
Wiring diagram for ModBus – circuit board A2 r.h. | UK
63
18 Wiring diagram for ModBus
– circuit board A2 –
A
Ventilation unit
A1 Electronic slide-in module
A2 CDV unit control
W11 Connecting cable for ModBus
(provided by customer), e.g.
LIYY 3 x 0.25 mm²
ModBus mode RTU
Baud rate
9600/19200
Data bits
8
Parity Even
Stop bits
1
Address
10 (basic setting)
If the comfort control unit is deactivated in the
parameter menu (touchscreen control unit
RLS T1 WS), the connection terminals on the
RS 485 terminal block can be used as the
ModBus interface. The controlled domestic
ventilation unit can thereby be incorporated
into a building control technology.
Ethernet
USB
A2
A
A1
X10
Digital
RS485
X1
1
X12
Sensoren
RLS
X13
3.
3S
DS
C
AB
12V
LD2
LD1
S1+
S2-
LD3
24V
24V
GND
B
A
W11
Summary of Contents for RB 170 CBL
Page 2: ...WS 160 Flat Kap Chap 3...
Page 3: ...WR 310 WR 410 WS 320 WS470 Kap Chap 3...
Page 4: ...WS 170 RB 170 Kap Chap 3...
Page 5: ...Trio Kap Chap 3...