7 Safety instructions and warnings

 | UK 

27

Risk of death from carbon monoxide 

when operating with air-ventilated 

fireplaces.

Ensure sufficient supply air intake during 

operation with air-ventilated fireplaces. Note 

maximum permissible pressure difference per 

residential unit. The consent of a professional 

chimney sweep is needed in all cases.

Ventilation units may only be installed 

in 

rooms, apartments or housing units of a com

-

parable size, in which air-ventilated fireplaces 

are installed if:
● a parallel operation of air-ventilated fire

-

places for liquid or gaseous fuels and the

air-extracting equipment can be prevented

via safety devices, or

● the extraction of exhaust gas from the

air-ventilated fireplaces is monitored by

special safety equipment. In the case of

air-ventilated fireplaces for liquid or gas

-

eous fuels, the fireplace or the ventilation

system must be switched off if the safety

device is triggered.

In the case of air-ventilated fireplaces for

solid fuels, the ventilation system must be

switched off if the safety device is triggered.

In order for ventilation systems (equipped with 

central ventilation units with heat recovery) to 

be operated as intended, it must be possible 

to close off any combustion air ducts or ex

-

haust gas ducts from air-ventilated fireplaces 

while the fireplaces are not being used.
For exhaust gas ducts of fireplaces for solid 

fuels, the shut-off device may only be operat

-

ed by hand. It must be possible to identify the 

position of the shut-off device from the setting 

of the operating handle. This is considered 

to be fulfilled if a soot blocking device is 

deployed.

Ventilation units must not be installed 

if there are air-ventilated fireplaces in the 

housing unit that are connected to exhaust 

gas systems, which themselves have multiple 

connections.

Explanations of safety devices

The safety device is checked for electronic 

and functional safety using the safety objec

-

tives of DVGWVP 121. A product standard 

based on this exists in the form of  

E DIN 18841:2005-12.

Fire protection requirements

In terms of the fire protection installation 

requirements for setting up the ventilation 

system, note the state regulations, especially 

the official guideline on fire protection require

-

ments of ventilation systems in its most recent 

version.

Exercise caution when handling 

packaging materials. 

 Observe 

applicable safety and accident prevention 

requirements. 

 Store packaging material out 

of the reach of children.

Vapours from enthalpy heat exchang-

er. 

Possible odours come from the 

installed components and pose no risk to 

health. They disappear after a short while. 

Development of odours in the beginning is 

due to the new components and does not 

constitute grounds for a complaint.

8 Requirements at the installation 

site

 

● Ambient tempe 10 °C to + 40 °C.

 

Space of at least 70 cm in front of/below the

unit.

 

Note the space needed for additional com-

ponents.

Summary of Contents for WS 300 Flat

Page 1: ...or download www maico ventilatoren com For more information consult the commissioning and maintenance instructions Unit can also be operated using APP or WebTool Quick start guide Read these instructi...

Page 2: ...2...

Page 3: ...Nicht f r andere Betriebs systeme zugelassen wie z B f r Mac OS Mac OS ist Marke der Apple Inc USA PC Mindestanforderungen Windows Vista SP2 inkl Microsoft Net Framework 4 5 Prozessor mit 1 GHz 2 GB R...

Page 4: ...e f r optionales KNX oder EnOcean Steck modul Schnittstelle S01 f r Kommunikation zu optionalen Steckmodulen mit KNX Geb udeleittechnik bzw EnOcean Funkkomponenten 4 4 Optionale Zusatzplatine Zusatzpl...

Page 5: ...zum K hlen der Raumluft in der warmen Jahreszeit 18 Befestigungsblech W rmetauscher Befestigungsblech drehbar Je 2 St ck W rmetauscher 19 Abluft Fortluftventilator F rdert verbrauchte Luft nach drau...

Page 6: ...sger t ist ausschlie lich f r den h uslichen Gebrauch und hnliche Zwecke vorgesehen Eine andere oder dar ber hin ausgehende Benutzung gilt als nicht bestim mungsgem 7 Sicherheitshinweise und Warnungen...

Page 7: ...uftfeuchte 70 kurzzeitig bis ca 80 r F m glich einsetzen zum Beispiel in Schwimmb dern oder zum Austrocknen von Neubauten Das L ftungsger t besitzt keinen Kondensatablauf und wird durch berm ig anfall...

Page 8: ...orschriften einhalten Zul ssige H chstbelastbarkeit von Hebe werkzeugen beachten Vorsicht beim Anheben Transportgewicht bis zu 50 kg und Schwerpunkt des L ftungs ger tes mittig beachten Ger t nur mit...

Page 9: ...ausschalten und gegen Wieder einschalten sichern Ein Warnschild sichtbar anbringen Gefahr durch elektrischen Schlag Brand oder Kurzschluss bei Nichtbeachtung der geltenden Vorschriften f r Elektroinst...

Page 10: ...sein Bei Abgasanlagen von Feuerst tten f r feste Brennstoffe darf die Absperrvorrichtung nur von Hand bedient werden k nnen Die Stellung der Absperrvorrichtung muss an der Einstellung des Bedienungsg...

Page 11: ...htungsplan Kapitel 14 bis 18 ModBus optional Nur wenn kein Komfort BDE Touchscreen BDE RLS T1 WS ange schlossen und die Parametrierung mit der Inbetriebnahmesoftware erfolgt ist Mit bis zu 5 Einfach B...

Page 12: ...anbringen 2 L ftungsger t mit geeignetem Befesti gungsmaterial fest mit der Decke ver schrauben C Universalbefestigungswinkel Art Nr 0092 0567 1 Die 4 Befestigungswinkel seitlich an den Geh useblechen...

Page 13: ...len 8 Elektrischen Anschluss vornehmen An schlussleitungen gem Verdrahtungsplan in Kapitel 14 bis 18 elektrisch verdrahten F r Anschlussvarianten der Zusatzkompo nenten Montageanleitung des Zubeh rs 9...

Page 14: ...14 DE 14 Verdrahtungsplan Hauptplatine 14 Verdrahtungsplan Hauptplatine...

Page 15: ...ensor Sicherheitseinrich tung mit potentialfreiem Kontakt 12 VDC 2 A W4 Anschlussleitung bauseitig f r externe Sicherheitseinrichtung Sicherheitseinrichtung mit potential freiem Kontakt 230 VAC 16 A W...

Page 16: ...seitig externer CO2 Sensor 2 z B LIYY 3 x 0 5 mm W10 Anschlussleitung bauseitig externer Sensor 3 z B LIYY 3 x 0 5 mm W11 Anschlussleitung bauseitig externer Sensor 4 z B LIYY 3 x 0 5 mm Die Sensorein...

Page 17: ...16 Verdrahtungsplan Schadgassensor DE 17 16 Verdrahtungsplan Schadgassensor A L ftungsger t WS 300 Flat A1 Elektronikeinschub A2 Steuerung KWL 2015 GS Schadgassensor am Kombialarm...

Page 18: ...0 19200 Daten Bits 8 Parit t Even Stop Bits 1 Adresse 10 Grundeinstellung Bei im Parametermen deaktiviertem Kom fort BDE Touchscreen BDE RLS T1 WS k nnen die Anschlussklemmen am Klem menblock RS 485 a...

Page 19: ...die Einbindung des KWL Ger tes in eine GLT Die poten tialfreien Kontakte des Aktors m ssen zum Schalten von 12 VDC ausgelegt sein Ethernet USB A2 A A1 X10 Digital RS485 X11 X12 Sensoren RLS X13 3 3 S...

Page 20: ...ssioning and maintenance instruc tions Scan the QR code with your smartphone tablet and load the commissioning and maintenance instructions onto your PC notebook Alternatively you can download the ins...

Page 21: ...in module Interface S01 for communication with optional plug in modules featuring KNX building control technology and or EnOcean wireless components 4 4 Optional additional circuit board Additional c...

Page 22: ...m months of the year 18 Fixing plate Heat exchanger fixing plate can be rotated 2 of each heat exchanger 19 Exhaust air outgoing air fan Conveys used air to the outside 3 1 Additional circuit boards o...

Page 23: ...ilation unit is only intended for do mestic use and similar purposes No other or additional use is intended 7 Safety instructions and warnings Warnings Symbols meaning DANGER Indicates a possibly haza...

Page 24: ...t cannot be removed The surroundings may also be damaged by water escaping Corrosion of metal parts inside the ventilation unit due to additional com ponents in the exhaust duct Do not use components...

Page 25: ...gravity of ventilation unit centre Only carry the unit together with several persons and fix it to the ceiling Dimensions LxWxH in mm 1500 x 700 x 300 mm Do not stand under a suspended load Check unit...

Page 26: ...ing acciden tally switched back on again Attach a warning sign in a clearly visible place Danger from electric shock fire or short circuiting when failing to comply with the relevant regulations for e...

Page 27: ...of fireplaces for solid fuels the shut off device may only be operat ed by hand It must be possible to identify the position of the shut off device from the setting of the operating handle This is co...

Page 28: ...arm display filter change dis play operating display supplementary heat ing PTC heat register external shutter brine EHE unregulated pump cooling function wiring diagram chapters 14 to 18 ModBus optio...

Page 29: ...the customer Note weight of 50 kg A Threaded rods provided by customer 1 Mount threaded rods on the ceiling 2 Fit ventilation unit and secure to prevent it from falling B Optional Ceiling fixing brac...

Page 30: ...nic slide in module and attach it 5 Install optional additional circuit board s ZP 1 and or ZP 2 in slots and connect with connecting cables provided Check DIP switch settings and adjust if necessary...

Page 31: ...cure against being accidentally switched back on and position a visible warning sign i Professional disposal avoids detrimen tal impact on people and the environ ment and allows valuable materials to...

Page 32: ...t control B1 Simple control unit RLS 1 WR B2 B5 Parallel connection max 5 simple control units BT1 Touchscreen control unit RLS T1 WS W1 Connecting cable 230 V AC W2 Screened control cable simple cont...

Page 33: ...ntact 230 VAC 16 A W6 Connection cable provided by customer for multi function contact Potential free relay contact 230 VAC 5 A or 30 VDC 5 A W8 Connection cable provided by customer for external sens...

Page 34: ...ilation sensor type digital e g LIYY 2 x 0 5 mm W9 Connecting cable provided by customer for external CO2 sensor 2 e g LIYY 3 x 0 5 mm W10 Connecting cable provided by customer for external sensor 3 e...

Page 35: ...harmful gas sensor UK 35 16 Wiring plan of harmful gas sensor A Ventilation unit WS 300 Flat A1 Electronic slide in module A2 Controlled domestic ventilation unit control 2015 GS Harmful gas sensor on...

Page 36: ...19200 Data bits 8 Parity Even Stop bits 1 Address 10 basic setting If the comfort control unit is deactivated in the parameter menu touchscreen control unit RLS T1 WS the connection terminals on the...

Page 37: ...s the controlled do mestic ventilation unit to be integrated in a building control technology The actuator s potential free contacts must be configured for switching 12 VDC Ethernet USB A2 A A1 X10 Di...

Page 38: ...s sys t mes d exploitation tels que Mac OS Mac OS est une marque de Apple Inc USA Configuration minimum du PC Windows Vis ta SP2 y compris Microsoft Net Framework 4 5 processeur avec RAM de 1 GHz 2 Go...

Page 39: ...ean en option Interface S01 pour la communication vers les modules enfichables op tionnelles avec la gestion technique du b timent domotique KNX ou des composants radio EnOcean 4 4 Platine suppl menta...

Page 40: ...rant la saison chaude 18 T le de fixation T le de fixation de l changeur de chaleur orientable 2 unit s respectivement changeur de chaleur 19 Ventilateur d air sortant d air rejet Achemine l air us ve...

Page 41: ...il de ventilation est exclusivement r serv l usage domestique et similaires Toute utilisation autre ou d passant ce cadre est consid r e comme non conforme 7 Consignes de s curit et avertissements Ave...

Page 42: ...d appareils de ventilation chan geur de chaleur enthalpique dans des pi ces dont l hygrom trie est 70 HR Ne jamais utiliser d appareils de ventilation long terme avec une hygrom trie 70 HR court term...

Page 43: ...ection avant Lors des travaux au des sus de la t te prot ger les yeux et les voies respiratoires Risque de blessure lors des travaux en hauteur Utiliser des auxiliaires d acc s vertical chelles approp...

Page 44: ...ureau d tudes L utilisation d une hotte aspirante d air sortant ou d un foyer d pendant de l air ambiant n cessite l accord du ramoneur responsable de votre district Danger en cas d utilisation d acce...

Page 45: ...itation L ex cution n cessite en r gle g n rale l accord du ramoneur responsable de votre district Les appareils de ventilation ne peuvent tre install s dans des pi ces des habi tations ou des unit s...

Page 46: ...lieu d installation Temp rature ambiante de 10 C 40 C Espace de travail devant sous l appareil au moins 70 cm Tenir compte de l encombrement des com posants suppl mentaires 9 Caract ristiques techniq...

Page 47: ...sur les bornes des d tecteurs 1 et 2 double occupation Module enfichable EnOcean E SM ou mo dule enfichable KNX K SM en option Pour des composants recommand s Internet 11 Montage 11 1 D monter monter...

Page 48: ...re r alis s install s et isol s selon les indica tions des plans du bureau d tudes Les raccords d air ext rieur et d air rejet doivent tre isol s contre la diffusion pour viter une formation de conden...

Page 49: ...chable dans le compartiment lectro nique et visser 10 Reposer le s cache s de protection avant Chapitre 11 1 11 Effectuer un test de fonctionnement Activer le fusible secteur Les LED sur l unit de com...

Page 50: ...simple RLS 1 WR B2 B5 Raccordement parall le max 5 unit s de commande simples BT1 Unit de commande cran tactile RLS T1 WS W1 C ble de raccordement 230 V CA W2 C ble de commande blind pour unit de comm...

Page 51: ...tif de s curit avec contact libre de potentiel 230 VCA 16 A W6 C ble de raccordement fournir par le client pour le contact multifonction nel Contact relais libre de potentiel 230 VCA 5 A ou 30 VCC 5 A...

Page 52: ...W9 C ble de raccordement fournir par le client d tecteur 2 de CO2 externe p ex LIYY 3 x 0 5 mm W10 C ble de raccordement fournir par le client d tecteur 3 externe p ex LIYY 3 x 0 5 mm W11 C ble de rac...

Page 53: ...tecteur de gaz nocif FR 53 16 Plan de c blage d tecteur de gaz nocif A Appareil de ventilation WS 300 Flat A1 Module lectronique A2 Commande appareil VMC double flux 2015 GS D tecteur de gaz nocif su...

Page 54: ...onn es 8 Parit Even Bits de stop 1 Adresse 10 r glage de base Lorsque l unit de commande Confort commande cran tactile RLS T1 WS est d sactiv e dans le menu de param trage les bornes de raccordement s...

Page 55: ...t domotique Les contacts libres de potentiel du commutateur doivent tre occup s pour activation de 12 VCC Ethernet USB A2 A A1 X10 Digital RS485 X11 X12 Sensoren RLS X13 3 3 SD SC A B 12V LD2 LD1 S1 S...

Page 56: ...ns at 20 Pa and 20 Pa q Lage Beschreibung optische Filterwarnanzeige position description of visual filter warning LED replace the lter con nuously to preserve the device proper es r Anweisungen f r A...

Reviews: