Semi-centrifugal duct fans
ERM.. and DRM..

Intended use

ERM.. and DRM.. fans are used 

for air extraction

or ventilation

 of commercial premises, canteens,

production sites, fitness rooms, workshops, labo-
ratories, conservatories etc.

They are also used in air extraction systems for
machine and workplace extraction or manufacturing
areas.

ERM.. : standard model single-phase AC motor

DRM..: special version three-phase AC motor

It is permitted to transport air or air-based
mixtures

. It is not permitted to transport gasses,

mist or vapours or mixtures thereof, as well as
liquids and solids. Operation is also not permitted
in areas subject to explosion hazards or in the area
of inflammable materials.

The fan may only be used when correctly installed
in ducts, if safety is guaranteed through safety
equipment in accordance with DIN EN 294 or other
structural protective measures.

Modifications and changes to the device are not
permitted. MAICO is not liable for damage caused
by non-authorised use.

Fig. 1 Components/spare parts

Advice about ordering spare parts:

 Always

quote the print number 0185.0845.0008 of these
instructions, the rating plate number (on the housing)
and the relevant item number..

1

Inlet flange

2

Impeller

3

Motor

4

Housing

5

Terminal box

6

Capacitor (only with ERM..)

Fig. 2 ERM../DRM.. with duct connection on
both sides

Fig. 3 ERM../DRM.. with duct connection on
one side / free inlet

Fig. 4 ERM../DRM.. in vertical installation
position, with downwards air flow direction

System components

A

Fan ERM.. /DRM..

B

REM.. reducer

C

ELM.. flexible cuffs

D

Duct / flexible duct

E

FUM.. mounting foot

F

SGM.. protective grille

G

Ceiling / wall / girder

       Safety instructions

Read the instructions through carefully and
completely before you install the fan or
commission it. Keep the instructions some-
where safe.

Installation should only be carried out by
specialists with knowledge of and experience in
ventilation technology.

Only qualified electricians are permitted to make
the electrical connections and/or repairs.

During assembly and electrical installation, please
take note of the valid regulations, in particular
DIN VDE 0100 and the pertinent sections.

The fan motor is thermally protected. It must
be connected to an external control unit with
automatic switch-off, such as the Maico
MVE 10 motor protection switch for example,
or to a self-latching  contactor circuit. The
control unit should not be able to switch itself
back on after being triggered.

Before starting it up again, leave the fan switched
off long enough for the motor and temperature
limiter to cool down. Depending on the size and
the temperatures involved, the cool-down time
could be up to 30 minutes. Only then should you
switch it back on.

Before removing the safety devices, the fan must
be completely removed from the power supply.

If the fans are being used with air-ventilated
fireplaces, you must ensure that there is sufficient
supply air intake.

The fan is designed in accordance with VDE
safety requirements within the framework of the
equipment and product safety act as well as the
pertinent regulations laid down in the EC
directives.

– Subject to change ! –

6

Summary of Contents for ERM 15

Page 1: ...mi centrifugal duct fans Ventilateurs h lico centrifuges www maico de ERM 15 ERM 18 ERM 22 ERM 25 ERM 28 DRM 18 DRM 22 DRM 25 DRM 28 Montage Bedienungsanleitung Mounting operating instructions Instruc...

Page 2: ...2...

Page 3: ...rection System components A Fan ERM DRM B REM reducer C ELM flexible cuffs D Duct flexible duct E FUM mounting foot F SGM protective grille G Ceiling wall girder Safety instructions Read the instructi...

Page 4: ...aced on sensitive components such as the impeller or terminal box Maico will not consider any replacements or guarantee claims in the event of incorrect transport methods Storage The fan should only b...

Page 5: ...ata Protective temperature limiter Nominal voltage at 50Hz 60Hz 250 VAC Nominal current ohmic cos 1 0 max 2 5 A Nominalcurrent inductive cos 0 6 max 1 6 A Starting up Function test Before starting up...

Page 6: ...M15 18 Motor protection switch provided by customer MVE10 not for ERM15 18 Disjoncteur protecteur de moteur sur le site MVE10 non compatible avec ERM15 18 ST ST STU STS 2 5 5 Drehzahlsteller Speed con...

Page 7: ...le site M 1 K1 S2 S1 4 N 2 TKTK 3 4 2 1 N ERM22 ERM25 ERM28 ERM18 L N PE ST 7 0 7 4 0 0 2 1 1 6 0 1 ERM18 ERM22 ERM25 ERM28 mit Drehzahlsteller with speed controller avec r gulateur de vitesse S1 Aus...