Maico DRD EC 010 Installation Instructions Manual Download Page 3

Installation instructions 

Centrifugal roof fan 

DRD EC

 

 
 

 

Version 5 

– 05.2014 – subject to errors and alterations 

Page 3 of 8 

 

MAICO Ventilatoren · Steinbeisstrasse 20 · D-78056 VS-Schwenningen · www.maico-ventilatoren.com 

 

0

5

.1

4

_

tr

 

1.7  Disposal 

If  no  return  or  disposal  agreements  have  been  made, 
bring the dismantled components to recycling: 

  Have metals scrapped. 

  Give plastic elements to recycling. 

  Bring  electronic  components  to  the  appropriate 

disposal centre. 

  Dispose  of  the  remaining  components  sorted  by 

the material characteristics. 

 

2  INTENDED USE 

The device is designed and constructed exclusively for 
the intended purpose described here. 
The  fan  is  exclusively  used  for  transporting  normal, 
dust-free  and  air-conditioned  air  and  other  non-
aggressive and non-flammable, non-explosive gases. 
Additional  applications  approved  by  the  manufacturer 
that  arise  from  the  fan’s  optional  equipment  are  de-
scribed in the customer specification. 
 

 

WARNING!  

Danger from non-intended use! 

Every  application  that  goes  beyond  intended 
use  and  /  or other use of  the device can lead 
to dangerous situations. Therefore: 

  Use  the  device  only  for  its  intended  pur-

pose. 

  Strictly  comply  with  all  information  in 

these operating instructions. 

 
Claims  of  any  kind  for  damage  that  have  arisen  from 
non-intended use are excluded. 
The operator alone shall be liable for all damage arising 
from non-intended use. 
 

3  TECHNICAL DATA 

3.1  Rated values 

Motor size 

18 

22 

31 

Nominal voltage [VAC] 

230 

Frequency [Hz] 

50 

Speed [min

-1

1950 

1850 

1635 

Power consumption [W] 

85 

165 

370 

Power supply [A] 

0.96 

1.30 

1.65 

Temperature [°C] 

-25 / +35 

Weight [kg] 

12 

13 

16 

3.2  Mounting data 

Screw  the  fan  baseplate  on  a  suitable  base  using  the 
four corner holes (max. M12). 

3.3   Device drawings 

 

Motor size 

18 

22 

31 



 

480 

520 

630 



 

420 

460 

570 



 

485 

525 

635 

 

300 

370 

445 

30 

30 

30 

M • z 

M6•3 

M6•3 

M8•8 

Øk 

213 

259 

356 

Ød 

12 

12 

12 

 
 

 

Summary of Contents for DRD EC 010

Page 1: ...fety regulations 2 1 4 Electrical current 2 1 5 Electro magnetic radiation 2 1 6 Storage 2 1 7 Disposal 3 2 INTENDED USE 3 3 TECHNICAL DATA 3 3 1 Rated values 3 3 2 Mounting data 3 3 3 Device drawings 3 3 4 Transport and storage conditions 4 4 CONNECTION AND COMMISSIONING 4 4 1 Make mechanical connection 4 4 2 Make electrical connection 4 4 2 1 Requirements 4 4 3 Check connections 4 4 4 Switch on ...

Page 2: ... the commercial sector The oper ator of the device is thus subject to the statutory obliga tions on occupational safety Alongside the safety regulations in these instructions the safety accident prevention and environmental safe ty regulations that are applicable for the area of use of the device must be complied with Alterations extensions or modifications are not permitted without the permission...

Page 3: ... by the manufacturer that arise from the fan s optional equipment are de scribed in the customer specification WARNING Danger from non intended use Every application that goes beyond intended use and or other use of the device can lead to dangerous situations Therefore Use the device only for its intended pur pose Strictly comply with all information in these operating instructions Claims of any k...

Page 4: ...ust be avoided Check the device for any transport damage Dam aged devices may no longer be mounted Mount the undamaged device on a suitable base based on its application Connect pressure line on the pressure tapping on site in the duct or pipeline 4 2 Make electrical connection DANGER Danger of lethal electrocution from elec trical current Contact with live parts poses a risk to life Switched on e...

Page 5: ...are pre set and fastened on the bolt Their purpose is to fix the lid and may not be removed to release the mounting bracket Remove mounting bracket and lid store safely Feed cable as shown through the opening in the outer coating 1 and the cable screw fitting in the inner ring 2 Insert cable with suitable radius into the junction box 3 Connect cable cores to the appropriate terminals based on the ...

Page 6: ...mpeller is running untrue Imbalance in the moving parts Clean device If there continues to be an imbalance after clean ing replace device Defective cooling Improve cooling if pos sible Reset by switch ing off the supply volt age for at least 20 s Ambient tem perature too high Lower ambient tem perature if possible Inadmissible operating point Check operating point Contact the manufacturer if you h...

Page 7: ...rifugal roof fan DRD EC Version 5 05 2014 subject to errors and alterations Page 7 of 8 MAICO Ventilatoren Steinbeisstrasse 20 D 78056 VS Schwenningen www maico ventilatoren com 05 14_tr 6 2 Version with EC 3 6 3 Version with EC 010 ...

Page 8: ...ctions Centrifugal roof fan DRD EC Version 5 05 2014 subject to errors and alterations Page 8 of 8 MAICO Ventilatoren Steinbeisstrasse 20 D 78056 VS Schwenningen www maico ventilatoren com 05 14_tr 6 4 Version with EC 230 ...

Reviews: