13 Fault rectification

31

3. Attach cover, switch on mains fuse, remove

warning sign and carry out function test.

13 Fault rectification

 Fault finding only by qualified electrician.

Call on the services of a qualified electrician
any time there is a fault. Repairs should only
be carried out by a qualified electrician.

Switch off mains fuse, secure against being acci-
dentally switched back on and position a warning
sign.

Fault

Cause, measures

Fan does not switch
on.

No mains voltage.

Check whether the
mains fuse has failed.
Switch on if necessary.

Impeller is blocked.
Rectification may
only be carried out by
a trained specialist:

Remove cover. Unlock
internal grille or internal
shutter via locking
hooks. Check impeller
and clean if necessary.

Humidity control is
not working correctly/
is faulty with RCH
units.

 Call on the ser-

vices of a trained spe-
cialist.

Motor’s thermal over-
load protection
switches the fan off.

Motor too hot.

 Wait

until the motor has
cooled down. Cool-
down time can be up to
10 minutes. Unit
switches back on auto-
matically after cooling
down.

Fan doesn’t react to
radio commands

Fans are not correctly
set up.

 Delete trans-

mitter of all compon-
ents (delete mode).
Delete the transmitter
on the RLS RC. Power
the fan off briefly. Then
re-teach the compon-
ents.

Fans are out of range.

Switch repeater mode
on at a fan that is
within range. If the
range is still insuffi-
cient, deploy additional
repeaters (to be
provided by the cus-
tomer).

14 Spare parts

 Spare parts may only be sourced from and

fitted by a specialist installer.

Designation

Article no.

Sensors

SE ECA 100 ipro H

E157.0141.0000

Covers

ABD ECA 100 ipro 1

E059.2022.9000

ABD ECA 100 ipro 3

E059.2022.9200

Electronics covers

ABDE ECA 100 ipro 1

E059.2010.0000

ABDE ECA 100 ipro 2

E059.2010.9000

In case of questions, please contact:

Maico Elektroapparate-Fabrik GmbH
Steinbeisstraße 20
78056 Villingen-Schwenningen, Deutschland

Summary of Contents for ECA 100 ipro RC

Page 1: ...Installation and operating instructions Notice de montage et mode d emploi Kleinraumventilatoren Funk Small room fans radio controlled A rateurs pour petites pi ces radio ECA 100 ipro RC ECA 100 ipro...

Page 2: ...Inhaltsverzeichnis Deutsch 3 English 18 Fran ais 33...

Page 3: ...Ger te bersicht 3 Ger te bersicht 1 Geh use mit Motor 2 Fl gelrad 3 Leitungst lle 4 Elektronikabdeckung 5 Innengitter feststehend 6 Abdeckung 7 Designabdeckung 8 Elektronikplatine 9 Feuchtesensor...

Page 4: ...ntabelle 9 7 Montagevorbereitungen 9 7 1 Wand 9 7 2 Decke 9 7 3 Rohr 10 8 Montage und Inbetriebnahme 10 8 1 Ventilator 10 8 2 Geh useeinbau 10 8 3 Elektrischer Anschluss 11 8 4 Endmontage 11 8 5 Inbet...

Page 5: ...itshinweise 4 1 Allgemeine Sicherheitshinweise Das Ger t darf in folgenden Situationen auf kei nen Fall eingesetzt werden GEFAHR Entz ndungs Brandgefahr durch brennbare Materialien Fl ssigkeiten oder...

Page 6: ...luftabh ngiger Feuerst tte unbedingt f r eine ausreichende Zuluftnachstr mung sorgen GEFAHR Gefahr durch Stromschlag bei Betrieb mit nicht komplett montiertem oder besch digtem Ventilator Vor dem Abne...

Page 7: ...ert liegt bei 48 relativer Luftfeuchte Steigt die Raumfeuch te um 7 an schaltet der Ventilator automatisch mit Leistungsstufe 1 78 m h ein Steigt die Raumfeuchte weiter an schaltet das Ger t in Leistu...

Page 8: ...Vorrang vor der RLS RC Einstellung Wird ein Funkschalter bet tigt schaltet der zu geordnete Ventilator in die manuell gew hlte Leistungsstufe Nach 30 Minuten ohne Bet tigung Timeout wird wieder auf d...

Page 9: ...equenzbereich nach EN 300220 1 868 35 MHz Reichweiten im Geb u de je nach Bausub stanz Raumluftsteuerung RLS RC Ventilator Funkschalter DS RC Ventilator Ventilator Ventilator Signalverst rker Ventilat...

Page 10: ...Fl gelrad Flanschh lse weder verspannt noch gequetscht einbauen F r ebenen Untergrund sorgen 1 Geh use in Wanddurchbruch Wandh lse ste cken TOP oben 3 Leitungst lle 2 Geh use waagerecht ausrichten un...

Page 11: ...mm abisolieren 11 Federklemme 12 Anschlussschaltbild 2 Netzleitung an Federklemme anschlie en Schaltbilder 50 3 Sitz der Leitungst lle kontrollieren Diese muss gut abdichten 8 4 Endmontage ACHTUNG Kur...

Page 12: ...4 Geh useabdeckung inkl Designabdeckung vorsichtig auf das Geh use dr cken bis diese im Schnapper einrastet 5 Funktionstest mit allen Systemkomponenten durchf hren 9 2 Tipps zum Einlernen von Funk ko...

Page 13: ...eingelernt Funkschalter einlernen Bei Doppelwippenschaltern DS RC beide Wip pen separat einlernen 2 Kan le 1 Am Empf ngerventilator den Einlernmodus aktivieren LED blinkt Einlernmodus ist aktiviert 2...

Page 14: ...oder nicht mehr identifizierbarem Sender m ssen eventuell alle Sender gel scht werden Systemkomponenten sind dann wieder neu einzulernen empfehlenswert falls ein Sen der verloren wurde oder defekt ist...

Page 15: ...mme f r Mischsys tem ECA ipro RC RCH ER 100 RC Sys temstu fe 0 Sys tem stufe 1 Sys tem stufe 2 Sys tem stufe 3 Pro gram m P1 Mas ter ECA Aus Leis tungs stufe 1 Leis tungs stufe 1 Leis tungs stufe 2 Sl...

Page 16: ...ausbauen Fl gelrad berpr fen und ggf reinigen Feuchtesteuerung bei RCH Ger ten arbeitet nicht korrekt ist de fekt Fachkraft hinzu ziehen Thermischer berlas tungsschutz des Mo tors schaltet den Ven ti...

Page 17: ...n 15 Demontage Die Demontage ist nur durch Elektrofachkr fte zul ssig 1 Abdeckungen abnehmen 2 Elektronikabdeckung entfernen 3 Netzleitung entfernen 4 Ventilator ausbauen 16 Umweltgerechte Entsorgung...

Page 18: ...Unit overview 18 Unit overview 1 Housing with motor 2 Impeller 3 Cable grommet 4 Electronics cover 5 Internal grille fixed 6 Cover 7 Designer cover 8 Electronic circuit board 9 Humidity sensor...

Page 19: ...aration for installation 24 7 1 Wall 24 7 2 Ceiling 24 7 3 Duct 24 8 Installation and commissioning 24 8 1 Fan 24 8 2 Housing installation 25 8 3 Electrical connection 26 8 4 Final mounting 26 8 5 Com...

Page 20: ...ions 4 1 General safety instructions The unit must not be used in the following situ ations under any circumstances DANGER Risk of combustion fire from flammable materials liquids or gases in the vici...

Page 21: ...nd position a visible warning sign Only operate the fan when it is completely in stalled Do not commission a damaged unit DANGER Danger if the relevant regula tions for electrical installations are no...

Page 22: ...ue If humidity falls below the reference value the power level is also switched back If an RLS RC is deployed operation is done in line with the setting on the RLS RC In the case of operation without...

Page 23: ...on the automatic humidity function has priority when operating in holiday mode Switching through the DS RC or through a radio window contact is possible dur ing humidity operating mode D Radio window...

Page 24: ...co ventil atoren com 7 Preparation for installation 7 1 Wall Use mounting material suitable for base and of sufficient dimensions Ensure sufficient supply air The prescribed minimum distances to the w...

Page 25: ...dowel holes see arrow 3 Drill dowel holes with a of 6 mm and insert dowels 4 Push cable grommet carefully out of housing and remove it NOTICE Danger of short circuits damage to the unit Water will pen...

Page 26: ...Check position of cable grommet It must be well sealed 8 4 Final mounting NOTICE Danger of short circuits and damage to the unit Humidity will penetrate if electron ics cover is not fitted correctly P...

Page 27: ...cover onto the housing until it en gages with the safety catches 5 Perform function test with all system compon ents 9 2 Tips for teaching in radio com ponents A fan automatically becomes a master if...

Page 28: ...ase of double rocker switches DS RC both rockers have to be taught in separately 2 channels 1 Activate teach in mode on the receiver fan LED flashes Teach in mode is activated 2 Press the radio switch...

Page 29: ...t is faulty or that can no longer be identified it is possible that all transmit ters must be deleted System components then have to be taught in again This is recommended if a transmitter was lost or...

Page 30: ...s with free outlet RLS RC pro gram for mixed sys tem ECA ipro RC RCH ER 100 RC System level 0 Sys tem level 1 Sys tem level 2 Sys tem level 3 Pro gram P1 Mas ter ECA Off Power level 1 Power level 1 Po...

Page 31: ...ialist Motor s thermal over load protection switches the fan off Motor too hot Wait until the motor has cooled down Cool down time can be up to 10 minutes Unit switches back on auto matically after co...

Page 32: ...The unit and the packaging contain parts that can be recycled and should not end up in the do mestic waste Dispose of the packaging material and the unit in an environmentally friendly way in complia...

Page 33: ...eil 33 Vue d ensemble de l appareil 1 Bo tier avec moteur 2 H lice 3 Manchon de c ble 4 Cache lectronique 5 Grille int rieure fixe 6 Cache de protection 7 Cache de protection design 8 Platine lectroni...

Page 34: ...7 2 Plafond 40 7 3 Gaine ronde 40 8 Montage et mise en service 41 8 1 Ventilateur 41 8 2 Montage du bo tier 41 8 3 Branchement lectrique 42 8 4 Montage final 42 8 5 Mise en service 43 9 Composants rad...

Page 35: ...par gaine rectangulaire ou ronde branchement lectrique encastr Jusqu 3 a rateurs peuvent tre interconnect s Cet appareil est exclusivement r serv l usage domestique et similaires 4 Consignes de s cur...

Page 36: ...isque de blessure et pour la sant en cas de modifications ou de transformations ou encore en cas d utilisation de composants non autoris s Le fonctionnement n est autoris qu avec des composants d orig...

Page 37: ...ce Les niveaux de puissance peuvent tre r gl s manuellement avec l interrupteur radio et ou au tomatiquement avec la commande radio RLS RC Marche Arr t par interrupteur radio DS RC op tionnel ou comma...

Page 38: ...hu midit r gulation automatique de l humidit Le syst me MAICOsmart peut tre command par un interrupteur radio et ou la commande d air ambiant RLS RC un interrupteur radio permet de s lectionner 2 niv...

Page 39: ...le ven tilateur s arr te nouveau fen tre encore ou verte ou revient au mode r gl sur RLS RC fen tre ferm e E Commande d air ambiant RLS RC com mande radio EnOcean Pour des informations sur la commande...

Page 40: ...au plafond selon la fi gure 1 Assurer un support plan au niveau du bo tier 2 Pratiquer un per age de cloison ou percer un avant trou Diam tre minimal 105 mm Recommandation utiliser une gaine mu rale...

Page 41: ...ort plan 1 Introduire le bo tier dans le per age de cloi son la gaine murale TOP haut 3 Manchon de c ble 2 Positionner le bo tier l horizontale et marquer les deux orifices des chevilles voir fl ches...

Page 42: ...longueur de 90 mm D nuder les conducteurs individuels sur 9 10 mm 11 Borne ressort 12 Sch ma de branchement 2 Brancher le c ble secteur sur la borne res sorts Sch mas de branchement 50 3 Contr ler l a...

Page 43: ...urs es claves 3 Sur les ventilateurs esclaves 2 ventilateurs max initialiser l interrupteur radio et les contacts de fen tres radio 4 Appuyer avec pr caution le cache du bo tier ainsi que le cache de...

Page 44: ...or rectement re u la LED de la touche du r cepteur reste allum e pendant 1 seconde L metteur a t initialis Initialisation de l interrupteur radio En pr sence d interrupteurs doubles bascules DS RC ini...

Page 45: ...du ventilateur esclave jusqu ce que la LED du ventilateur esclave s allume 1 fois bri vement Le t l gramme d initialisation est envoy Une initialisation r ussie est signal e par l allumage de la LED d...

Page 46: ...Les ventilateurs sont mis en marche arr t s soit sur la commande d air ambiant RLS RC soit par l interrupteur radio DS RC soit par un contact de fen tre radio fournir par le client ECA 100 ipro RCH L...

Page 47: ...entretien 12 Nettoyage Nettoyer r guli rement le ventilateur no tamment apr s une immobilisation prolong e ATTENTION Endommagement de l appareil en cas d utilisation de produits de nettoyage in correc...

Page 48: ...s mode Effacement Ef facer l metteur sur la RLS RC Mettre bri ve ment les ventilateurs hors tension Ensuite r initialiser des compo sants Les ventilateurs sont hors de port e Acti ver le mode R p teur...

Page 49: ...ballage ainsi que l appareil dans le respect de l environnement conform ment aux prescriptions en vigueur dans votre pays Mentions l gales Maico Elektroapparate Fabrik GmbH Traduc tion du mode d emplo...

Page 50: ...Schaltbilder Wiring diagrams Sch mas de branchement 50 Schaltbilder Wiring diagrams Sch mas de branchement ECA 100 ipro RC ECA 100 ipro RCH...

Page 51: ...Notizen...

Page 52: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de 0185 1148 0000_RLF 9_12 21_DSW AS...

Reviews: