For Models:

WMC36

WMC42

For use in U.S./Canada
Underwriter's Laboratories 
Report No. MH6018

DO NOT DISCARD THIS MANUAL:  Retain for future use.

20000583  8/08  Rev. 22

FP583A

WMC

12/18/98

WMC Series

 

Woodburning Fireplaces

Homeowner's Installation 

and Operating Manual

Summary of Contents for WMC36

Page 1: ...e in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 8 08 Rev 22 FP583A WMC 12 18 98 WMC Series Woodburning Fireplaces Homeowner s Inst...

Page 2: ...d by MHSC in combination or assembly with a MHSC re place system notwithstanding any indepen dent testing laboratory or other third party ap proval of such component parts or accessory Any such action...

Page 3: ...Dia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series speci cations and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt 1 6 m m 13mm 36 914mm 35 895mm 40 1016m...

Page 4: ...Surround Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...be at least 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak...

Page 7: ...If you live in a cold climate it is not required but highly recommended that you insulate replace enclosure to eliminate cold air penetration as much as possible Insulate base of replace with a nonco...

Page 8: ...ns Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V swit...

Page 9: ...ows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to ins...

Page 10: ...frame for ceiling chimney hole FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for install...

Page 11: ...e clearly snap together Once sections are snap locked in place it is extremely dif cult to get them apart Make sure the pipe is rmly snapped and locked together as each pipe section is mounted When in...

Page 12: ...raming hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Co...

Page 13: ...himney sec tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chas...

Page 14: ...SC Wall Shield Model SP40 or a speci cally built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and can be...

Page 15: ...manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R valu...

Page 16: ...ted material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in...

Page 17: ...and tube NOTE Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from replace side NOTE When installing an ANSI Z21 11 2 ventless appli...

Page 18: ...lace 7554338 7554338 6 Damper Knob Wood 7536177 7536177 7 Screen Pulls two per replace 5584139 5584139 8 Firebrick Left Side 3041104 3034102 9 Firebrick Back 3030102 3034104 10 Firebrick Right Side 30...

Page 19: ...may void the coverage provided by the owner s insurance Accessories Contact your MAJESTIC distributor or dealer for nishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold...

Page 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Inc...

Page 21: ...the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclos...

Page 22: ...22 WMC Series Woodburning Fireplace 20000583...

Page 23: ...dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your local build...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...