and ventilated location We shall in no case be liable for damages associated with improper use or incorrect maintenance of the equipment WARNING Repla...

Page 8: ...or equal to 11 5 Vdc Repeat the measurement after having disconnected the load and the battery Recheck the signalling of the indicator lights see chapter 5 If all the steps are validated check the co...

Page 9: ...a Fl a mb re 31300 To u l o u s e FR ANCE T l 33 0 5 61 31 86 87 Fax 33 0 5 61 31 87 73 co mmerc i a l ma j o rco m fr w w w majorcom fr AES24V MS40 AES24V MS150 POWER SUPPLY UNITS User manual MAJORC...

Reviews: