11.2 Replacing RLS T2 WS

Removal (steps ① to ④)

Installation (steps ① to ③)

12 RLS 1 WR: Control elements, LEDs

The ventilation levels can be set manually with the 

RLS 1

WR

 control unit. LEDs indicate the selected ventilation

level, a pending filter change or faults.

In 

ventilation level II

 (nominal ventilation), the ventilation

unit switches to the 

Auto sensor operating mode

 (setting

can be changed by the installer). The automatic system en-
sures hygienically perfect ventilation based on the determ-
ined humidity values (combi sensor) and/or air quality val-
ues (optional CO2/VOC sensor).

 Ventilation levels I-III: Shift up with the ▼ but-

ton, shift down with the ▲ button.

Ventilation level

 

I

Ventilation for 

humidity

protection

 (building preser-

vation). LED I flashes. Inter-
val ventilation 13 minutes
on – 17 minutes off –
13 minutes on.

Ventilation level

 

I

Reduced ventilation

. LED I

on. Continuous operation.

Ventilation level

 

II

Nominal ventilation

. LED II

on. Continuous operation.
Ventilation unit in Auto
sensor operating mode.

Ventilation level

 

III

Intermittent ventilation

.

LED III flashes. Intensive
ventilation with timer. Once
a timer interval has elapsed,
the ventilation unit switches
back to nominal ventilation

Ventilation level

 

III

Intensive ventilation

. LED III

on. Continuous operation.

Filter change indicator

LED II flashes.

Fault display

All 3 LEDs flash on the

RLS 1 WR

. The fault elimina-

tion must be acknowledged
manually. Press both arrow
keys at the same time for
3 seconds. 

RLS T2 WS:

 The fault is dis-

played. Acknowledge fault
clearance on the display.

RLS G1 WS:

 The status LED

lights up red.
Press both ventilation level
keys at the same time for
3 seconds.

Operating modes with RLS 1 WR as a solo control unit

Manual, Auto sensor or Off

Auto sensor function only active

• with 

nominal ventilation

 (ventilation level II),

• if 

external sensors

 are 

connected

 or

Combi-sensor operation

 parameter is set to 

linear

.

Off function

 can be deactivated with 

Single control unit

Blocking off

 parameter (single control unit = RLS 1 WR con-

trol unit).

Operating modes when using several RLS 1 WR/EnOcean
pushbuttons or in combinations with a touchscreen con-
trol unit

Manual, Auto time, Auto sensor, ECO mode supply air, ECO
mode exhaust air or Off

• The operating mode is preset via the touchscreen con-

trol unit, APP or the web tool.

Ventilation level adjustment

 is possible for a 

limited

period of time

.

Off function

 can be deactivated with 

Single control unit

Blocking off

 parameter (single control unit = RLS 1 WR

control unit).

 To put units into standby on the control unit,

select ventilation level 0 = Off.

13 RLS T2 WS: Control elements, displays,
functions

RLS T2 WS

 touchscreen control unit for ventilation units

with 

 

control

. Scope of functions on the RLS T2 WS as

described below.

13.1 Standard display/start screen

 Start screen activated ex works. This can be de-

activated with the commissioning software.

1 Main switch

2 System settings

3 Unit settings

4 Unit query

5 Current operating mode / operating mode selec-

tion

6 Quick unit selection (if using several units)

7 Current ventilation level / ventilation level selec-

tion

8 Current fault messages

9 Current notes

10 Logout

11 Date, time, room temperature, CO2 value of cur-

rent unit

13.2 Main menu value call-up

Here current unit values such as temperature and humidity
measurement values, unit statuses or fault messages can
be called up.

Summary of Contents for WS 160 Flat

Page 1: ...bersicht 2 4 1 Ger tefront 2 4 2 Aufbau Rohranschl sse 2 5 Bedieneinheiten Software Schnittstellen 4 5 1 Berechtigungen f r Parametereinstellun gen mit folgenden Bedieneinheiten Tools 4 5 2 Bedieneinh...

Page 2: ...gister ET Enthalpiew rmetauscher Z Zonenklappe 4 1 Ger tefront WS 160 Flat F Frontabdeckung USB USB Anschluss A1 Filterabdeckung 1 Schacht f r G4 bzw F7 Fil ter Alternative f r F7 Pollenfilter Aktivko...

Page 3: ...optio nal Aktivkohlefilter 10 Schutzgitter Vorheizregister 11 Abluftventilator Fortluftventilator 12 Vorheizregister optional 13 Au enluft Temperaturf hler Frostschutz vor dem W rmetauscher 14 Fortluf...

Page 4: ...icht belegt sein X1 X KNX optional X1 X 1 nderungen nur eingeschr nkt m glich 5 2 Bedieneinheit RLS 1 WR Lieferumfang Mit Funktionen Ein Aus 4 L ftungsstufen Filterwechsel und St ranzeige Die RLS 1 WR...

Page 5: ...sse WS 160 Flat WS 300 Flat DN 125 160 DN 160 Au enluftfilter F7 Abluftfilter G4 Schutzklasse 1 Schutzart IP 00 Max zul ssige Feuchte im Aufstellraum 20 C 70 Bemessungsspannung 230 V AC Netzfrequenz...

Page 6: ...ehrt vorgehen Darauf achten dass die Abdeckung rich tig sitzt und keine Fehlluft angesaugt werden kann L ftungsger t an der Decke oder Wand befestigen Befestigungsvarianten A B oder C A Gewindestange...

Page 7: ...LEDs an der RLS 1 WR schalten ein 14 Inbetriebnahmesoftware downloaden F r Systeman forderungen und Download Inbetriebnahme 9 15 L ftungsger t einstellen und einregulieren 10 Montage der Bedieneinhei...

Page 8: ...r t in die Betriebsart Auto Sensor Einstellung durch Instal lateur ver nderbar Die Automatik sorgt f r eine hygie nisch einwandfreie L ftung anhand der ermittelten Feuch tewerte Kombisensor und oder L...

Page 9: ...wischen den Automatik Betriebsarten Auto Zeit Auto Sensor und den manuellen Betriebsarten Manuell Eco Betrieb Zuluft Eco Betrieb Abluft und Aus 13 4 Kurzwahl L ftungsstufe Aktiviert die L ftungsstufe...

Page 10: ...hutzkappe entfernen und PC Notebook an der USB Schnittstelle mit dem L ftungsger t verbinden 3 L ftungsger t mit der Netzsicherung einschalten 4 Inbetriebnahmesoftware aufrufen Verbindung per USB w hl...

Page 11: ...colours Colours are used to identify associated assemblies components Additional software Commissioning software for configuring and adjusting the ventilation unit chapter Commissioning 19 or www mai...

Page 12: ...unit is only intended for domestic use and similar purposes No other or additional use is intended 4 Unit overview Unit types WS 160 Flat unit types WS 300 Flat unit types WS 160 Flat ET WS 300 Flat R...

Page 13: ...er active carbon filter optional 10 Protective grille for preheating register 11 Exhaust air fan outgoing air fan 12 Preheating register optional 13 Outside air temperature sensor for frost protec tio...

Page 14: ...erface must not be occupied X1 X KNX optional X1 X 1 Changes only possible to a limited extent 5 2 RLS 1 WR control unit scope of delivery With functions on off 4 ventilation levels filter change and...

Page 15: ...WS 160 Flat WS 300 Flat DN 125 160 DN 160 Outside air filter F7 Exhaust air filter G4 Protection class 1 Degree of protection IP 00 Max permissible humidity in installation room 20 C 70 Rated voltage...

Page 16: ...t on the ceiling or wall Mounting variants A B or C A Threaded pin B Ceiling bracket with damping element C Universal fixing bracket 1 Firmly screw down ventilation unit to ceiling or wall with approp...

Page 17: ...iring will result in unit damage Be sure to note the writing on the control unit and control circuit board Only connect as shown in the enclosed wir ing plan The commissioning software must be install...

Page 18: ...limina tion must be acknowledged manually Press both arrow keys at the same time for 3 seconds RLS T2 WS The fault is dis played Acknowledge fault clearance on the display RLS G1 WS The status LED lig...

Page 19: ...y all connection lines are correctly and firmly attached all supply and exhaust air valves are mounted and open the ventilation ducts are insulated all outgoing air and outside air covers are mounted...

Page 20: ...entifier les modules compo sants correspondants Logiciels suppl mentaires Logiciel de mise en service pour la configuration et l ajus tage de l appareil de ventilation Chapitre Mise en ser vice 29 ou...

Page 21: ...es similaires Cet appareil de ventilation est exclusivement r serv l usage domestique et similaires Toute utilisation autre ou d passant ce cadre est consid r e comme non conforme 4 Vue d ensemble de...

Page 22: ...pous si res fines filtre charbon actif en option 10 Grille de protection registre de pr chauffage 11 Ventilateur d air sortant ventilateur d air rejet 12 Registre de pr chauffage en option 13 Sonde de...

Page 23: ...LS T1 WS ou RLS T2 WS les deux en op tion Propri taire X X Installateur X X Unit de com mande design RLS G1 WS en option Propri taire Installateur X X APPLI Propri taire X1 X Locataire X Outil Web Pro...

Page 24: ...rme Affichage de remplacement de filtre Affichage de fonctionnement R chauffage Registre de pr chauffage Volet ext rieur EG saumure pompe non r gul e Fonction de refroidissement R seau domestique Loxo...

Page 25: ...gure 6 Visser fermement l appareil de ventilation au plafond au niveau des querres de plafond avec le mat riel de fixation appropri 7 Placer le filtre air l changeur de chaleur et le cache de protecti...

Page 26: ...accrocher comme d crit ci dessous 1 D sactiver le fusible secteur 2 Retirer le cache de protection avant Montage WS 160 Flat 25 ou Montage WS 300 Flat 25 Fl che s T tons de suspension Figures appareil...

Page 27: ...Risque de court circuit endommagement de l appareil en cas de p n tration d eau dans le compar timent lectronique Veillez ce que les arriv es soient correctes et tanches au moyen de passe c ble 11 Per...

Page 28: ...ement en cas d utilisation de plu sieurs boutons RLS 1 WR EnOcean ou de combinaisons avec une unit de commande cran tactile Manuel Auto Temps Auto D tecteur Mode ECO Air en trant Mode ECO Air sortant...

Page 29: ...les passages de c bles sont tanches Les interrupteurs DIP des platines suppl mentaires op tionnelles install es sont r gl s en fonction de l applica tion Instructions d utilisation des accessoires 14...

Page 30: ...Anschlussleitung bauseitig f r externen Senso ren XO1 Steckplatz f r optionales Kommunikationssteck modul EnOcean KNX XO2 Steckplatz Hardware Erweiterung Modular Ka bel ZP1 230 VAC Anschlussklemmen z...

Page 31: ...S Modbus p ex LIYY 4 x 0 34 mm W3 C ble de raccordement fournir par le client pour le dispositif de s curit externe avec con tact libre de potentiel 12 V 2 A W4 C ble de raccordement fournir par le cl...

Page 32: ...ce with potential free contact 12 V 2 A W4 Connection cable provided by customer for ex ternal safety device with potential free contact 230 V 16 A W6 Connection cable provided by customer for multifu...

Page 33: ...rmittent ventilation sensor ty pe digital W9 Connection cable provided by customer for external CO2 sensor 2 e g LIYY 3 x 0 5 mm W10 Connection cable provided by customer for external sensor 3 e g LIY...

Page 34: ...tronikeinschub A2 KWL Steuerung W11 Anschlussleitung ModBus bauseitig z B LIYY 3 x 0 25 mm ModBus Mode RTU Baudrate 9600 19200 Daten Bits 8 Parit t Even Stop Bits 1 Adresse 10 Grundeinstellung Bei im...

Page 35: ...m of Integration in building control system A Ventilation unit A1 Electronics slide in module A2 Controlled domestic ventilation unit control 12VDC 1 Operating display 12VDC 2 Filter change indicator...

Page 36: ...stallation de mise en service et d entretien WS 160 Flat WS 300 Flat DE 36 Maico Elektroapparate Fabrik GmbH I Steinbeisstr 20 I 78056 Villingen Schwenningen I Germany I Service 49 7720 6940 I info ma...

Reviews: