background image

62D4037

39

MASSACHUSETTS RESIDENTS ONLY:

PLEASE READ AND FOLLOW THESE 

SPECIAL REQUIREMENTS

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed pluber or gas fitter when installed iwthin the common-
wealth of Massachusetts.
Any residence with a direct vent product must have a CO detector installed in the residence.
installation of the fireplace or vented gas log ins the State of Massachusetts requires the damper to 
be permanently removed or welded in the fully open position.
In additin, a naturally vented gas log may not be installe din a abedroom or bathroom int eh state 
of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shut-off valve.

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter when instaled within the Com-
monwealth of Massachusetts.
In addition, vent free products may not be installe din a abedroomm or bathroom regardles sof size 
or type in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2)  Revise 10.8.3 by adding the following additional requirements:
(a)  For all side wall horizontally vented gas fueled equipemnt installe din every dwelling, building or 

structure used in whole or in part for residential purposes, including those owned or operated 
by the Commonwealth and where the side wall exhaust vent termination is less than seven 
(7) feet above finished grade int he area of the venting, inlcuding but not limited to decks and 
porches, the follwing requirements shall be satisfied:

1.  INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the 

side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall 
observe that a hard wired carbon monoxide detector with an alarm is installed on each 
additional level of the dwelling, building or structure served by the side wall horizontally 
vented gas fueled equipment. It shall be the responsibility of the property owner to secure 
the  services  of  qualified  licensed  professionals  for  the  installation  of  hard  wired  carbon 
monoxide detectors.
a.  In the event that the side wall horizontally vented gas fueled equipment is installed in a 

crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery 
back-up may be installed on the next adjacent floor level.

b.  In the event that the requirements of this subdivision can not be met at the time of 

completion of installation, the owner shall have a period of thirty (30) days to comply 
with the above requirements; provided, however, that during said thirty (30) day period, 
a battery operated carbon monoxide detector with an alarm shall be installed.

2.  APPROVED  CARBON  MONOXIDE  DETECTORS.  Each  carbon  monoxide  detector  as 

required in accordance with the above provisions shall comply with NFPA 720 and ANSI/UL 
2034 listed and IAS certified.

3.  SIGNAGE.  A  metal  or  plastic  identification  plate  shall  be  permanently  mounted  to  the 

exterior of the building at a minimum height of eight (8) feet above grade directly in line 
with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or 
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, 

“GAS 

VENT DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.

Summary of Contents for 400BBV

Page 1: ...taller service agency or the gas supplier WARNING Improper installation adjustment alteration services or maintenance can cause injury or property damage Refer to this man ual For assistance or additi...

Page 2: ...ecautions 14 Installation Planning 14 Outside Combustion Air Precautions and Rec ommendations 16 Combustion Air Assembly 17 Fireplace Installation 18 Check Gas Type 18 Installing Gas Piping to Firepla...

Page 3: ...rformance problems do not use propane LP fuel tank of less than 100 lbs capacity 3 If you smell gas shut off gas supply do not try to light any appliance do not touch any electrical switch do not use...

Page 4: ...not intended for use with a thermo stat 22 This appliance must be installed with draft hood in same atmospheric pressure zone as the combustion air inlet to the appliance 23 For Massachusetts Resident...

Page 5: ...ion code ANSI Z223 1 NFPA 54 in the US and CSA B149 in Canada The appliance must be properly connected to a venting system The appliance is not approved for closet or recessed installations Gas Contro...

Page 6: ...0 Min BTU hr Input 16 000 14 500 16 500 16 300 19 000 20 000 Burner Ori ce size as shipped 43 55 41 53 37 52 BEFORE YOU START Read this homeowner manual thoroughly and follow all instructions carefull...

Page 7: ...priate height When the rebox is installed directly on carpeting tile or other combustible material other than wood ooring the rebox shall be installed on a metal or wood panel extending the full width...

Page 8: ...raming Dimension 14 1 2 or 5 8 Drywall Spacers 1 2 or 5 8 Drywall Spacers 8 9 Air Kit 16 7 Electrical Gas Access 2 40 40 Framing Dimension 21 34 6 B C D Framing Dimension 624037 400 BBV dims 10 08 4 B...

Page 9: ...f the gas knock out hole lo cated at the bottom of the left side NOTE 400SBV 500SBV A 24 30 B 36 42 C 40 46 D 40 46 A 21 Framing Dimension 21 13 6 1 2 or 5 8 Drywall Spacers 1 2 or 5 8 Drywall Spacers...

Page 10: ...k and windows Minimum clearances to combustibles must be maintained This replace may be installed along a wall across a corner or use an exterior chase Location should be out of high traf c areas and...

Page 11: ...not be installed on a carpet tile or other combustible material other than wood ooring If installed on carpet or vinyl ooring the appliance shall be installed on a metal wood or noncombustible materia...

Page 12: ...screws to secure replace to the oor Use four 4 screws to attach replace to framing The side brackets are adjustable from 1 2 to 5 8 to accommodate different thicknesses of material Framing 1 2 Nail F...

Page 13: ...his may create a re hazard Only noncombustible materials i e brick tile slate steel or other materials with a UL re rating of Zero may be used to cover the black surface of the appliance A 300 F minim...

Page 14: ...us injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious injury property damage or loss of life NOTICE Failure to follow these...

Page 15: ...stop in Ceiling When installing in a chase you should insulate the chase as you would the out side walls of your home This is especially important in cold climates Insulation should be considered a co...

Page 16: ...sure the location cannot be accidentally blocked Locate assembly above snow line to prevent snow from blocking assembly 3 Never mount combustion air inlet assem bly in garage or storage area where co...

Page 17: ...th a standard pocket knife Figure 14 WARNING DO NOT remove the cover if the outside air will not be connected WARNING Do not use a combustible duct Always use UL Listed Class 0 or 1 duct material If n...

Page 18: ...m regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 16 Pointing the vent down protects it from freezing rain or sleet WARNING A quali ed installer...

Page 19: ...the replace Check your building codes for any special requirements for locating equipment shut off valve to replaces Apply pipe joint sealant lightly to male threads This will pre vent excess sealant...

Page 20: ...gas meter to the replace for leaks Use a solution of 50 50 water and soap or a gas sniffer 4 To adjust ame height turn HI LO knob to HI to get maximum pressure to burner Turn HI LO knob to LO to get...

Page 21: ...d only be performed by a quali ed licensed electrician Main power must be off when connecting to main electrical power supply or performing service All wiring shall be in compliance with all local cit...

Page 22: ...ion the wall switch Do not extend beyond the 15 of wire OPTIONAL DC REMOTE SYSTEMS These instructions replace the section entitled Hearth Mount in the Millivolt hand held remote in structions supplied...

Page 23: ...rear log 1 on grate assembly Log should rest rmly on the two log mounting pins on the hori zontal bars Figure 22 2 Place bottom left log 2 on grate Rest the back side of the log in the at area of the...

Page 24: ...Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it Call a quali ed service technician Force or attempted re...

Page 25: ...using a soap and water solu tion to test for leaks DO NOT spray solution onto control body DANGER Never check for gas leaks with open ame NOTE Remove any excessive pipe compound from the connec tions...

Page 26: ...he ON posi tion to light the main burner Figure 24 LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position Fig ure 25 It will take less than four 4 seconds for the burner to...

Page 27: ...of it has been under water Immediately call a quali ed service technician to inspect the appliance and to replace any pat of the control system and any gas control that has been under water LIGHTING E...

Page 28: ...e pilot ame must always be present when the replace is in operation Figure 29 The pilot ame has three distinct ames one engul ng the thermopile one engul ng the thermo couple and the other reaching to...

Page 29: ...with a brush attachment If logs must be removed for cleaning handle carefully by holding gently at each end Gloves are recom mended to prevent skin irritation from ceramic bers If skin becomes irrita...

Page 30: ...62D4037 30 ILLUSTRATED PARTS LIST FIREBOX COMPONENTS 4a 4b 4c 1 2 3 5 6 7...

Page 31: ...ctory 1 n a 62D1017 62D2017 Optional Field Installed Accessoriesd 5 Firebrick Assembly 1 F400BBVW n a n a 6 Outside Air Kit 1 OAC4 OAC4 OAC4 7 Black Glass Door Assembly 1 GD36BA GD36BA GD36BA 7 Polish...

Page 32: ...62D4037 32 ILLUSTRATED PARTS LIST STANDING PILOT MILLIVOLT CONTROL 1 2 3 4 5 6 7 8 10 12 13 2T 2I 2C 9 11...

Page 33: ...0048 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 7 Injector 1 62D3006 62D3005 62D3004 20H3143 62D3003 59D0094 8 Burner Assembly 1 54D0200 54D0200...

Page 34: ...62D4037 34 ILLUSTRATED PARTS LIST ELECTRONIC IGNITION 1 2 3 4 5 6 7 9 8 10 11 12...

Page 35: ...23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Injector 1 62D3006 62D3005 62D3004 20H3143 62D3003 62D0094 7 Burner Assembly 1 54D02...

Page 36: ...the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one mil livolt lead wire on the tip of the thermocouple and the other meter lead wire on the thermocouple co...

Page 37: ...heck electrical connections between module and pilot operator on gas control C Check for 24VAC across PV MVPV terminals If voltage is correct replace gas control If voltage is not correct replace modu...

Page 38: ...age or restriction in venting ACTION A Install log set per instructions Inspect the injector and air intake area Make sure this area does not have any blockage from debris and clean Check gas supply A...

Page 39: ...he follwing requirements shall be satis ed 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gas...

Page 40: ...ions provided by the manufacturer for installation of the equipment and the venting system shall include 1 Detailed instructions for the installation of the venting system design or the venting system...

Page 41: ...62D4037 41 NOTES...

Page 42: ...62D4037 42 NOTES...

Page 43: ...Warranty will also be void if the appliance is not operated and main tained according to the operating instructions supplied with the appliance and does not extend to 1 rebox burner assembly damage by...

Page 44: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com OCTOBER 2008 62D4037 Rev 10...

Reviews: