7. Start-up
64
7.3 Ventilation levels factory setting
Supply air
(
blue
potentiometer adjusters)
Exhaust air
(
red
potentiometer adjusters)
7.3.1 Extended setting range for each
ventilation level
The volumetric flow settings for each ventila-
tion level are permanently specified as part of
the factory setting (jumpers 1, 2 and 3 open
Chapter 6.7.3)
"S" potentiometer.
Alternatively, the volumetric flows can be
adjusted in the extended setting range for
each ventilation level separately (setting
range 40....160 m³/h, control voltage for fans
at each ventilation level freely adjustable from
1.7...10 V).
Jumpers 1 + 2 must be bridged and jumper 3
must be open for the extended setting range.
The control voltage measurement process is
described in the next chapter "Volumetric flow
setting with voltmeter".
NOTICE
Use a suitable measuring
instrument when measuring
the control voltages.
7.3.2 Voltage / volumetric flow table
Volumetric flow
[m³/h]
Control voltage
[V]
40
1,7
50
2,5
60
3,3
70
4,0
80
4,7
90
5,3
100
5,8
110
6,4
120
6,9
130
7,5
140
8,0
150
8,5
160
8,8
7.4 Volumetric flow setting with
voltmeter
Alternatively, the volumetric flows for the
individual ventilation levels can be adjusted
using a voltmeter.
Summary of Contents for WS 170 L
Page 3: ......
Page 38: ...DE 12 Anhang Verdrahtungsplan WS 170 Komfortger t 36 12 2 Verdrahtungsplan WS 170 Komfortger t...
Page 40: ...DE 12 Anhang KNX Bus Konzept 38 12 3 KNX Bus Konzept...
Page 76: ...UK 12 Appendix KNX bus concept 74 12 3 KNX bus concept...
Page 116: ...FR 12 Annexe Concept bus KNX 114 12 3 Concept bus KNX...
Page 119: ......
Page 120: ......
Page 121: ......