1
Magnum Energy Solutions, LLC 43 Village Way Suite 209 Hudson, OH 44236 phone 330.656.9365 fax 330.656.9368 www.magnumenergysolutions.com [email protected]
Product Installation Guide
Motion / Lux Sensor
Mx-ML2
1] Description
6] Dimensions
7] Pairing
2] Operation
5] Technical Specifications (continued)
The Magnum Energy Solutions (MES) Motion and Lux sensor (Mx-ML2) is a wireless, self powered, passive
infrared sensor that ensures reliable detection of occupant presence. The Mx-ML2 is ideally suited for occupancy
based lighting control and also provides for indoor daylight harvesting functionality, with a light range of 0-1020lx.
When paired with a relay (Mx-USR-L1) and a wireless rocker switch (Mx-ESRP), the sensor creates an out of the
box, cost effective, lighting control system. When combined with an MES gateway (Mx-EBOX), the Mx-ML2 can be
integrated into an existing BACnet-compatible building automation system.
Built in solar cells draw and store energy from available ambient light to power the device and keep it operational
during periods of darkness. The device must be placed at the location where sensing is required and this location
is dependent on individual application (refer to Sensor Placement Tips below). An optional battery back up is
available for locations with low or no ambient light. The Mx-ML2 must be paired with a receiver (refer to Compatible
Devices section). The device can be paired manually to compatible devices by pressing the LRN button while
following the pairing instructions for the receiver. For more sophisticated configuration, please refer to the MES
AirConfig tool available at
http://download.magnumes.net
.
The sensor can be mounted using screws or simply
placed in selected location with double stick tape. It is recommended that the pairing of this device be done prior
to installing the ceiling sensor.
4] Applications
• Hotels & Resorts
• Private Offices
• Colleges & Universities
• Retrofits
• New Construction
• Conference Rooms
• Executive Offices
• Classrooms
• Lighted Hallways
• Perimeter Zones
• Cruise Ships
• Daylight Harvesting
• Restrooms
• Daycare Facilities
• And more..
Light Sensor
0-95 FC (0-1020 Lux)
Default Transmission Interval
Immediate upon detected occupancy
(Status signal sent every 15 minutes)
Default Unoccupied Send Delay
5 minutes (Adjustable via airConfig Tool*)
Minimum Light Required to Charge
4FC (40 Lux)
Minimum Charge Time to Begin Operation
1 minute @ 20FC (200 Lux)
Full Charge Time
8 hours (approx) @100FC (1000 Lux)
Maintain Charge Time
3 hours per 24 hours @ 20FC (200 Lux)
Operation Life at Full Charge (no battery)
up to 72 hours
Optional Battery Life
10 years (1/2AA 3.6V Lithium)
Operating Temperature
-3°F to 140°F (20°C to 60°C)
Detection Distance (PIR Sensor)
39 ft (12 m)
Detection Range (Horizontal & Vertical) (PIR Sensor) 102° x 92°
3.17”
(80.52 mm)
2.96”
(75.18 mm)
4.02”
(102.11 mm)
LRN Button
Press and release the LRN button. The red LED light should
flash once, signaling the device has sent a “learn” message to
identify itself with compatible devices within wireless range
Please refer to the corresponding device installation guides to
review the process of learning this sensor with compatible devices.
NOTE: It is recommended that pairing of device be done prior to installing the ceiling sensor.
NOTE: Place the sensor under bright light for 1 or more minutes to gather energy to begin functioning.
Light Sensor
LED
5] Technical Specifications:
Part Numbers (Frequency Dependant)
M9-ML2 (902 MHz - North America)
M8-ML2 (868 MHz - Europe and China)
MJ-ML2 (928 MHz - Japan)
Range
150 feet (50-150 typical)
EnOcean Profiles
A5-07-03 (Default) - Occ, Supply Voltage, Illumination 0-1000lx
F6-02-01 - Rocker On/Off, Occ Only
A5-06-02 - Illumination 0-1020lx only
A5-07-01 - Occ, Supply Voltage
A5-07-02 - Occ, Supply Voltage
A5-08-01 - Occ, Supply Voltage, Illumination 0-510lx
A5-08-02 - Occ, Supply Voltage, Illumination 0-1020lx
A5-08-03 - Occ, Supply Voltage, Illumination 0-1530lx
To select profiles other than default,
utilize the MES software for configuration
“AirConfig Tool*”. Download available
at
http://download.magnumes.net
MAGNUM