Maico WR 600 Wiring Diagram Download Page 12

WIRING DIAGRAM

WR 600

Version: 2019-05-22 - MAICO VENTILATOREN, www.maico-fans.com - We are not responsible for mistakes or printing errors and retain the
right to make technical modifications without giving prior notice

Page 12

WR 600 ventilation unit with RSL 1 WR or RLS 2 F room air control and electric air
heater

If the heat recovery unit is installed in a passive-energy house, a heat register in the outside air is necessary, in order
to guarantee a permanent air exchange.
It preheats cold outside air and keeps the heat exchanger free of frost. The switch-on temperature of the TH 10 should
be set to -3#.
If the outside air temperature gets too cold, the external frost protection heating of the DRH 25-6 switches on and
guarantees an uninterrupted ventilation operation.
The switch-off difference should be set to 5 K. Optionally, the switch-on temperature can be adjusted manually using
the setting wheel at the TH 10.
The air flow controller sensor "S1" must be installed in the direction of flow, at least 30 cm ahead of the electrical air
heater. The TH 10 temperature sensor "R1" must be installed in the air flow direction, at least 50 cm after the electri-
cal air heater.
LW 9 - air flow monitor
S1 - air flow monitor sensor before the DRH..
JP1 - plug jumper on operating mode “H”. Relay switches on as the temperature drops.
TH 10 - thermostat
R1 - temperature sensor after DRH..
US 16 T- universal contactor
DRH 25-6 - electrical air heaters
S - sensor
We recommend the filter box TFE 25-4 (with G4 filter) to protect the electrical heat register against dirt. If a filter box is
used, the G4 filter in the outside air channel can be removed from the heat recovery unit.
A ground collector and brine-air heat exchanger can be used to keep the heat exchanger free of frost.
For external heat register, filter box, outside air and outgoing air channel: These must be diffusion-resistant insulated
to protect against condensation.

Summary of Contents for WR 600

Page 1: ...n t e i l L1 N Z u l u f t N L 1 L 1 N L 1 L 1 N 1 2 3 4 5 6 7 8 9 1 0 CO2 BDE On Off Temp 2 4 V GY PK WH BN BN BU GNYE BN GNYE BU WH BU A2 W2 BN WH T y p 0 10V M1 0 10V M2 5 3 1 GNYE BU BN N e t z A...

Page 2: ...r volumetric flow ventilation level 2 S3 blue setting potentiometer for supply air volumetric flow ventilation level 3 S1 red setting potentiometer for exhaust air volumetric flow ventilation level 1...

Page 3: ...d Jumper 10 CO2 set B1 room air control RLS 1 WR CO2 CO2sensor SKD W1 230 V AC connecting cable W2 control cable for room air control W3 connecting cable for external CO2sensor to be supplied by the c...

Page 4: ...his purpose This blocks the room air control RLS 1 WR The LED display goes out The unit is only released again when the differ ential pressure controller switches the fans back on The ventilation unit...

Page 5: ...rols can be connected to the ventilation unit No CO2 sensor should be connected if several room air controls are connected A1 electrical terminal box WR 600 A2 control circuit board Jumper setting Fac...

Page 6: ...back to the previously selected ventilation level If you switch manually or using the timer from ventilation level 3 to level 2 or 1 this deactivates the automatic function of the hygrostat temporaril...

Page 7: ...O VENTILATOREN www maico fans com We are not responsible for mistakes or printing errors and retain the right to make technical modifications without giving prior notice Page 7 Wiring diagram for WR 6...

Page 8: ...entilation level 2 S3 blue Potentiometer adjuster ventilation level 3 Exhaust air S1 red Potentiometer adjuster ventilation level 1 S2 red Potentiometer adjuster ventilation level 2 S3 red Potentiomet...

Page 9: ...O VENTILATOREN www maico fans com We are not responsible for mistakes or printing errors and retain the right to make technical modifications without giving prior notice Page 9 Wiring diagram for WR 6...

Page 10: ...ventilation level 2 S3 blue Potentiometer adjuster ventilation level 3 Exhaust air S1 red Potentiometer adjuster ventilation level 1 S2 red Potentiometer adjuster ventilation level 2 S3 red Potentiome...

Page 11: ...ation unit switches back to the previously selected ventilation level If you switch manually from ventilation level 3 to level 2 or 1 this deactivates the automatic function of the hygrostat temporari...

Page 12: ...rature can be adjusted manually using the setting wheel at the TH 10 The air flow controller sensor S1 must be installed in the direction of flow at least 30 cm ahead of the electrical air heater The...

Reviews: