UK
│
Safety instructions, Mounting
12
ALD 10 T can only be
fully closed by removing
the spacing ring [10].
If
the outside air is polluted,
remove the spacing ring
and fully close the supply
air element.
6. Mounting
6.1 Mounting instructions
● Position outside wall air opening as per
the details of your planning office.
● For dimensions
Chapter 11.
● Install ALD at an incline of around 1...2 %
towards the outside wall.
● Recommendation: Install ALD in top part
of window (to right or left of window) at a
height of 2 to 2.20 m.
● It must be possible for the cover to be
removed in order to change the filter. The
installation location should be selected
accordingly.
● ALD 10: The internal cover slider must be
easy to move. The slider/guide must not
be soiled, for example from paint residues
or cleaning materials.
● Thinner walls will mean reduced sound
insulation.
● You will find more information and
planning instructions in Practical Guidance
for Comfort Ventilation, (
maico-
fans.com, service, download product
documents, controlled domestic
ventilation).
6.2 Preparations for mounting
1. Take ALD components out of the
packaging.
2. Decide on the installation position.
Ensure a minimum distance of
110 mm between the core hole
centre and wall and ceiling.
6.3 Mounting wall sleeve
NOTICE
Condensate will run towards
the inside wall if the core hole
is drilled at too small an incline.
Ensure an incline of 1...2 % to
the outside wall so that any
condensation which collects can
drain outwards.
Fit the wall sleeve [4] in the wall as follows.
1. Drill core hole with a minimum diameter of
115 mm in the wall.
2. Push the two-piece wall sleeve into the
wall (with the large sleeve diameter
towards the outside). Select a wall sleeve
length which ends with the sleeve flush
with the plaster on both sides.
3. If walls have a wooden construction,
additionally seal the interfaces to this
construction. Stick sealing strips to the
wall sleeve in these areas. Suitable
sealing material is to be supplied by the
customer.
4. Fully seal the spaces between the wall
sleeve and wall with permanently elastic
and weatherproof sealant (
arrow „S“).
5. Optional: Insert storm protection.
Stick enclosed sealing strips on the
outer ring of the storm protection and
insert them in at approximately the
middle of the wall sleeve. Ensure a
vertical installation position ‒ the
silicone ribs must not sag under their
own weight.
Outside wall
Inside wall