Installation and assembly
7.4
Setting up foundation and placing empty conduits
7.4.1
Requirements foundation
The foundation must meet the following requirements:
›
Have sufficient load-carrying capacity
›
Concrete C20/25 XD3 XF2 or corresponding industrial floor
›
Attachment must be able to grip securely
›
Foundation cross section according to foundation and empty conduit plan
›
Non-slip surface
›
Horizontal and level.
For outdoor assembly, the foundation must meet the following additional
requirements:
›
Concrete C20/25 XD3 XF2
›
Foundation depth: at least 800 mm, frost-proof. Adapt foundation depth to
the local conditions.
›
Reinforcement mesh according to reinforcement plan
ä
Foundation and empty conduit plan and reinforcement: Page 40, Fig. 11.
7.4.2
Requirements empty conduits
Observe the following points for the empty conduits:
›
Place empty conduits according to the foundation plan.
›
Conduits have to be planned to a sufficient length.
›
Plan empty conduits required for access-control devices and other
peripheral devices. The cabling for this is the responsibility of the customer.
Alternatively, you can thread the mains cable and control lines into the swing
door via cable screw connections in the floor ring.
ä
IMPORTANT!
To ensure trouble-free operation, install separate empty conduits
for the mains cable and control lines.