10 Start-up | UK
49
10.4 Service menu for PP 45 RC
bold = factory setting
PP 45 RC LEDs
Parameter
Set value
Setting / description
The orange operating
mode LED flashes
once
per cycle
Supply air
mode
0
1
2
Supply air mode without over-
run
Supply air mode with overrun of
6 min. (red LED 1x)
Supply air mode with overrun of
15 min. (red LED 2x)
Supply air mode for exhaust air
units (e.g. ER.../ECA...) is released
and parameterised here.
Notice: The choice of overrun (6 or
15 minutes) depends on the unit.
ER 60 (0 min.), ER 60 VZ (6 min.),
ER 60 VZ 15 (15 min.).
The orange operating
mode LED flashes
twice
per cycle
Sensor
0
1
inactive
active (red LED 1x)
The PP 45 HYI internal humidity
sensor is activated here. This sen-
sor can be retrofitted as an option
(only in master unit) and is not
included in the scope of delivery.
The orange operating
mode LED flashes
three times
per cycle
Ventilation
levels
0
1
Ventilation level "0" possible
Ventilation level "0" blocked
(red LED 1x)
With the ventilation level "0"
blocked setting, the ventilation
units cannot be switched off on
this control. The units then run
with at least ventilation level 1.
The blue operating
mode LED flashes
once
per cycle
Duration of
intermittent
ventilation/
ventilation
level
1
2
3
10 minutes (red LED once)
30 minutes (red LED twice)
60 minutes (red LED three times)
Parameters for the duration of
intermittent ventilation (level 5)
and the duration of the ven-
tilation level when overriding
demand-driven operation are set
here (factory setting 30 minutes).