Maico AWV 10 Mounting Instructions Download Page 5

– Subject to change! –

5

Electrical connection work and repairs should only
be carried out by qualified electricians.

During electrical installation and assembly, ensure
compliance with the corresponding directives, in
particular the pertinent sections of DIN VDE 0100.

Do not insert any objects into the unit due to the
danger of injury when the fan is running.

This device may only be used:

–  

surface-mounted

 on the external wall, as de-

   scribed below.
–  with the shutter [5] directed downwards (towards
   the floor).
– with a preceding air filter. This makes the unit
   maintenance-free.
– installed on a flat, non-curved wall.
– connected to DN 100, DN 150 or DN 200 ven-
   tilation ducts, depending on device type.
– with a free inlet, only with protective grille. Pro-
   tection against accidental contact with the im-
   peller in accordance with DIN EN 294 must be
    guaranteed.

This device may not be used:

– in the vicinity of inflammable materials, fluids or
   gases.
– in areas subject to explosion hazards.
– if the extracted air or smoke has particles that
  contain grease or soot, or that are chemical,
   corrosive, easily flammable or explosive.

If the fans are being used with air-ventilated
fireplaces, you must ensure that there is sufficient
flow of supply air. The maximum permitted pressure
difference is 4 Pa.

The temperatures of the air medium and the
ambient temperature must not exceed 40 °C. With
the AWV 10, the maximum is 30 °C.

The motor has a thermal overload protection,
which switches the unit off in the event of overheating.

Before removing the cover [2], disconnect the unit
completely from the power supply. To do this,
switch off the mains fuse at the fuse box.

The device must not be put into operation if it is
damaged.

Modifications and changes to the device are not
permitted and if carried out, they release MAICO
from any and all guarantee commitments or liability.

The fan is designed in accordance with VDE safety
requirements within the framework of the equipment
safety legislation as well as the pertinent regulations
laid down in the EC directives.

Overview

 1

Base ceiling with 4 fastening holes

 2

Cover

 3

Coupling

 4

Screw with tooth lock washer ( 2 of each)

 5

Airstream-operated  shutter

 6

Protective grille

 7

Terminal block

 8

Capacitor

 A1

“Impeller rotation direction“ label

 A2

“Wiring Diagram“ label

 B

Hole for connecting cable (2 pieces)

 T

Rating plate

Function

The external wall fan will be switched on and off with
a switch to be supplied by the customer.

Electrical connection

Wiring diagrams can be found on the back page of
the instructions.

The fan may only be connected to a permanent
electrical installation with 1.5 mm² cabling. This
must be fitted with a mains isolation device that has
contact openings of at least 3.5 mm at each pole.

The degree of protection is only guaranteed if the
cabling is installed and inserted correctly.

The power supply must comply with the rated
voltage as stated on the rating plate.

The external wall fan can be speed-controlled.

Installation

Important notes

Installation should only be carried out by a specia-
list.

There is a danger of injury through sharp metal
edges. Proceed in a secure and danger-aware
manner.

1.

Mark and drill holes for the screw plugs.

2.

Carry out the wall breakthrough and install the
mains cable (recessed mounted) and “WH“ wall
sleeve, as required).

3.

Remove the cover [2] from the AWV. To do this,
loosen the two screws [4], swing the cover outwards
from the lower side and lift it up.

4.

Feed the connection cable in through the left or
right-hand side hole “B“ in the fan housing.

5.

Screw the base plate [1] with 4 screws to the wall.
Fixing material must be supplied by the customer.

Summary of Contents for AWV 10

Page 1: ...L A T O R E N Au enwand Ventilatoren External wall fans Ventilateurs muraux ext rieurs www maico de AWV 10 AWV 10 S AWV 15 AWV 15 S AWV 20 AWV 20 S Montageanleitung Mounting instructions Instructions...

Page 2: ...2...

Page 3: ...rehrichtung Laufrad A2 Aufkleber Schaltbild B Bohrung f r Anschlussleitung 2 St ck T Typenschild Au enwand Ventilatoren AWV und AWV S AWV Ventilatoren dienen zur Entl ftung von K chen Gewerber umen Ka...

Page 4: ...auben 8 Funktionstest durchf hren fertig Bei einer St rung Eine St rung kann z B durch erh hte F rdermittel temperaturen oder durch Blockieren des Ventilator motors auftreten Der berlastungsschutz rea...

Page 5: ...changes to the device are not permitted and if carried out they release MAICO from any and all guarantee commitments or liability The fan is designed in accordance with VDE safety requirementswithint...

Page 6: ...ext rieure suffisante La diff rence de pression maximale est de 4 Pa Les temp ratures du fluide refoul et de l environ nement ne doivent pas d passer les 40 C max Max 30 C pour l AWV 10 6 Make the ele...

Page 7: ...ossible de r gler la vitesse du ventilateur mural ext rieur Montage Consignes importantes Le montage ne doit tre confi qu un personnel qualifi Risque de blessures par des t les bord ac r Agissez en ay...

Page 8: ...Aus Schalter 7 0 7 4 0 2 6 8 0 0 0 0 with On Off switch avec interrupteur Marche Arr t 4 3 1 2 M 1 N L AWV10 AWV15 AWV20 AWV10S AWV15S AWV20S ST STU1 L N PE mit Drehzahlsteller ST STU1 10 15 20 AWV AW...

Reviews: