UK
│
10. Technical data
68
10. Technical data
Housing dimensions
(W x H x D) in mm
● WS 170 standard unit
● WS 170 comfort unit
● WS 170
bypass unit
595 x 820 x 375
595 x 820 x 375
595 x 820 x 435
Material
Galvanised
sheet steel,
partly powder-
coated
Air connections
Ø 125 mm
Condensate drain
Sleeve with
Ø 28 mm lip
seal, 28x19 mm
reducer for
3/4" hose
Protection class
1
Degree of protection
IP 00
G4 outside air filter:
Included with standard unit,
optional with comfort and
bypass unit
WSG 170
air filter,
class G4
G4 exhaust air filter:
Included in all units
WSG 170
air filter,
class G4
F7 pollen filter in comfort
and bypass unit
WSF170,
pollen filter,
class F7
Permissible ambient
temperature
in installation room
+10 ... +40 °C
Permissible moisture in
installation room (at 20 °C)
● Standard unit
● Comfort unit
● Bypass unit
50 % RH
70 % RH
70 % RH
Permitted outside air
temperature
-15 ... +60 °C
Degree of heat
provision
Sensitive heat exchanger
Enthalpy heat exchanger
up to 94 %
up to 87 %
Rated voltage
power frequency
230 V AC
50 Hz / 60 Hz
Ventilation levels
(factory setting):
Humidity protection
ventilation (interval
operation)
● Reduced ventilation
● Nominal ventilation
● Intensive ventilation
approx. 57 %
of reduced
ventilation
60 m³/h
90 m³/h
120 m³/h
Power consumption (unit)
at 100 Pa Counter
pressure per duct
● 60
m³/h
● 90
m³/h
● 12
0 m³/h
24 W
35 W
50 W
Weight
● Standard unit
● Comfort unit
● Bypass unit
38 kg
43 kg
47 kg
Summary of Contents for WS 170 L
Page 3: ......
Page 38: ...DE 12 Anhang Verdrahtungsplan WS 170 Komfortger t 36 12 2 Verdrahtungsplan WS 170 Komfortger t...
Page 40: ...DE 12 Anhang KNX Bus Konzept 38 12 3 KNX Bus Konzept...
Page 76: ...UK 12 Appendix KNX bus concept 74 12 3 KNX bus concept...
Page 116: ...FR 12 Annexe Concept bus KNX 114 12 3 Concept bus KNX...
Page 119: ......
Page 120: ......
Page 121: ......