WIRING DIAGRAM

WR 600

Version: 2019-05-22 - MAICO VENTILATOREN, www.maico-fans.com - We are not responsible for mistakes or printing errors and retain the
right to make technical modifications without giving prior notice

Page 3

WR 600 ventilation unit with RLS 1 WR room air control and COsensor

Connection of a CO2 sensor for the demand-driven supply of fresh air. The ventilation unit only reacts to the
CO

2

sensor if ventilation level 2 (nominal ventilation) is selected at the room air control.

A1 - electrical terminal box WR 600
A2 - control circuit board: Jumper 10 (CO2) set
B1 - room air control RLS 1 WR
CO2 - CO

2

sensor SKD

W1 - 230 V AC connecting cable
W2 control cable for room air control
W3' - connecting cable for external CO

2

sensor (to be supplied by the customer). Connection to control circuit board

A2 at terminals “CO2” and “OT”. Set jumper 10 (CO2) to release the feature, see figure.
Switching points for CO  

2

  sensor

< 900 ppm, ventilation unit switches to ventilation level 1. Ventilation level 2 is shown at the room air control.
> 1,000 ppm, ventilation unit switches from ventilation level 1 to ventilation level 2.
> 1,100 ppm, ventilation unit switches to ventilation level 3. Ventilation level 2 is shown at the room air control.
< 1,000 ppm, ventilation unit switches from ventilation level 3 to ventilation level 2.

Summary of Contents for WR 600

Page 1: ...n t e i l L1 N Z u l u f t N L 1 L 1 N L 1 L 1 N 1 2 3 4 5 6 7 8 9 1 0 CO2 BDE On Off Temp 2 4 V GY PK WH BN BN BU GNYE BN GNYE BU WH BU A2 W2 BN WH T y p 0 10V M1 0 10V M2 5 3 1 GNYE BU BN N e t z A...

Page 2: ...r volumetric flow ventilation level 2 S3 blue setting potentiometer for supply air volumetric flow ventilation level 3 S1 red setting potentiometer for exhaust air volumetric flow ventilation level 1...

Page 3: ...d Jumper 10 CO2 set B1 room air control RLS 1 WR CO2 CO2sensor SKD W1 230 V AC connecting cable W2 control cable for room air control W3 connecting cable for external CO2sensor to be supplied by the c...

Page 4: ...his purpose This blocks the room air control RLS 1 WR The LED display goes out The unit is only released again when the differ ential pressure controller switches the fans back on The ventilation unit...

Page 5: ...rols can be connected to the ventilation unit No CO2 sensor should be connected if several room air controls are connected A1 electrical terminal box WR 600 A2 control circuit board Jumper setting Fac...

Page 6: ...back to the previously selected ventilation level If you switch manually or using the timer from ventilation level 3 to level 2 or 1 this deactivates the automatic function of the hygrostat temporaril...

Page 7: ...O VENTILATOREN www maico fans com We are not responsible for mistakes or printing errors and retain the right to make technical modifications without giving prior notice Page 7 Wiring diagram for WR 6...

Page 8: ...entilation level 2 S3 blue Potentiometer adjuster ventilation level 3 Exhaust air S1 red Potentiometer adjuster ventilation level 1 S2 red Potentiometer adjuster ventilation level 2 S3 red Potentiomet...

Page 9: ...O VENTILATOREN www maico fans com We are not responsible for mistakes or printing errors and retain the right to make technical modifications without giving prior notice Page 9 Wiring diagram for WR 6...

Page 10: ...ventilation level 2 S3 blue Potentiometer adjuster ventilation level 3 Exhaust air S1 red Potentiometer adjuster ventilation level 1 S2 red Potentiometer adjuster ventilation level 2 S3 red Potentiome...

Page 11: ...ation unit switches back to the previously selected ventilation level If you switch manually from ventilation level 3 to level 2 or 1 this deactivates the automatic function of the hygrostat temporari...

Page 12: ...rature can be adjusted manually using the setting wheel at the TH 10 The air flow controller sensor S1 must be installed in the direction of flow at least 30 cm ahead of the electrical air heater The...

Reviews: