UK │ 6. Product information
26
6. Product information
● Ventilation unit with humidity sensor and
humidity control.
● The ventilation unit runs continuously. It
does not have an on/off switch.
● Ventilation levels: absent (energy save
mode), low, normal and high.
● Automatic operation with humidity control.
● Speed of low, normal and high levels can
be set using DIP switch (total of 28 pos-
sible selections).
● 5 possible exhaust air sockets, consisting
of 3x Ø125 mm, 1x Ø125/Ø160 mm, 1x
Ø160 mm (knockout points) and 1x Ø125
mm outgoing air socket.
● Permissible connection ducts: Ø125 mm or
Ø160 mm folded spiral-seams ducts.
● Supply air inlet by means of decentralised
outside air openings, e.g. with ZE supply
air element (
Internet).
● In the event of thermal overload, the
integrated motor overload protection
switches the unit off. Once cooled, the unit
starts back up again automatically.
● Unit with speed-controllable, EC DC motor.
● Wireless remote controls (max. 20 pieces)
are registered at the ventilation unit
(
Chapter 12).
ZEG2 EC-FB Remote control
● Remote control with setting buttons: Ab-
sence (energy-save mode), low/normal/high
levels, automatic and timer
Fig. A.
● LED status display.
● In
Timer operation
, the ventilation unit runs
for the selected time (15/30/60 minutes) at
the high level. Then it returns to the
previously selected ventilation level.
Cancel by pressing another button.
● In
Automatic operation,
the ventilation
unit controls the ventilation level according
to the measured values from the humidity
sensor.
●
Humidity control
in automatic operation.
The unit runs at a lower speed until a
significant increase in the relative humidity
is measured in the exhaust air.
If the humidity increases by 5% or 10%
within 3 minutes (value can be set with DIP
switch 7), the unit switches from low to
normal or high level (speed depends on the
setting of DIP switch 7).
If there is a noticeable drop in the humidity
level, the unit runs for 15 or 30 minutes at
normal or high level (overrun time is set
through DIP switch 8). It then switches
back to low level.
● If Absence mode is activated, the
ventilation unit runs in energy save mode
and doesn’t react to the humidity sensor.
7. Technical data
Installation permissible in all areas
compliant with DIN VDE 0100-701.
For technical data
rating plate [T].
For dimensions and characteristic
curves
Catalogue or Internet
(maico-ventilatoren.com).
ZEG2 EC
Rated voltage
230 V
Power frequency
50 Hz
Current input
0.8 A
Power consumption, max.
85 W
Degree of protection
IP 20
Housing sound power level
L
WA2
(min./max.)
28 dB(A)
55 dB(A)
Max. distance between
ventilation unit and remote
control (depending on building
circumstances)
Up to 20 m,
(only 1 floor)
Frequency range
(in acc. with EN 300220-1)
868.3 MHz
Dimensions (HxWxD)
Height with connection socket
430 x 443 x
303 mm
463 mm
Weight
4.4 kg