16 Spare parts

21

Fault

Cause → Measure

Fan performance inad-
equate.

Dirty filter. → Replace
filter.

Locking hook not en-
gaged. → Engage fan
insert correctly.

Incorrect duct diameter.
→ Check diameter of
the main duct.

Supply air cross section
is too small. → Increase
the supply air cross
section.

Spiral housing too loud. Dirty filter. → Replace

filter.

Fan insert incorrectly in-
stalled. → Insert fan in-
sert correctly in accord-
ance with these instruc-
tions.

The main duct is under-
sized. → Re-calculate
pressure losses.

H model does not
switch from base load
to full load operation
despite there being hu-
midity in the room.

No rapid increase in hu-
midity (7% in 2 minutes)
took place.

H model no longer
switches back to base
load operation or off
even after a long period
in full load operation.

The level has not yet
fallen below reference
value. After 1 h, the
valve automatically
switches from full load
operation to base load
operation after an over-
run time of 15 minutes
and resets the refer-
ence value.

Additional consumers
connected to terminal 4.

Damage to the unit if
connected incorrectly.

Do not connect addi-
tional consumers to ter-
minal 4.

The unit may only be
connected according to
the wiring diagrams
(

Wiring diagrams

[

}

 22]

).

 If the fault persists or reoccurs

: Disconnect

the unit completely from the power supply. Let a
qualified electrician determine the cause of the
fault and eliminate it. If you have any question re-
lating to troubleshooting: Service: +49 7720 6940.

16 Spare parts

 Spare parts may only be sourced from and

fitted by a specialist installer.

Designation

Article no.

Cover for upper part of
housing

0059.1037.0001

Filter mat ZF 60/100: 5
pieces, filter class G2
according to EN 779
with filter change indic-
ator (time strip)

0093.0331

Upper part of housing,
complete Centro-APB
60/100

0059.1036.9001

Spiral housing without
cover

Centro-E-APB

Centro-H-APB

E084.0184.0000

E084.0185.0000

Lower part of housing,
complete Centro-APB
60/100

E059.1035.9200

SB printed circuit
boards, complete
Centro-H / H-APB

F101.1027.900

In case of questions, please contact:

Maico Elektroapparate-Fabrik GmbH
Steinbeisstraße 20
78056 Villingen-Schwenningen, Deutschland
Tel. +49 7720 694 445
Fax +49 7720 694 175
E-mail: 

[email protected]

 Spare parts

 can be ordered at

www.shop.maico-ventilatoren.com

.

17 Removal

 Dismantling may only be undertaken by a

qualified electrician.

Summary of Contents for Centro-M-APB

Page 1: ...Installation and operating instructions Surface mounted system for centralised ventilation in ac cordance with DIN 18017 3 Centro M APB Centro E APB Centro H APB www maico ventilatoren com...

Page 2: ...preparations 9 8 1 Requirements in line with approval 9 8 1 1 Approval provisions 9 8 2 Permitted installation positions 9 8 3 Preparations for installation with fire protection requirements 10 8 3 1...

Page 3: ...3 Preface Please read the instructions carefully before in stalling and using for the first time Follow the in structions Pass these instructions on to the owner for safekeeping Overview of Centro APB...

Page 4: ...ci ated with electricity on the basis of your technical training and experience 3 Intended use Centro APB exhaust air elements are intended for use in central ventilation systems with a common main du...

Page 5: ...shock If the unit is open all off the supply circuits must be switched off mains fuse off secured against being accidentally switched back on and a visible warning sign must be attached Only operate t...

Page 6: ...mulate harmful substances mould germs etc This may also happen if the unit is shut down for an extended period If the air filter is missing the unit and air ducts become soiled Never operate the unit...

Page 7: ...y relative humidity This hu midity value is saved as the first reference value The reference value does not have to be spe cified manually If the room humidity rises by 7 within 2 minutes the exhaust...

Page 8: ...ch the air is to be extracted must be fitted with a non closable free supply air cross section of at least 150 cm e g with MLK door ventilation grille Centro E APB and Centro H APB with resist ance to...

Page 9: ...duct between the main duct in the shaft and the unit max 2 m long ap proval Duct elbows in the unit con nection duct Max 90 bend ascending Number of duct elbows permit ted for wall installation Max 1...

Page 10: ...DANGER Danger to life due to fire trans mission in case of faulty ceiling compound It is essential that the remaining gap between the main duct and the wall or ceiling is completely sealed with non fl...

Page 11: ...r bolt steel dowel 27 2 Metal expansion dowel 28 Retaining bolt with nut 29 Retaining bolt 30 Steel clamping band Keep a maximum distance of 1 5 m between the duct fastenings It is essential to observ...

Page 12: ...mmable materials that are resistant to de formation For example use concrete or ce ment mortar or for wall boards use fire protec tion filler 7 Fasten duct bends with 3 steel screws or 3 steel blind r...

Page 13: ...socket is incorrectly con nected to the connection duct Make the connection in accordance with these in structions and the general building approval 3 steel blind rivets are prescribed for the connec...

Page 14: ...It is es sential that the permissible installation posi tions are observed 3 Drill fixing holes and insert dowels Suitable mounting material is to be provided by the customer 4 Check ease of movement...

Page 15: ...r rectly all the way round 10 Slide connection duct up to stop above ex haust socket Connection between connection duct and exhaust socket must be leak tight use cold shrink tape for example Prescribe...

Page 16: ...of incorrect installation if non permitted mounting material is used Only secure connection duct to ceiling with per mitted mounting material duct clamp or clamping band Prescribed mounting material...

Page 17: ...ning sign DANGER Danger from electric shock The unit will be damaged if installed incorrectly with too long a power cable If the cable feed is too long inside the housing the fan insert cannot be inst...

Page 18: ...PB with fixed air volume setting for basic ventilation 8 Sealing 10 2 Shut off shutter 36 38 Locking tabs 37 Locking lever 2 Switch off mains fuse and fit warning sign 3 Check ease of movement of shut...

Page 19: ...n A all the way The red dye in the interior of the bar B is released The bar indicator first fills slightly Within the next 6 months the bar indicator B will rise to the upper edge indicator value 6 1...

Page 20: ...ocking tabs 37 Locking lever 38 Locking tabs 1 Switch off mains fuse secure and fit warning sign 2 Remove cover and upper part of housing 3 Press locking lever slightly to the left arrow I release and...

Page 21: ...o not connect addi tional consumers to ter minal 4 The unit may only be connected according to the wiring diagrams Wiring diagrams 22 If the fault persists or reoccurs Disconnect the unit completely f...

Page 22: ...estic waste Dispose of the packaging material in an environ mentally friendly way in compliance with the reg ulations valid in the country where you are Dispose of the air filter in an environmentally...

Page 23: ...erence value does not have to be specified manually If the room humidity rises by 7 within 2 minutes the exhaust air element switches to full load operation demand based ventilation If the relative hu...

Page 24: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de D11 21_EN_DSW AV...

Reviews: