gb | 8. Electrical connection (specialist installer)
34
9. Secure external cover to frame with
screw supplied.
7.6 Frame of PP 60 K-SE internal
cover
1. Remove plaster protective cover on
inside if necessary.
2. Check angle of inclination of fitted wall
sleeve. There must be an inclination
of 1…2 % to the outside.
3. Take internal cover [8] off frame of
internal cover [6].
4. Align frame of internal cover [6]
horizontally and centred in the middle
to the wall insulation sleeve [10].
5. Use dowels and screws (6 mm in
diameter, provided by customer) to
secure frame to internal wall.
7.7 PP 60 K-SE ventilation unit
1. Remove plaster protective cover on
inside if necessary.
2. Place G3 external filter [3] (optional
M6) on slide-in module [4] and turn
down pasting lugs. The pasting frame
must be facing the slide-in module.
3. Place G3 internal filter [5] (optional
M6) on slide-in module [4] and turn
down pasting lugs. The pasting frame
must be facing the slide-in module.
4. Slide slide-in module [4] including
filter, heat exchanger and EC fan into
wall insulation sleeve [10]. Consider
the sticker „Unten/Bottom/ Bas“. The
heat exchanger must be facing you.
5. Seal ventilation unit with internal
cover [8].
You will hear it engage.
8.
Electrical connection
(specialist installer)
Only qualified electricians are permitted
●
to make the electrical connections, in
compliance with the wiring diagrams
below.
Make sure to observe the relevant
●
regulations for electrical installation; in
Germany this is particularly
VDE 0100
with the corresponding parts.
Check the mains supply to the building
●
before commissioning. This must comply
with the voltage specified on the mains
adapter (230 V /
50 Hz).
DANGER
Danger to life from electric shock!
Deactivate the fuse in the fuse box and
protect against being accidentally switched
back on. Fit a warning notice on the fuse
box.
8.1 RLS PP-K room air control
The customer should provide control
cables between the room air control and
PushPull 60 K ventilation units, types
J-YSTY and 0.8 mm, 4 wires.
NOTICE
Material damage if the incorrect cables
are used.
Only connect the room air control to
permanently wired electrical installations
with NYM-O or NYM-J, (3 x 1.5 mm²) type
cables. Mains isolation device required
with contact openings of at least 3 mm at
each pole.