49
57-606 ECLIPSE Model 706 Guided Wave Radar Transmitter
Refer to the table below for a complete listing of the
Model 706 diagnostic indicators, along with their explana-
tions, default categories, and recommended remedies.
NOTES:
1) The remedies shown in this table can also be seen on
the transmitter LCD by viewing the present status
screen when the device is in a diagnostic condition.
2) Those indicators showing failure as the default result
in an alarm condition.
3.3.2 Diagnostic Indication Simulation
The DD and DTM allow for the ability to manipulate
diagnostic indicators. Intended as a means to verify the
configuration of the diagnostic parameters and connected
equipment, a user can manually change any indicator to
and from the active state.
3.3.3 Diagnostic Indicator Table
Below is a listing of the Model 706 diagnostic indicators,
showing their priority, explanations and recommended
remedies. (Priority 1 is highest priority.)
Priority
Indicator Name
Default
Category
Explanation
Remedy (Context Sensitive Help)
1
Software Error
Failure
Unrecoverable error occurred in stored
program.
Contact MAGNETROL Technical Support.
2
RAM Error
Failure
RAM (read/write) memory failing.
3
ADC Error
Failure
Analog-to-digital converter failure.
4
EEPROM Error
Failure
Non-volatile parameter storage failing.
5
Analog Board Error
Failure
Unrecoverable hardware failure.
6
Analog Output
Error
Failure
Actual loop current deviates from com-
manded value. Analog output is inaccu-
rate.
Perform Adjust Analog Output mainte-
nance procedure.
7
Spare Indicator 1
OK
Reserved for future use.
8
Default
Parameters
Saved parameters are set to default val-
ues.
Perform complete Device Configuration.
9
No Probe
Failure
No Probe Connected.
Attach a probe.
Torque HF nut.
Clean gold pin on transmitter and socket
on probe.
Ensure Model 705 style probe is not
being used.
Contact MAGNETROL Technical Support.
10
No Fiducial
Failure
Reference signal too weak to detect.
Torque HF nut.
Clean gold pin on transmitter and socket
on probe.
Check settings:
Fiducial Gain
HF Cable Length
Window
Increase Fid Gain.
Contact MAGNETROLTechnical Support.