Installations-, Inbetriebnahme- und Wartungsanleitung WS 160 Flat, WS 300 Flat
Installation, Commissioning and Maintenance Instructions for WS 160 Flat, WS 300 Flat
Notice d'installation, de mise en service et d'entretien WS 160 Flat, WS 300 Flat
EN
14
Maico Elektroapparate-Fabrik GmbH
I
Steinbeisstr. 20
I
78056 Villingen-Schwenningen
I
Germany I S49 7720 6940 I [email protected]
0185.1242.0001_RLF.9_12.22_DSW-AS
I Outside air
II Supply air
III Exhaust air
IV Outgoing air
1 Control unit
RLS 1 WR
. Alternative control units:
RLS T1 WS
,
RLS T2 WS
or
RLS G1 WS
2 Cable feedthrough for
power cable
3 Cable feedthrough for connection cables,
control
unit
and
accessories
(outer diameter 3.2 ... 6.5
mm)
4 Main board
A1
on electronics plate
4.1 Ethernet interface/network connection
4.2 USB interface (circuit board)
4.3
S01
interface for optional KNX plug-in module (for
KNX building control system) or EnOcean plug-in
module (for EnOcean radio components)
4.4 Additional board
ZP 1
or
ZP 2
(both optional)
4.5 USB interface on board for USB port on front
cover
5 Air filter, filter class G4
6 Enthalpy heat exchanger
7 Combi sensor for exhaust air humidity/exhaust air
temperature
8 Outside air temperature sensor for frost protec-
tion (in front of the heat exchanger)
9 Preheating register with protective grille (for K
variant in scope of supply, otherwise optional)
10 Pollen filter, filter class F7 (fine dust filter), active
carbon filter, optional
11 Air filter, filter class G4 (for filter cascade optional)
12 Outside air/supply air fan
13 Harmful gas sensor (optional)
14 Supply air temperature sensor
15 Outgoing air temperature sensor
16 Cover centring plate with wing screw. Provides
protection when taking off front cover, centres
the cover when refitting
17 Bypass module (optional)
18 Heat exchanger fixing plate, can be rotated,
2 items per heat exchanger
19 Exhaust air/outgoing air fan
T Rating plate with unit serial number
5 Control units, software, interfaces
The ventilation unit is switched on/off with the
mains fuse in the fuse box. For unit standby on the
touchscreen control unit or with the commission-
ing software, select the Off operating mode
(standby not possible with RLS 1 WR control unit).
5.1 Authorizations for parameter settings with the
following control units/tools
Control unit/tool Authorised
person
Changing
paramet-
ers
Querying
paramet-
ers
RLS T1 WS
or
RLS T2 WS
touch-
screen control
unit
(both optional)
Owner
X
X
Installer
X
X
RLS G1 WS
design
control unit (op-
tional)
Owner
Installer
X
X
app
Owner
X
1
X
Tenant
X
web tool
Owner
X
1
X
Installer
X
X
ModBus
instead
of RLS T1 WS, RLS
T2 WS or RLS G1
WS touchscreen
control unit (in-
terface must not
be occupied).
X
1
X
KNX (optional)
X
1
X
1) Changes only possible to a limited extent.
5.2 RLS 1 WR control unit (scope of delivery)
With functions
on/off
,
4 ventilation levels
,
filter change
and
fault indicator
. The
RLS 1 WR
can be combined with
up to
4 further RLS 1 WR, connected in parallel
→ Opera-
tion with RLS 1 WR.
Auto sensor operation
only possible
when using a
single RLS 1 WR
.
5.3 RLS T2 WS touchscreen control unit
RLS T2 WS functions (touchscreen control unit):
Manual,
Auto time, Auto sensor, ECO mode supply air, ECO mode
exhaust air, On/Off, Filter change and Fault display.
The
RLS T2 WS
can be combined with up to
5 RLS 1 WR
,
with a reduced range of functions. Reduced range of func-
tions
RLS 1 WR
= no operating modes selectable, ventila-
tion runs for a limited time, no device off/standby.
5.4 RLS G1 WS design control unit
RLS G1 WS functions (touchscreen control unit):
5 ventila-
tion levels, Auto time, ECO supply air, ECO exhaust air, On/
Off, Filter change and Fault display. Operating mode
Auto
Sensor indirectly available via Auto Time setting.
The
RLS G1 WS
can be combined with up to
5 further
RLS 1 WR
, with a reduced range of functions. Reduced
range of functions on
RLS 1 WR
= no operating modes se-
lectable, ventilation runs for a limited time, no unit off/
standby.
5.5 Further operating and setting options for users
and specialist installers
• Free
app
(iOS/Android smartphone app)
•
Web tool
(PC software for operating or setting up
the ventilation unit, download from the Internet)
With the web tool, a registered owner can activ-
ate authorisations for tenants or specialist in-
stallers so that they have special setting options
for the ventilation unit on the Internet.
5.6 RLS 1 WR operating modes with single control
unit (Solo)
•
Manual operating mode
•
Auto sensor operating mode:
Function only active for
nominal ventilation (ventilation level II) if external
sensors are connected or the
Combi sensor operation
parameter is set to linear
→ CO2-/VOC-/Rel. Humidity
limit value min./max..
•
Operating mode Off:
Function can be deactivated with
Single control unit Blocking off
parameter (single con-
trol unit = RLS 1 WR control unit).
5.7 Functions RLS 1 WR and EnOcean button in
combination with RLS T1 WS, RLS T2 WS or
RLS G1 WS
Operating modes selectable with the RLS T1 WS,
RLS T2 WS or RLS G1 WS:
Manual, Auto time, Auto sensor,
ECO mode supply air, ECO mode exhaust air and Off.
•
Operating mode:
The operating mode selected on the
touchscreen control unit
cannot
be changed with the
RLS 1 WR.
•
Ventilation level:
The change of the ventilation level
made at an
RLS 1 WR
or with an
EnOcean button
runs
for a limited time
. The ventilation unit then switches
back to the ventilation level selected on the touchscreen
control unit.
The Off function can be deactivated with the
Single control unit Blocking off parameter (single
control unit = control unit RLS 1 WR).