Installations-, Inbetriebnahme- und Wartungsanleitung WS 160 Flat, WS 300 Flat
Installation, Commissioning and Maintenance Instructions for WS 160 Flat, WS 300 Flat
Notice d'installation, de mise en service et d'entretien WS 160 Flat, WS 300 Flat
EN
18
Maico Elektroapparate-Fabrik GmbH
I
Steinbeisstr. 20
I
78056 Villingen-Schwenningen
I
Germany I S49 7720 6940 I [email protected]
0185.1242.0001_RLF.9_12.22_DSW-AS
11.2 Replacing RLS T2 WS
Removal (steps ① to ④)
Installation (steps ① to ③)
12 RLS 1 WR: Control elements, LEDs
The ventilation levels can be set manually with the
RLS 1
WR
control unit. LEDs indicate the selected ventilation
level, a pending filter change or faults.
In
ventilation level II
(nominal ventilation), the ventilation
unit switches to the
Auto sensor operating mode
(setting
can be changed by the installer). The automatic system en-
sures hygienically perfect ventilation based on the determ-
ined humidity values (combi sensor) and/or air quality val-
ues (optional CO2/VOC sensor).
Ventilation levels I-III: Shift up with the ▼ but-
ton, shift down with the ▲ button.
Ventilation level
I
Ventilation for
humidity
protection
(building preser-
vation). LED I flashes. Inter-
val ventilation 13 minutes
on – 17 minutes off –
13 minutes on.
Ventilation level
I
Reduced ventilation
. LED I
on. Continuous operation.
Ventilation level
II
Nominal ventilation
. LED II
on. Continuous operation.
Ventilation unit in Auto
sensor operating mode.
Ventilation level
III
Intermittent ventilation
.
LED III flashes. Intensive
ventilation with timer. Once
a timer interval has elapsed,
the ventilation unit switches
back to nominal ventilation
Ventilation level
III
Intensive ventilation
. LED III
on. Continuous operation.
Filter change indicator
LED II flashes.
Fault display
All 3 LEDs flash on the
RLS 1 WR
. The fault elimina-
tion must be acknowledged
manually. Press both arrow
keys at the same time for
3 seconds.
RLS T2 WS:
The fault is dis-
played. Acknowledge fault
clearance on the display.
RLS G1 WS:
The status LED
lights up red.
Press both ventilation level
keys at the same time for
3 seconds.
Operating modes with RLS 1 WR as a solo control unit
Manual, Auto sensor or Off
Auto sensor function only active
• with
nominal ventilation
(ventilation level II),
• if
external sensors
are
connected
or
•
Combi-sensor operation
parameter is set to
linear
.
Off function
can be deactivated with
Single control unit
Blocking off
parameter (single control unit = RLS 1 WR con-
trol unit).
Operating modes when using several RLS 1 WR/EnOcean
pushbuttons or in combinations with a touchscreen con-
trol unit
Manual, Auto time, Auto sensor, ECO mode supply air, ECO
mode exhaust air or Off
• The operating mode is preset via the touchscreen con-
trol unit, APP or the web tool.
•
Ventilation level adjustment
is possible for a
limited
period of time
.
•
Off function
can be deactivated with
Single control unit
Blocking off
parameter (single control unit = RLS 1 WR
control unit).
To put units into standby on the control unit,
select ventilation level 0 = Off.
13 RLS T2 WS: Control elements, displays,
functions
RLS T2 WS
touchscreen control unit for ventilation units
with
control
. Scope of functions on the RLS T2 WS as
described below.
13.1 Standard display/start screen
Start screen activated ex works. This can be de-
activated with the commissioning software.
1 Main switch
2 System settings
3 Unit settings
4 Unit query
5 Current operating mode / operating mode selec-
tion
6 Quick unit selection (if using several units)
7 Current ventilation level / ventilation level selec-
tion
8 Current fault messages
9 Current notes
10 Logout
11 Date, time, room temperature, CO2 value of cur-
rent unit
13.2 Main menu value call-up
Here current unit values such as temperature and humidity
measurement values, unit statuses or fault messages can
be called up.