5.4.3 Test Mode Configuration
Test Mode is a troubleshooting aid that is intended for troubleshooting Flux Vector control method problems. This
feature cannot be left on indefinitely, as it will generate a fault after being on for a total accumulated time of ten
minutes. At this time, the fault must be reset or the power must be cycled.
To enable Test Mode, refer to parameter L05-01.
Table 5-62: Test Mode Configuration Parameter Settings
Parameter
Display
Function
Range
Default
E03-01
Control Method
Control Method
0, 2
2
0 V/f Control
2 Open Loop Vector
E03-02
Stopping Method
Deceleration Method
0, 1
1
0 Decel to Stop
1 Coast to Stop
E03-03
Max Frequency
Maximum Frequency
20.0–150.0 Hz
60.0
E03-04
Max Voltage
Maximum Voltage
230 V: 0.0–255.0
460 V: 0.0–510.0
575 V: 0.0–733.1
Determined by
O02-04
E03-05
Base Frequency
Motor Base Frequency
0.0–150.0 Hz
60.0
E03-06
Mid Frequency A
Motor Middle output frequency
0.0–150.0 Hz
Determined by
E01-03
E03-07
Mid Voltage A
Motor Middle output frequency voltage
230 V: 0.0–255.0
460 V: 0.0–510.0
575 V: 0.0–733.1
Determined by
E01-03
E03-08
Min Frequency
Minimum Frequency
0.0–150.0 Hz
Determined by
E01-03
E03-09
Min Voltage
Motor Minimum output frequency voltage
230 V: 0.0–255.0
460 V: 0.0–510.0
575 V: 0.0–733.1
Determined by
E01-03
E03-10
Mid Frequency B
Midpoint Output Frequency B
0.0–150.0 Hz
0.0
E03-11
Mid Voltage B
Midpoint Output Voltage B
230 V: 0.0–255.0
460 V: 0.0–510.0
575 V: 0.0–733.1
0.0
E03-12
Base Voltage
Motor Base Voltage
230 V: 0.0–255.0
460 V: 0.0–510.0
575 V: 0.0–733.1
0.0