Operation Instructions
MBE35_50 OPERATION MANUAL 2005_10
-
21
-
closing delay timer will start and the gate will not close
until the timer is elapsed.
3 ON
and
4 ON
In this switch setting the closing delay time is set to 9
sec. When a closing command on IN3 was given or a
vehicle passed through the safety-closing zone the
closing delay timer will start and the gate will not close
until the timer is elapsed.
4 OFF
This switch sets the closing delay time to 2 sec. When a
closing command on IN3 was given or a vehicle passed
through the safety-closing zone the closing delay timer
will start and the gate will not close until the timer is
elapsed.
4 ON
This switch sets the closing delay time to 5 sec. When a
closing command on IN3 was given or a vehicle passed
through the safety-closing zone the closing delay timer
will start and the gate will not close until the timer is
elapsed.
5 OFF
Relay K1 active when gate starts to open. Indication of
motor drive direction. Relay cycles on/off when a gate
failure occurred.
5 ON
Relay K1 active when gate is in fully closed position
(depending on how the down limit switch is set).
Relay cycles on/off when a gate failure occurred.
6 OFF
Relay K2, 500ms pulse when passing the safety/closing
device connected on IN5.
6 ON
Relay K2, 500ms pulse when gate opens
7 OFF
Relay K3; For warning signals (Lights and horns).
Depending on the DIP switch settings 3 and 4 this relay
will turn on and off warning signals to alert patrons that
the gate will soon close. The relay will stay active 5 sec.
after the gate reached the down limit switch.
7 ON
Relay K3; For red/green traffic lights. The relay is
activated as soon as a closing command on IN3 is given
or a vehicle passed through the safety-closing device.
The gate will close after the closing delay timer
(DIPswitch 3 and 4) is elapsed. The relay will stay active
until an opening command to IN1 or 2 was provided.