Option:
Message „Max. Grease Storage Capacity Reached“
In order measure properly the grease separator needs to be ready for operation and
refilled. As soon as the main switch is turned to position „ON“ the measuring process
starts. When the max. grease storage capacity is reached an alarm light immediately
indicates “Acknowledge General Fault” which means that the disposal process is
pending. The display says “Max. Grease Storage Capacity Reached”. At the same time
the in-house alarm signal processing system (BMS / GLT) is / can be activated via a
floating contact.
By pushing the button “Acknowledge General Fault” the BMS/GLT message can be
confirmed. While the alarm light switches off the message in the text display “Max.
Grease Storage Capacity Reached” remains on until the container of the grease
separator is emptied. The message disappears automatically as soon as water is
recognized.
Nominal Size NS
Stirring Time in Min.
2
5
4
8
7,5
12
10
12