Maico EZR B Series Mounting And Operating Instructions Download Page 17

4. Product information │ UK 

 

15 

●  Reversing mode permitted. Flow rate in 

opposite air flow direction reduced by 
around 35 %. For reversing switch  

 Internet or catalogue. 

●  Thermal properties of fan designed for 

continuous operation. The fan motor may 
heat up impermissibly if the direction of 
rotation is changed frequently. 

●  EZR units (single-phase AC models) with 

capacitor motor Capacitor in the terminal 
box is ready to be connected. 

●  Thermal overload protection as standard. 

Exception: On request for DZR 25/4 D and 
pole-changeable units. 

 

4.3 Thermal overload protection 

The fan motor has thermal protection 
(temperature sensor in the motor winding). 
The overload protection automatically 
switches off the fan via the external control 
device in the event of overload (overheating). 
Exception: Pole-changeable units and  
DZR 25/4 D. 
The fan must remain switched off long enough 
for the motor and temperature limiter to cool 
down, before starting the fan back up. Depen-
ding on size and temperature conditions, it 
may take 

up to 30 minutes

 to cool down. 

Only switch unit on after this. 

EZR … 

Potential-free terminal connections, which 
must be connected to e.g. an MVE 10 motor 
protection switch or the control circuit of a 
contactor circuit. The MVE 10 is not suitable 
for EZR 25/4 D, EZR 30/6 B and EZR 35/6 B 
units. 

DZR ... 

Potential-free terminal connections, which 
must be connected to e.g. an MV 25 motor 
protection switch or the control circuit of a 
contactor circuit. 
 
 
 
 

Pole-changeable units DZR … and  
DZR 25/4 D 

Overload protection with a motor protection 
switch provided by the customer must be 
ensured for pole-changeable units. Use an 
optional pole changing switch, e.g. MAICO 
pole changing switch P1 or WP1, to change 
over the speed. 
 

5. Operation: Switching on/off 

The fan is switched on or off with a switch 
that is to be provided by the customer.  
The speed of EZR units can be controlled 
steplessly with an optional speed controller. 
EZR/DZR units can be switched in steps 
using an optional 5-step transformer. 
Ensure sufficient air supply during operation. 
 

6. Technical data 

For technical data, 

 the rating plate. 

●  For rating plate 

 the fan or these 

instructions. 

●  For dimensions and characteristic curves 

 catalogue or Internet. 

●  Internet 

 maico-ventilatoren.com or  

QR code on the fold-out page. 

Degree of protection

 

IP 55

*

 

Exception: IP 54 for 
EZR/DZR … 

D

 

Air volume, free outlet 
or free inlet 

500 to 14,800 m³/h, de-
pending on unit variant 

Weight 

5.7 to 41 kg, depen-
ding on unit variant 

Maximum air flow 
temperature 

40 °C 

*

   

IP 55 protection only guaranteed in hori-

zontal installation position or, in the case 
of vertical installation, with downward air 
flow.

 

 

Summary of Contents for EZR B Series

Page 1: ...ung Axial Rohrventilatoren Mounting and Operating instructions Axial duct fans Instructions de montage et Mode d emploi Ventilateurs de gaines h lico des EZR B DZR B EZR D DZR D www maico ventilatoren...

Page 2: ...ing diagrams Page 30 Scope of delivery Duct fan EZR B DZR B EZR D or DZR D Cable grommets in terminal box Capacitor for EZR units in terminal box These mounting and operating instructions Instructions...

Page 3: ...A B...

Page 4: ...rofachkraft vorgenommen werden Sie sind eine Elektrofachkraft wenn Sie aufgrund Ihrer fachlichen Ausbildung Schulung und Erfahrung die einschl gigen Normen und Richtlinien kennen die elektrischen Ansc...

Page 5: ...ung dieser Stoffe verwenden Explosionsf hige Gase und St ube k nnen entz ndet werden und zu schweren Explosionen oder Brand f hren Ventilator auf keinen Fall in explo sionsf higer Atmosph re einsetzen...

Page 6: ...en die Leiter ggf durch eine 2 Person zu sichern Sorgen Sie daf r dass Sie sicher stehen und sich niemand unterhalb des Ger tes aufh lt Hohe Ger uschemissionen in der N he des Ventilators Verwenden Si...

Page 7: ...fen Schutzleiterdurchgang am Geh use pr fen Ger t kann auch im Stillstand unter Spannung stehen und durch Sensorik Zeitverz gerung Feuchte etc oder dem Thermoschalter in der Motorwicklung automatisch...

Page 8: ...nicht geeignet f r EZR 25 4 D EZR 30 6 B und EZR 35 6 B Ger te DZR Die Anschl sse sind potentialfrei auf Klemmen gef hrt und m ssen an einem Motorvollschutzschalter z B MV 25 oder dem Steuerstromkreis...

Page 9: ...ngen mit zur Ger tetype Nennweite passenden Wickelfalzrohren 250 bis 600 fest verlegter elektrischer Zuleitung einer Installation an Wand Decke oder Konsole mit ausreichender Tragf higkeit Einbau mit...

Page 10: ...ch nach dem Ausl sen nicht selbstst ndig wieder einschalten Polumschaltbare Motoren mit Drehzahl verh ltnissen von 8 4 oder 4 2 sind im Dahlanderprinzip geschaltet F rderrichtungsumkehr bei DZR Ger te...

Page 11: ...mtliche Schraubenverbindungen auf festen Sitz pr fen 3 Sicherstellen dass die Luft ungehindert str men kann und sich keine Fremdk rper im Luftkanal befinden 4 Anschlussdaten mit den technische Daten...

Page 12: ...z trennen ein Wiedereinschalt Verbotsschild anbringen und Fehlerursache von einer Elektrofachkraft ermitteln lassen Bei wiederkehrenden St rungen das Ger t zur Reparatur in unser Werk schicken 14 Ersa...

Page 13: ...u are deemed a trained electrician if you are familiar with the relevant standards and guidelines can competently and safely connect units to an electrical power supply in line with the attached wirin...

Page 14: ...s may ignite and cause serious explosions or fire Never use fan unit in an explosive atmos phere risk of explosion Explosive gases and dusts may ignite and cause serious explosions or fire Never use f...

Page 15: ...ers Stability should be ensured if necessary have the ladders steadied by a 2nd person Ensure that you are standing securely and cannot lose your balance and that there is no one under the unit High n...

Page 16: ...lass I connect the PE conductor and check the connection Check protective conductor opening on housing Unit may also be energized even when at a standstill and may be switched on automa tically by sen...

Page 17: ...circuit The MVE 10 is not suitable for EZR 25 4 D EZR 30 6 B and EZR 35 6 B units DZR Potential free terminal connections which must be connected to e g an MV 25 motor protection switch or the control...

Page 18: ...s 250 to 600 to suit the unit type nominal size permanent electrical supply cable installation on a wall ceiling or bracket of sufficient load bearing capacity installation with flexible cuffs and fle...

Page 19: ...circuit Reverse in air flow direction for DZR units with reverse wiring of external conductor L1 and L2 Operation with frequency converters is only admitted if factory is consulted Feasibility must be...

Page 20: ...ns quietly and ensure if necessary 7 Switch off unit 12 Cleaning maintenance Cleaning Before cleaning switch off mains fuse secure against being accidentally switched back on and position a warning si...

Page 21: ...Only use original spare parts When ordering spare parts please provide the following details 1 Print no 0185 0928 0004 of these instructions 2 Rating plate no rating plate on unit or title page 3 Ite...

Page 22: ...tre ex cut s que par des lectriciens qualifi s On entend par lectricien qualifi une personne qui par son apprentissage sa formation et son exp rience conna t les normes et directives en vigueur est ca...

Page 23: ...e jamais utiliser le ventilateur dans une atmosph re explosive risque d explosion Des gaz et poussi res explosifs risquent de s enflammer et de provoquer une grave explosion ou un incendie Ne jamais u...

Page 24: ...chelles appropri s Assurer la stabilit le cas ch ant faire appel une 2 me personne pour maintenir l chelle Veiller avoir une position stable et ce que personne ne s journe sous l appareil missions so...

Page 25: ...ble Le couvercle de bornier doit tre pos correctement de mani re ce que le joint qui l entoure repose compl tement sur le bornier Type de protection IP 54 IP 55 assur uniquement avec montage horizonta...

Page 26: ...e en cas de surcharge surchauffe Exception appareils inversion de la polarit et DZR 25 4 D Avant sa remise en service le ventilateur doit rester l arr t jusqu refroidissement du moteur et du limiteur...

Page 27: ...transport Il est interdit toute personne de s journer sous des charges en suspens PRUDENCE Risque de coupure par les tranchants des t les du bo tier Porter des gants de protection ATTENTION Endommagem...

Page 28: ...r le site 5 Du c t air aspir et air comprim poser les tuyaux agraf s en spirale fleur du ventilateur Respecter les carts pour les manchettes flexibles ou les manchettes de raccordement flexibles types...

Page 29: ...tesse transformateur 5 plots Chapitre 10 2 ou 10 3 10 Poser le couvercle du bornier Veiller la propret du bornier et l tanch it du couvercle de bornier qui doit reposer en affleurement avec le bornier...

Page 30: ...ruits atypiques D tection d erreurs et r parations uniquement par des lectriciens professionnels Dysfonction nement Cause mesure Le ventilateur ne se met pas en marche Pas de tension du secteur Contr...

Page 31: ...Fax 49 7720 694 175 Courriel ersatzteilservice maico de 15 D montage Seul un lectricien qualifi peut se charger du d montage 1 D connecter le fusible secteur s curiser et apposer un panneau d avertiss...

Page 32: ...er STX STSX With STX STSX speed controller Avec variateur de vitesse STX STSX EZR B EZR D S1 Aus Taster Off switch Bouton d arr t S2 Ein Taster On switch Bouton de marche Q1 Sch tz US 16 Contactor US...

Page 33: ...vec disjoncteur protecteur de moteur MVE 10 1U 1V1W 1U 1V1W M 1 L N TKTK TKTK S2 S1 Q1 L N PE 3 2 1 TRE 1 2 3 EZR B EZR D 1U 1V1W 1U 1V1W M 1 L N TKTK TKTK S2 S1 Q1 L N PE 3 2 1 TRE 1 2 3 EZR 25 2B S1...

Page 34: ...r protection switch Avec variateur de vitesse STX STSX et disjoncteur protecteur de moteur MVE 10 EZR 25 2 B Mit Drehzahlsteller STX STSX und Motorschutzschalter MVE 10 With STX STSX speed controller...

Page 35: ...ransformator TRE und Motorschutzschalter MVE 10 With TRE 5 step transformer and MVE 10 motor protection switch Avec transformateur de tension 5 plots TRE et disjoncteur protecteur de moteur MVE 10 1U...

Page 36: ...ZR B Mit Motorschutzschalter MV 25 und 5 Stufentransformator TR With MV 25 motor protection switch and TR 5 step transformer Avec disjoncteur protecteur de moteur MV 25 et transformateur de tension 5...

Page 37: ...with Dahlander circuit With MV25 motor protection switch inversion de la polarit 2 vitesse de rotation avec commutation Dahlander Avec disjoncteur protecteur de moteur 1U 1V 1W 1U 1V 1W TKTK TKTK M 3...

Page 38: ...formator TR 0 4 With MV motor protection switch and 5 step transformer TR 0 4 Avec disjoncteur protecteur de moteur MV et transformateur de tension 5 plots TR 0 4 1 2 3 1 2 3 3 M DZR25 4D L1 L2 L3 PE...

Reviews: