8 Mounting preparations | UK 

27

7.3 Number of ventilation units

Combinations

Number of ventilation 

units

Ventilation units 

PP 45 O/K + 

room air control 

RLS 45 O/K
Up to 3 additional  

RLS 45 K permitted

Max. 6 PP 45 units

 

(3 x 2 unit pairs). 

 

From star point, 25 m  

cable connection length 

to PP45 unit. Up to star 

point, max. 4 m.

Ventilation units 

PP 45 O/K + 

power unit RLS 45 LT
Up to 3 PP 45 LT per-

mitted

Max. 6 PP 45 units

 

(3 x 2 unit pairs)

 

per power unit.  

From star point, 25 m  

cable connection length 

to power unit. Up to star 

point, max. 4 m.

PP 45 RC units 

(wireless)

Only operate PP 45 RC 

devices in pairs, 

any number of pairs*. 

Observe ranges.

Ventilation units 

PPB 30 

O

 + 

room air control 

RLS 45 O

3 PPB 30 O 

or

2 PPB 30 O

 + 

2 PP 45 O/K or

1 PPB 30 O 

4 PP 45 O/K
Set up unit pairs for 

PP 45 units, if possible. 
From star point, 25 m  

cable connection length 

to PPB 30-/PP 45 unit. 

Up to star point, max. 

4 m.

Ventilation units 

PPB 30 

K

 + 

room air control  

RLS 45 

or 

power unit PP 45 LT

3 PPB 30 K 

or

2 PPB 30 K

 + 

2 PP 45 O/K or

1 PPB 30 K 

4 PP 45 O/K
Set up unit pairs for 

PP 45 units, if possible. 
From star point, 25 m  

cable connection length 

to power unit. Up to star 

point, max. 4 m.

* Can be used as a stand-alone unit with an 

external wall air opening (ALD) for volumetric 

flow compensation.

8 Mounting preparations

8.1 Mounting information

 

PP 45 units are only suited for supply air 

rooms. 

 

PPB 30 units are the ideal choice for 

exhaust air rooms.

 

Observe minimum spacing.

 

● Ensure sufficient space to work in front of 

the unit 

 for filter change.

 

The customer should provide appropriate 

mounting material for mounting the wall 

sleeve and external cover.

 

Core hole diameter 

Ø

 162. To ensure that 

condensate is removed via the external cov

-

er, the core drill hole should have a 1 to 2 % 

incline to the external wall. The condensate 

is drained via the external cover. 

Recom-

mendation:

 To prevent dirt from depositing 

on the façade around the external cover, fit 

a water-repellent plaster system.

 

Wall thickness PP 45 min. 265 mm,  

wall thickness PPB 30 min. 320 mm.

 

PPB 30:

 The slide-in unit (slide-in module 

+ extension duct) must be appropriate for 

the wall thickness to avoid a ventilation 

short-circuit (lack of air). To ensure this, 

shorten the extension duct accurately.

 

PPB 30:

 With wall thicknesses of 500 to 

790 mm, use the optional PP 45 VS exten

-

sion kit. When installing, use the centring 

ring provided for the extension.

 

Observe permissible ranges for radio-con-

trolled units 

 Technical data PP 45.

 

Select installation position so as to avoid 

contamination and draughts.

 

Only connect PP 45 O/K devices to power 

modules PP 45 LT.

 

In case of thin walls, use the compensating 

frame PPB 30 ARE (stainless steel) or PPB 

30 ARW (white). This frame can be screwed 

to the wall with the fixing plate PPB 30 ARE 

BB or PPB 30 ARW BB. Compensating 

frames (depth 55 mm) are stackable. Only 

use stainless steel screws when mounting 

compensating frames made of stainless steel.

Summary of Contents for PushPull PP 45 RHK

Page 1: ...tructions for PushPull ventilation systems Notice de montage Gros uvre pour syst mes de ventilation PushPull UK FR PP 45 RHK PP 45 RHL PP 45 AK PP 45 AE PP 45 AW PP 45 AS PP 45 LE PP 45 LEV PP 45 LEW9...

Page 2: ...2...

Page 3: ...3...

Page 4: ...eckung Rohbauh lse kurz PP 45 RHK 0059 0081 Rohbauh lse lang PP 45 RHL 0059 0082 Wandh lse Putzschutzdeckel und Keile F r Montage diese Montageanleitung Rohbau Laibungselement PP 45 LE 0093 0179 nur f...

Page 5: ...er te pro Raum Zur Verf gung stehen PP 45 Ger te in den Ausf hrungen Objekt O Komfort K und die funkgesteuerten Varianten RC PPB 30 sind balancierte L ftungsger te die vorzugsweise f r den Einsatz in...

Page 6: ...mehrfach belegten Abgasanlage angeschlossen ist Explosionsgefahr Explosionsf hige Gase und St ube k nnen entz ndet wer den und zu schweren Explosionen oder Brand f hren L ftungsger t auf keinen Fall...

Page 7: ...aben installieren Insbesondere die Ausf hrungen zur D m mung und Schalld mmung beachten Verletzungs und Gesundheitsgefahr bei Einsatz von nicht zugelassenen Zubeh rkomponenten Das L ftungsger t ist mi...

Page 8: ...tung die W rmeenergie der Abluft an den W rmetauscher Jeweils nach 60 Se kunden wechselt die Luftrichtung und erm g licht so einen L ftungsbetrieb mit konstanter W rmer ckgewinnung ber einen Feuchtese...

Page 9: ...en L ftungsstufe 1 bis 5 23 28 33 37 40 dB A Bemessungsspannung Netzfrequenz 230 V 50 60 Hz Volumenstr me L f tungsstufe 1 2 3 4 5 15 20 30 36 42 m h Leistungsaufnahme 1 2 1 7 2 1 2 8 3 5 W Zul ssige...

Page 10: ...d nur f r Zuluftr ume geeignet PPB 30 Ger te sind vorzugsweise f r Abluftr ume vorgesehen Mindestabst nde beachten Ausreichend Arbeitsfreiraum vor dem Ger t sicherstellen f r Filterwechsel Geeignetes...

Page 11: ...lten Disbalancen die durch unterschiedliche L ngen der Steuerleitungen entstehen Installationsvorgaben bzgl der Kabell ngen und typen beachten Fehlerhafte Messwerte bei ungeeignetem Montageort der Ste...

Page 12: ...nur an W nden mit ausreichender Tragkraft vornehmen Die Wandh lse muss fest eingeputzt werden 1 Montageort e bestimmen Einbauma e und Mindestabst nde zur Wand und Decke beachten Leerrohr Kabeldurchf h...

Page 13: ...eckung PP 45 AK Kunststoff Montage VORSICHT Vorsicht beim Umgang mit scharf kantigen Geh useteilen z B bei Edelstahl Au enabdeckungen Schutzhandschuhe benutzen 1 Nach Beendigung der Au enputzarbeiten...

Page 14: ...ie Wandh lse setzen ausrichten und Befestigungsl cher markieren Positi on TOP beachten 2 L cher bohren und D bel einsetzen 3 Frontabdeckung vom Geh use abnehmen PPB 30 AK Unten auf die beiden Rasthe b...

Page 15: ...d nach unten schwenken Die Frontabdeckung muss unten an den beiden Rasthebeln R h rbar einrasten PPB 30 AE AW AS Frontabdeckung anbringen VORSICHT Vorsicht beim Umgang mit scharf kantigen Geh useteile...

Page 16: ...enputzes 20 bis 25 mm ber den Au enputz hinausstehen 1 Wandh lse DN 160 nicht im Lieferumfang 2 Gummidichtung Wandh lse 3 Laibungselement PP 45 LE 4 Edelstahl Aufnahme mit Abtropfkante und integrierte...

Page 17: ...tage kleber M versehen Laibungselement mit der Verl ngerung bzw dem Winkel verkleben Unbedingt die berg nge ringsum abdichten z B mit Klebeband Verl ngerung auf das gew nschte Ein bauma abs gen Auf b...

Page 18: ...cht zu fest Darauf achten dass die Aufnah me im unteren Bereich komplett abgedich tet ist i Wanddichtung 4 1 sch tzt bei Lecka gen damit anfallendes Kondenswasser nicht hinter den Putz laufen kann 8 L...

Page 19: ...tellende Elektronik Schalterdose ein zubauen Diese bietet ausreichend Platz f r den Anschluss der Leitungen an der Raumluftsteuerung Nach Innenputz und Malerarbeiten 1 Endmontage Set bestehend aus Ven...

Page 20: ...B 30 O K PP 45 VS Weitere Abmessungen Komponente Abmessungen BxHxT RLS 45 O RLS 45 K Raumluftsteuerung 80 x 80 x 49 mm DS45 RC Funkschalter 80 x 80 x 15 mm PP 45 EO EnOcean Erweiterungsmodul 80 x 80 x...

Page 21: ...al grille with external grille holder and wall seal For mounting these shell mounting instructions Optional Extension element PP 45 LEV 0093 1483 For mounting Chapter 10 Compensating frame PPB 30 ARE...

Page 22: ...e recommend multiple ventilation units per room for larger living units PP 45 units are available in the following models O for object K for comfort and RC for radio controlled PPB 30 are balanced ven...

Page 23: ...Never use ventilation unit in an explosive atmosphere Risk of explosion Explosive substanc es in lab extraction units may ignite and cause serious explosions or fire Aggressive substances may damage...

Page 24: ...ssories which have not been approved The ventilation unit is tested and approved with original accessories e g air filters The unit may only be operated with original components Modifications and alte...

Page 25: ...gy from the exhaust air to the heat exchanger during air extraction Every 60 seconds the air direction changes thereby permitting a ventilation mode with constant heat recovery In case of high air hum...

Page 26: ...1 to 5 23 28 33 37 40 dB A Rated voltage power frequency 230 V 50 60 Hz Volumetric flows for ven tilation levels 1 2 3 4 5 15 20 30 36 42 m h Power consumption 1 2 1 7 2 1 2 8 3 5 W Permissible ducti...

Page 27: ...air rooms PPB 30 units are the ideal choice for exhaust air rooms Observe minimum spacing Ensure sufficient space to work in front of the unit for filter change The customer should provide appropriate...

Page 28: ...Observe installation requirements relating to cable lengths and types Incorrect measurements if the installation location of the control and external sensors is inappropriate Avoid disturbing influenc...

Page 29: ...ng capacity The wall sleeve must be firmly plastered in 1 Determine installation location s Observe installation dimensions and minimum spacing to the wall and ceiling Fit empty ducting cable feedthro...

Page 30: ...tic Mounting CAUTION Exercise caution when handling housing parts with sharp edges e g stainless steel external covers Wear protective gloves 1 Once the external plastering is complete remove the plas...

Page 31: ...lace drilling template over the wall sleeve align it and mark the fixing holes Observe the TOP position 2 Drill the holes and insert dowels 3 Remove front cover from housing PPB 30 AK Push onto the tw...

Page 32: ...onto the housing from above and swing it downwards The front cover must audibly engage in the two locking levers R at the bottom PPB 30 AE AW AS Attaching front cover CAUTION Exercise caution when ha...

Page 33: ...external plastering once this plastering is applied 1 Wall sleeve 160 not in scope of supply 2 Rubber seal wall sleeve 3 Soffit element PP 45 LE 4 Stainless steel holder for drip edge and integrated...

Page 34: ...M all around slot on face end Glue the soffit element with the extension or angle Be sure to seal around the couplings e g with adhe sive tape Saw off extension to desired installation dimension Ensur...

Page 35: ...der is sealed completely at the bottom i Wall seal 4 1 protects against leaka ges and prevents any condensate pro duced from getting behind the plaster 8 Only mount soffit external grille 5 once the p...

Page 36: ...mer This provides sufficient space for the connection of the cables to the room air control After internal plastering and painting 1 Install final mounting set comprising fan slide in module and inter...

Page 37: ...B 30 O K PPB 30 O K PP 45 VS Other dimensions Component Dimensions WxHxD RLS 45 O RLS 45 K room air control 80 x 80 x 49 mm DS45 RC radio switch 80 x 80 x 15 mm PP 45 EO EnOcean extension module 80 x...

Page 38: ...de montage Gros uvre l ment d embrasure PP 45 LE 0093 0179 seulement pour le raccordement des appareils PP 45 l ment d embrasure joint en caoutchouc de gaine murale grille ext rieure en acier inoxydab...

Page 39: ...espaces similaires Ils conviennent aux constructions neuves et en r novation Les appareils sont con us pour 24h de service Le syst me de ventilation de l unit d utilisation doit tre agenc selon la nor...

Page 40: ...tra ne la mort ou de graves blessures si elle n est pas vit e AVERTISSEMENT signale une situa tion dangereuse ventuellement possible susceptible d entra ner la mort ou de graves blessures si elle n es...

Page 41: ...gement de l appareil par encrassement du ventilateur L utilisation de l appareil de ventilation est interdite pendant la phase de construction Des vapeurs de graisse et d huile en provenance de hottes...

Page 42: ...ations apport es aux appareils sont rigoureusement interdites et d gagent le fabricant de toute responsabilit et garantie Danger de mort d la pr sence de monoxyde de carbone en cas d uti lisation avec...

Page 43: ...de l air sortant l changeur de chaleur Apr s 60 secondes le sens de l air change et permet ainsi un mode de ventilation avec une r cup ration de chaleur constante La ventilation intensive peut tre act...

Page 44: ...ants porteurs comme par exemple le linteau ou l anneau d ancrage 7 Caract ristiques techniques 7 1 Caract ristiques techniques PP 45 Diam tre ext rieur 160 Longueur max de la gaine murale 500 ou 800 m...

Page 45: ...appareils de ventilation Combinaisons Nombre d appareils de ventilation Appareils de ventilation PP 45 O K Commande d air ambiant RLS 45 O K Admissible jusqu 3 RLS 45 K suppl mentaires 6 appareils PP...

Page 46: ...acte ment le tube de prolongation PPB 30 Pour les paisseurs du mur de 500 790 mm utiliser le kit de prolonga tion optionnel PP 45 VS utiliser pour la rallonge lors de l installation de la bague de cen...

Page 47: ...embrasure PP 45 LE et PP 45 LEV ne peuvent pas tre combin s avec des appareils PPB 30 9 Montage de la gaine murale et de la protection externe 9 1 Montage de la gaine murale PP 45 RHK RHL pour apparei...

Page 48: ...ale 160 et l aligner avec des cales en polystyr ne 3 R duire la gaine murale Respecter la saillie de la gaine murale par rapport au mur ext rieur Donn es pour le mur int rieur et ext rieur une fois cr...

Page 49: ...gants de protection 1 D s que le cr pi ext rieur est pos retirer le couvercle de protection du cr pi 2 D poser le cache de protection F du bo tier G de la protection externe 3 Placer le bo tier G l h...

Page 50: ...it de per age sur la gaine murale orienter et marquer les trous de fixation Respecter la position TOP 2 Percer les trous et ins rer les chevilles 3 Retirer le cache de protection du bo tier PPB 30 AK...

Page 51: ...bas Le cache de protection doit s encliqueter de mani re audible en bas sur les deux leviers cran R PPB 30 AE AW AS monter le cache de protection PRUDENCE Manipuler avec prudence les pi ces de bo tie...

Page 52: ...mier de condensat doit le d passer de 20 25 mm 1 Gaine murale 160 non comprise dans la fourniture 2 Joint en caoutchouc de la gaine murale 3 l ment d embrasure PP 45 LE 4 Support en acier inoxydable a...

Page 53: ...asure Pr paration de l l ment d embrasure R Rainure transversale M Colle de montage i Pour rallonges PP 45 LEV ou l ments d angle 90 PP 45 LEW90 Appliquer de la colle de montage M sur tout le pourtour...

Page 54: ...dans le canal d embrasure et le visser avec pr caution sans trop serrer avec les 4 vis Spax en acier inoxydable 4 2 fournies Veiller tancher compl tement la partie inf rieure du support i En cas de fu...

Page 55: ...nt Celle ci est assez vaste pour permettre le raccordement des c bles la commande d air ambiant Apr s la pose du cr pi int rieur et les travaux de peinture 1 Monter le kit de montage final constitu du...

Page 56: ...0 6940 info maico de PP 45 LEV ne peut pas tre combin avec PPB 30 PPB 30 O K PPB 30 O K PP 45 VS Autres dimensions Composant Dimensions lxhxp Commande d air ambiant RLS 45 O RLS 45 K 80 x 80 x 49 mm I...

Reviews: