11. Electrical connection, Unit settings │ UK
30
a:
DIP-switch 7 Off (humidity control 5%))
DIP switches 1 to 6: Levels 0 to 14
Level
1 2 3 4 5 6 7 8
0: Absent
o
1: Low
o o
2: Low
● o
3: Normal
o o o o
4: Normal
● o o o
5: Normal
o ● o o
6: Normal
● ● o o
7: Normal
o o ● o
8: Normal
● o ● o
9: Normal
o ● ● o
10: Normal
● ● ● o
11: High
o o o
12: High
● o o
13: High
o ● o
14: High
● ● o
● = On, o = Off
a:
Performance data when DIP switch 7 = Off
Level
Volume
flow
[m³/h]
Pres-
sure
[Pa]
Power
[W]
0: Absent
45
5
2
1: Low
70
10
3
2: Low
85
14
4
3: Normal
150
46
7
4: Normal
171
62
9
5: Normal
197
81
12
6: Normal
222
101
50
7: Normal
245
123
20
8: Normal
270
150
27
9: Normal
293
175
32
10: Normal
316
205
38
11: High
245
123
20
12: High
295
177
33
13: High
318
208
40
14: High
342
241
50
b:
DIP- switch 7 On (humidity control 10 %)
DIP- switches 1 to 6: Levels 0 to 14
Level
1 2 3 4 5 6 7 8
0: Absent
●
1: Low
o
●
2: Low
● ●
3: Normal
o o
●
4: Normal
● o ●
5: Normal
o ● ●
6: Normal
● ● ●
7: High
o o o
●
8: High
● o o ●
9: High
o ● o ●
10: High
● ● o ●
11: High
o o ● ●
12: High
● o ● ●
13: High
o ● ● ●
14: High
● ● ● ●
● = On, o = Off
b:
Performance data when DIP switch 7 On
Level
Volume
flow
[m³/h]
Pres-
sure
[Pa]
Power
[W]
0: Absent
58
3
2
1: Low
83
9
4
2: Low
138
14
5
3: Normal
165
20
6
4: Normal
215
34
10
5: Normal
271
53
16
6: Normal
324
77
25
7: High
298
65
29
8: High
353
92
31
9: High
381
107
38
10: High
405
121
45
11: High
428
134
52
12: High
452
149
60
13: High
475
163
69
14: High
502
184
82