UK │ 8. Installation preparations 

 

14 

8.2 Ceiling 

1.  Perform installation preparations as 

described in Chapter 8.1. 

 

2.  Prepare cover [4]. Remove cover from 

housing before drilling. Drill through cover 

using an appropriate drill bit, in order to 

prevent damp and the build-up of germs  

in the fan housing. 

 

 

NOTICE

 

Danger of short-circuits and damage to 

unit if condensation builds up in the fan 

housing. 

Thermally insulate ventilation 

ducts in professional manner. Allow for a 

condensation drain or condensate collector 

in the riser. 

 

8.3 Duct 

1.  Debur edges on the inside of the duct. 
2.  Perform installation preparations as 

described in Chapter 8.1. 

 

8.4 Housing [1] 

 

NOTICE

 

Damage to unit/functional problems  

in the event of rubbing impeller [7].  

Do not fit connecting flange so it is twisted 

or crushed. Make sure there is a level 

seating. 

 

 

 

1.  Check that the sealing ring [5] is present at 

the rear of the housing and that it is seated 

correctly. 

2. 

ECA piano STANDARD, ECA piano TC:

 

If necessary, supply additional material 

(e.g. foam strip), to fix the unit to the wall 

or duct. Make sure there is a minimum 

distance of 20 mm to the end of the 

connector. Don’t apply any adhesive to the 

shutter bearing [6], see arrow. 

 

ECA piano H: 

Install foam strip as 

described before. 

This is important to 

prevent the unit from drawing any air in 

from outside.

 

 

8.5 Preparation for operation with 

speed controller 

Only with ECA piano STANDARD.  

Not permitted for TC or H models. 

 

1.  Remove shutters [6]. 
2.  Use an STU 1, ST 1 or STS 2,5 from the 

Maico range of accessories.. 

 

 

NOTICE

 

The fan will not operate and cause 

malfunctions if the output voltage from 

the speed controller is too low. 

Take note of the advice given in the speed 

controller operating instructions. 

Always set the minimum speed at the  

speed controller, such that the motor starts 

up again after a power failure.

 

 

 

There can be vibration noises 

caused by the phase control 

technology. 

 

Summary of Contents for ECA piano STANDARD

Page 1: ...Kleinraumventilatoren Mounting and Operating instructions Small room fans Instructions de montage et Mode d emploi A rateurs pour petites pi ces ECA piano STANDARD ECA piano TC ECA piano H B www m ai...

Page 2: ...2...

Page 3: ...der Elektrik d rfen nur von einer Elektrofachkraft vorgenommen werden Sie sind eine Elektrofachkraft wenn Sie aufgrund Ihrer fachlichen Ausbildung Schulung und Erfahrung die einschl gigen Normen und...

Page 4: ...shauben k nnen den Ventilator und die Luftleitungen verschmutzen und die Leistungsf higkeit reduzieren Ventilator auf keinen Fall zur F rderung fetthaltiger Luft verwenden z B in Kombination mit Dunst...

Page 5: ...le Versorgungs stromkreise abschalten Netzsicherung ausschalten und gegen Wiedereinschalten sichern Ein Warnschild sichtbar anbringen Bei der Elektroinstallation die geltenden Vorschriften beachten z...

Page 6: ...k ca 12 min Umgebungsbedingungen und 6 Grenzen f r den Betrieb Zul ssige H chsttemperatur des F rder mediums 40 C St rfestigkeit nach EN 55014 2 je nach Impulsform und Energieanteil 1000 bis 4000 V Be...

Page 7: ...tel 8 1 beschrieben vornehmen 8 4 Geh use 1 ACHTUNG Ger tebesch digung Funktionsst rung bei streifendem Fl gelrad 7 Ger t weder verspannt noch gequetscht einbauen F r ebenen Untergrund sorgen 1 Geh us...

Page 8: ...auch Positionen P in Abb A ECA piano TC Poti P Nachlaufzeit ab Werk ca 6 Minuten 9 00 Uhr ECA piano H Poti P1 Nachlaufzeit ab Werk ca 12 Minuten 12 00 Uhr ECA piano H Poti P2 Feuchteschaltpunkt ganz l...

Page 9: ...h Abk hlung selbstt tig wieder ein Ventilator schaltet nicht aus oder Ventilator schaltet ungewollt ein Durch eine Glimmlampe im Kontrollschalter parallel ver legte Leitungen Induktion oder Transforma...

Page 10: ...electrician is permitted to work on the electrics You are deemed a trained electrician if you are familiar with the relevant standards and guidelines can competently and safely connect units to an ele...

Page 11: ...wledge Fan may only be installed commissioned cleaned and maintained by people who can safely recognise and avoid the risks associated with this work Danger of injury due to suction from fan and rotat...

Page 12: ...ating plate The degree of protection stated on the rating plate is only guaranteed if installation is undertaken correctly and if the connection cable is correctly guided through the cable grommet The...

Page 13: ...ion Connect a X2 capacitor 220 nF 250 V against neutral lead in case of a switch with negative glow lamp The capacitor is to be provided by the customer Storage Store unit exclusively in a dry locatio...

Page 14: ...ring 5 is present at the rear of the housing and that it is seated correctly 2 ECA piano STANDARD ECA piano TC If necessary supply additional material e g foam strip to fix the unit to the wall or du...

Page 15: ...rox 12 minutes 12 o clock ECA piano H potentiometer P2 Humidity switching point setting to the far left approx 50 r h 12 o clock see figure approx 70 r h factory setting setting to the far right appro...

Page 16: ...tch negative glow lamp parallel installed wires mutual induction or transformers respectively other electrical parts Recommendation Connect a X2 capacitor 220 nF 250 V against neutral lead Dismantling...

Page 17: ...p rience dans la technique de ventilation est autoris effectuer le montage Les travaux sur le syst me lectrique ne doivent tre ex cut s que par des lectriciens qualifi s On entend par lectricien quali...

Page 18: ...ifs risquent de nuire la sant notamment s ils sont diffus s dans les pi ces par le ventilateur Ne jamais utiliser le ventilateur pour diffuser des produits chimiques ou gaz vapeurs agressifs Des vapeu...

Page 19: ...ant de retirer le cache de l lectronique couper tous les circuits d alimentation lectrique d sactiver le fusible secteur s curiser contre toute remise en service intempestive et apposer un panneau d a...

Page 20: ...nt par l interrupteur d clairage Si l humidit relative est sup rieure au point de commutation il est impossible d arr ter le ventilateur m me avec l interrupteur d clairage Le ventilateur s arr te si...

Page 21: ...e le c ble secteur encastr jusqu au lieu de montage Pour les carte ments voir ci dessus Ce faisant faire sortir le c ble secteur d au moins 110 mm du mur 8 2 Plafond 1 Pr parations de montage comme d...

Page 22: ...se R gler toujours la vitesse de rotation minimale sur le r gulateur de vitesse de sorte que le moteur red marre apr s une panne de courant La technique de r glage par redres sement l entr e des phase...

Page 23: ...secteur s curiser contre toute remise en service intempestive et apposer un panneau d avertissement 2 Si le cache 4 est tr s sale le retirer avec pr caution du ventilateur chap 13 et le nettoyer avec...

Page 24: ...e l appareil du secteur couper le fusible secteur le prot ger contre toute remise en service intempestive et apposer un panneau d avertissement de mani re bien visible 2 Tirer d abord le cache 4 dans...

Page 25: ...25 Schaltbilder 15 ECA piano STANDARD ECA piano TC ECA piano H Variante 1 Variante 2 15 Schaltbilder Wiring diagrams Sch mas de branchement...

Page 26: ...26...

Page 27: ...27...

Page 28: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Germany Service 49 7720 6940 technik maico de 04 18_Es 0185 1111 0005_RLF 7_04 18_DSW...

Reviews: