12 Fault rectification
21
3. Refit the internal grille/shutter frame.
12 Fault rectification
Fault finding only by qualified electrician.
Call on the services of a qualified electrician
any time there is a fault. Repairs should only
be carried out by a qualified electrician.
Fault
Cause, measures
Fan does not switch
on.
•
VZ or F units
: Wait for
start delay (approx. 50
seconds).
•
No mains voltage.
Check whether the
mains fuse has failed.
Switch on if necessary.
•
Impeller is blocked.
Rectification may
only be carried out by
a trained specialist:
Unlock and remove the
internal grille/shutter
frame. Check impeller
and clean if necessary.
Fan does not switch
off.
•
VZ or F units:
Wait for
overrun time (approx. 6
minutes).
Motor’s thermal over-
load protection
switches the fan off.
•
Motor too hot.
Wait
until the motor has
cooled down. Cool-
down time can take up
to 10 minutes. Unit
switches back on auto-
matically after cooling
down.
Lamellae do not open
or close for K units.
•
Lamellae very dirty or
blocked.
Clean lamel-
lae. Check whether
there are any objects
between the lamellae.
If so, remove them.
13 Spare parts
Spare parts may only be sourced from and
fitted by a specialist installer.
Designation
Article no.
Circuit boards
PL ECA 100/120
E101.1010.9000
Covers
ABD ECA 120 1
E059.1010.9000
ABD ECA 120 2
E059.1010.9100
Thermostatic bimetal strip
TB ECA 120 K
E180.0913.9100
Shutter frame
ABDK ECA 120 1
E059.1011.9001
ABDK ECA 120 2
E059.1011.9101
Summary of Contents for ECA 120
Page 2: ...Inhaltsverzeichnis Deutsch 3 English 14 Fran ais 25...
Page 12: ...16 Schaltbilder 12 ECA 120 VZ ECA 120 F ECA 120 P ECA 120 24 V ECA 120 K...
Page 23: ...16 Wiring diagrams 23 ECA 120 F ECA 120 P ECA 120 24 V ECA 120 K ECA 120 KVZ...
Page 37: ...Notizen...
Page 38: ......
Page 39: ......