11. Fault rectification │
GB
17
11.
Fault rectification
A fault can occur if, for example, the airstream
temperature increases or if the fan motor is blocked.
The overload protection kicks in and the fan switches
off.
If no motor protection switch or self-holding,
cabled control contactor is used, the fan starts
up again automatically after the fan motor has
cooled down.
DANGER
Risk of electric shock.
Disconnect the device completely from
the mains power supply and protect it
against be started up before starting
work on the electrical system or in the
case of a fault.
Also make sure that the TC power
circuit to the thermal contacts is
completely disconnected from the
power supply.
CAUTION
Danger from rotating impeller.
Make sure the impeller has come to a
complete stop before opening the
service door.
EKR 20-2 ... EKR 40-2
If the fan fails to operate, always check whether the
mains fuse is switched on.
Check that the cabling of the fan is correct.
If a motor protection switch is used as a safety
device, the motor protection switch must be activated
in the case of a fault. Before starting the fan, let the
fan motor cool down and release the motor
protection switch. The fan starts up again.
If a self-holding, cabled control contactor is used as
a safety device, the control contactor must be
activated in the case of a fault. Before starting the
fan, let the fan motor cool down and release the
control contactor. The fan starts up again.
If the fault still continues or occurs again, disconnect
the device from the mains and call on the services of
a trained electrician.
EKR 25 FU … EKR 40 FU
Motor protection
: The motor does not require
any external motor protection. It is protected
against slowly developing overload as well as
blocking (IEC 34-11: TP 211).
Voltage surge protection
: The motor is
protected against pulse overvoltage
(→ EN 61800
-3).
You will find detailed information about fault
messages in the in the additional "Grundfos"
Motor manual.
If the fan fails to operate, always check whether the
mains fuse is switched on.
Check that the cabling of the fan is correct.
If the fault still continues or occurs again, disconnect
the device from the mains and call on the services of
a trained electrician.
12.
Dismantling
DANGER
Risk of electric shock.
Disconnect the device completely from
the power supply and secure it against
being started up.
Dismantling may only be undertaken by a specialist
electrician.
13.
Disposal
Dispose of the unit once it has reached the end of its
working life according to the regulations valid where
you are.
Do not dispose of it in domestic waste!
The unit contains in part material that can be
recycled and in part substances that should
not end up as domestic waste.
i
i
i
i
Summary of Contents for EKR 20-2
Page 9: ...14 Schaltbilder DE 9 14 Schaltbilder EKR 2 EKR 2 mit MVE 10 und TRE...
Page 10: ...DE 14 Schaltbilder 10 EKR FU Standardanschluss EKR FU Optionen EKR FU Optionen...
Page 18: ...GB 14 Wiring diagrams 18 14 Wiring diagrams EKR 2 EKR 2 with MVE 10 and TRE...
Page 19: ...14 Wiring diagrams GB 19 EKR FU Standard connection EKR FU Options EKR FU Options...
Page 27: ...14 Sch mas de branchement FR 27 14 Sch mas de branchement EKR 2 EKR 2 avec MVE 10 et TRE...