UK │ 12. Cleaning, maintenance 

 

18 

12. Cleaning, maintenance 

Cleaning: 

Before cleaning, switch off mains 

fuse, secure against being accidentally 
switched back on and position a warning 
sign. 

If required, the unit is cleaned with a dry 
cloth. The operator should determine the 
cleaning intervals 

– frequency depends on 

ambient conditions and anticipated 
impairments. 

Maintenance:

 EZR/DZR units require no 

maintenance. Despite this, check the unit 
from time to time for bearing noise, damage 
and disproportionate vibration. If necessary, 
clean the unit of dirt/foreign particles as 
described above. 
Never use water or a high-pressure cleaner 
on the interior. 

 

13. Fault rectification 

Check whether the thermal motor protection 
(PTC thermistor triggering device) has 
tripped. Once the motor protection has cooled 
down, switch the unit on and check for 
unusual noise.  

If the fault still continues, call on the 
services of a trained electrician Repairs 
should only be carried out by a trained 
electrician. 

 

Fault

 

Cause, measure

 

Fan does not 
switch on. 

No mains voltage. 
Check whether the mains 
fuse has failed. Switch on if 
necessary. 

Motor's thermal 
overload 
protection 
switches the fan 
off. 

Motor too hot. 
Leave the unit switched off 
until the motor and the 
temperature limiter cool 
down.  
Cool-down time can be 

up 

to 30 minutes

. Only then, 

switch the unit back on. 

 

 
 
 

Fault 

Cause, measure 

Fan does not 
switch on. 

Impeller is blocked. 

Repairs may only be 
carried out by an 
electrician: 

Check impeller 

and clean if necessary. 

 
Deposits on the 
impeller and in 
the housing 
caused by dust 
in the air. 

Call on the services of a 
trained electrician. Install air 
filter in the duct system.  
Under no circumstances 
should the inside of the unit 
be cleaned with water or a 
high-pressure cleaner. 

Impeller not 
turning. 

Switch off unit. Switch off all 
supply circuits - switch off 
mains fuse, secure against 
being accidentally switched 
back on and position a 
visible warning sign. 

Call on 

the services of a trained 
electrician.

 Ensure that the 

impeller is not blocked by 
foreign bodies. 

 

 

If the fault persists, disconnect unit 
from the power supply, fit a sign 
prohibiting it from being switched 
back on and have cause of error 
investigated by a trained electrician. 
If faults reoccur, send the unit to our 
factory for repairs. 

 

Summary of Contents for DZR B Series

Page 1: ...nleitung Axial Rohrventilatoren Mounting and Operating instructions Axial duct fans Instructions de montage et Mode d emploi Ventilateurs de gaines h lico des EZR B DZR B EZR D DZR D www m aico ventil...

Page 2: ...erating instructions Page 11 Wiring diagrams Page 30 Scope of delivery Duct fan EZR B DZR B EZR D or DZR D Cable grommets in terminal box Capacitor for EZR units in terminal box These mounting and ope...

Page 3: ...A B...

Page 4: ...lgen Sie den Anweisungen bergeben Sie diese Anleitung nach der Endmontage zur sorgf ltigen Aufbewahrung an den Eigent mer Kinder auch ab 8 Jahren oder Personen mit eingeschr nkten F higkeiten d rfen a...

Page 5: ...Ber hrungsschutz des Fl gelrades nach EN ISO 13857 fehlt MAICO haftet nicht f r Sch den durch bestimmungswidrigen Gebrauch 1 3 Allgemein Die Montage ist nur durch Fachkr fte mit Kenntnissen und Erfahr...

Page 6: ...und entbinden den Hersteller von jeglicher Gew hrleistung und Haftung WARNUNG Stromschlaggefahr Ger t allpolig vom Netz trennen bevor Sie die Klemmenkasten abdeckung abnehmen Warn schild gegen Wieder...

Page 7: ...icherweise gef hrliche Situation die zu leichten bis mittleren K rperverletzungen f hren k nnte ACHTUNG M gliche Situation die zu Sachsch den am Produkt oder seiner Umgebung f hren k nnte INFO Symbol...

Page 8: ...llenden Motorvollschutzschalter zu gew hrleisten Zum Umschalten der Dreh zahlen einen optionalen Polumschalter z B MAICO Polumschalter P1 oder WP1 verwenden 5 Ein Ausschalten Der Ventilator wird mit e...

Page 9: ...ICO Schutzgitter SG BeachtenSie die F rder und Drehrichtung Pfeile auf Aufkleber S 9 Montage ACHTUNG Leckage bei unzureichender Abdichtung Ventilator an allen Flanschbohrungen mit dem Rohrleitungssyst...

Page 10: ...gepr ft werden 10 1 Ventilatoranschluss Vorgeschriebene Anzugsmomente Komponente Anzugs moment Klemmenkastendeckel M4 Edelstahl Zylinderkopfschrauben 1 0 Nm Mantelklemme M7 x 0 75 mm 0 7 Nm Motorklemm...

Page 11: ...herstellen 7 Ger t ausschalten 12 Reinigung Wartung Reinigung Vor der Reinigung Netzsicherung ausschalten gegen Wiedereinschalten sichern Warnschild anbringen Die Reinigung erfolgt bei Bedarf mit eine...

Page 12: ...Ersatzteilbestellungen bitte folgende Daten an 1 Druck Nr dieser Anleitung 0185 0928 0003 2 Typenschild Nr Typenschild auf Ger t oder Titelseite 3 Positionsnummer in Abbildung A Bestelladresse MAICO E...

Page 13: ...he first time Follow the instructions Hand these instructions to the owner for safe keeping once final assembly is complete Children including those aged 8 and above or people with restricted abilitie...

Page 14: ...eering The electrical connection and work on the electrical equipment may only be performed by a qualified electrician They are trained in electrical engineering and are aware of the risks and consequ...

Page 15: ...nently wired electrical installations with NYM O or NYM J 3 x 1 5 mm or 5 x 1 5 mm cables Install a mains isolation device with contact openings of at least 3 mm at each pole Humidity which penetrates...

Page 16: ...depending on installation position The speed of EZR DZR fans can be controlled Exception The speed of the DZR 40 2 B cannot be controlled Reversing mode permitted Flow rate in opposite air flow direc...

Page 17: ...otection IP 55 Exception IP 54 for EZR DZR D Air volume free outlet or free inlet 500 to 14 800 m h de pending on unit variant Weight 5 7 to 41 kg depen ding on unit variant Maximum air flow temperatu...

Page 18: ...rve Chapter 7 1 4 Mount pre fitted fan unit with mounting foot to wall ceiling or bracket Mounting material of the sufficient size should be provided by the customer 5 Lay folded spiral seams ducts fl...

Page 19: ...hat there are no dirt particles in the terminal box and that the seal of the terminal box cover has close contact all the way around the terminal box Note tightening torques Check seal integrity of te...

Page 20: ...voltage Check whether the mains fuse has failed Switch on if necessary Motor s thermal overload protection switches the fan off Motor too hot Leave the unit switched off until the motor and the temper...

Page 21: ...dertaken by an electrician DANGER Danger to life from electric shock Prior to accessing the connection terminals switch off all supply circuits Switch off mains fuse secure against being accidentally...

Page 22: ...emi re utilisation de l appareil Suivez les instructions Une fois le montage final achev remet tez les pr sentes instructions au propri taire qui devra les conserver avec soin Ne pas laisser les enfan...

Page 23: ...tacts selon EN ISO 13857 en cas d entr e ou de sortie d air libre MAICO d cline toute responsabilit en cas de dommages d coulant d une utilisation non conforme 1 3 G n ralit s Seul un personnel qualif...

Page 24: ...le fabricant de toute responsabilit et garantie AVERTISSEMENT Risque d lectrocution Coupez l appareil du secteur sur tous les p les avant de retirer le capot du bornier Apposez un panneau d avertisse...

Page 25: ...3 Symboles utilis s dans le pr sent mode d emploi DANGER Danger imm diat qui s il n est pas pris en compte entra ne de graves blessures corporelles ou la mort AVERTIS SEMENT Situation vraisemblablemen...

Page 26: ...ontacteur disjoncteur Le MVE 10 ne convient pas aux appareils EZR 25 4 D EZR 30 6 B et EZR 35 6 B DZR Les branchements sont amen s par contacts secs sur bornes et doivent tre raccord s p ex un disjonc...

Page 27: ...ateur admise uniquement avec installation fixe dans conduits avec tuyaux agraf s en spirale 250 600 adapt s au type d appareil largeur nominale installation lectrique permanente installation sur mur p...

Page 28: ...VDE 0100 et les parties correspondantes Le ventilateur doit tre raccord un dispositif de commande externe avec d connexion automatique automaintien Chapitre 4 3 Protection thermique contre les surchar...

Page 29: ...R Pour le transformateur 5 plots TR ou TRV adapt au type d appareil cf Internet ou catalogue 11 Mise en service test de fonctionnement 1 D sactiver le fusible secteur s curiser contre toute remise en...

Page 30: ...Installer un filtre air dans le syst me gaine ronde Ne nettoyer en aucun cas l int rieur de l appareil l eau ou avec un nettoyeur haute pression Dysfonction nement Cause mesure L h lice ne tourne pas...

Page 31: ...vertissement de mani re bien visible 1 D connecter le fusible secteur s curiser et apposer un panneau d avertissement 2 Retirer les tuyaux agraf s du ventilateur 3 Ouvrir le couvercle du bornier et re...

Page 32: ...er ST STU STS With ST STU STS speed controller Avec variateur de vitesse ST STU STS EZR B EZR D S1 Aus Taster Off switch Bouton d arr t S2 Ein Taster On switch Bouton de marche Q1 Sch tz US 16 Contact...

Page 33: ...R 25 2 B Mit Motorschutzschalter MVE 10 With MVE 10 motor protection switch Avec disjoncteur protecteur de moteur MVE 10 S1 Aus Taster Off switch Bouton d arr t S2 Ein Taster On switch Bouton de march...

Page 34: ...protection switch Avec variateur de vitesse ST STU STS et disjoncteur protecteur de moteur MVE 10 EZR 25 2 B Mit Drehzahlsteller ST STU STS und Motorschutzschalter MVE 10 With ST STU STS speed control...

Page 35: ...e tension 5 plots TRE et disjoncteur protecteur de moteur MVE 10 EZR 25 2 B Mit 5 Stufentransformator TRE und Motorschutzschalter MVE 10 With TRE 5 step transformer and MVE 10 motor protection switch...

Page 36: ...MV 25 With MV 25 motor protection switch Avec disjoncteur protecteur de moteur MV 25 DZR B Mit Motorschutzschalter MV 25 und 5 Stufentransformator TR With MV 25 motor protection switch and TR 5 step...

Page 37: ...chaltbar 2 Drehzahlen mit Dahlanderschaltung Mit Motorschutzschalter Pole changing 2 speeds with Dahlander circuit With MV25 motor protection switch inversion de la polarit 2 vitesse de rotation avec...

Page 38: ...DZR 25 4 D Mit Motorschutzschalter MV und 5 Stufentransformator TR 0 4 With MV motor protection switch and 5 step transformer TR 0 4 Avec disjoncteur protecteur de moteur MV et transformateur de tensi...

Reviews: