12. Appendix ‒ Wiring diagram for WS 170 standard unit
│
UK
71
WS 170 standard unit
A
WS 170 ventilation unit
A1
Electronic slide-in module
A2
Control circuit board
B
RLS D1 WR room air control
B1
RLS 1 WR room air control
W1
230 V AC connection cable
W2
Shielded control cable provided by
customer, e.g. LiYCY 2 x 0.75 mm²
for RLS D1 WR room air control.
Instead of B1 (RLS 1 WR) room air
control, B (RLS D1 WR) room air
control can be connected.
W2´
Control cable (provided by
customer) for RLS 1 WR room air
control
Outer diameter of control cable
3.2...6.5 mm, e.g. LIYY 6x0.34 mm²
S1
Unit switch
M1
Supply air fan
M2
Exhaust fan
S
Door contact switch: Activated
by front plate
T-min
Frost protection temperature sensor
Supply air
Z1 (blue) Potentiometer adjuster
Ventilation level 1
Z2 (blue) Potentiometer adjuster
Ventilation level 2
Z3 (blue) Potentiometer adjuster
Ventilation level 3
Exhaust air
A1 (red) Potentiometer adjuster
Ventilation level 1
A2 (red) Potentiometer adjuster
Ventilation level 2
A3 (red) Potentiometer adjuster
Ventilation level 3
Jumper settings (Chapter 6.7.3)
J 1-3
Unit type, 000 = WS 170
J 4-5
Frost protection temperature
(Chapter 6.7.4)
J 6
No function
J 7
Jumper 7 open: Ventilation level 3
is reset after an hour.
J 8
RLS 1 WR or RLS D1 WR room air
control active: Leave factory setting,
J8 must be bridged.
J 9
Jumper 9 open: The ventilation
unit can be switched off at the
room air control.
Jumper 9 bridged:
Room air control RLS 1 WR:
Switch-off function blocked.
RLS D1 WR room air control:
Ventilation unit runs in "Humidity
protection ventilation" ventilation
level in the OFF switch position.
J10
Hygrostat or CO
2
/VOC sensor:
Without a sensor, jumper 10 must
be open.
Jumper 10 open: Hygrostat re-
leased with potential-free contact.
Jumper 10 bridged: CO
2
/ VOC
sensor (0 to 10 V output) released.
Further connection options
W3
Connection cable (provided by cus-
tomer) for external operating display.
k1
Potential-free relay contact
(max. 3 A / 250 V AC, 2 A / 30 DC).
The contact is closed when the ven-
tilation unit is running.
W4
Connection cable (provided by cus-
tomer) for external CO
2
or VOC
sensor or external hygrostat (with
potential-free contact).
W5
Connection cable (provided by custo-
mer) for external differential pressure
controller. Differential pressure con-
troller with potential-free relay contact.
Minimum switching power of relay
contact: 230 V AC/2 A.
Remove J1 bridge on A2 control
circuit board.
Summary of Contents for WS 170 L
Page 3: ......
Page 38: ...DE 12 Anhang Verdrahtungsplan WS 170 Komfortger t 36 12 2 Verdrahtungsplan WS 170 Komfortger t...
Page 40: ...DE 12 Anhang KNX Bus Konzept 38 12 3 KNX Bus Konzept...
Page 76: ...UK 12 Appendix KNX bus concept 74 12 3 KNX bus concept...
Page 116: ...FR 12 Annexe Concept bus KNX 114 12 3 Concept bus KNX...
Page 119: ......
Page 120: ......
Page 121: ......