November 2020
Page 52
5.1.3 Sequence/Reference Source
B03.01 and B03.02 determine the source from where the frequency reference and RUN command are generated.
5.1.3.1
Stopping Method
B03.03 selects the stopping method suitable for the particular application.
* Initial value is determined by X-Press Programming
Parameter Name
Function
Range
Default
B03.01
Reference Source
Selects frequency reference source.
00–04
01
00 Keypad
Keypad
01 Terminals
Control circuit terminal
02 Serial Communication
Modbus Serial Communication
03 Option PCB
Industrial Communication
04 Pulse Input
Pulse Input (Terminal RP)
B03.02
Run Source
Selects run command source.
00–03
01
00 Keypad
Keypad
01 Terminals
Control circuit terminal.
02 Serial Communication
Modbus Serial Communication
03 Option PCB
Industrial Communication
Parameter Name
Function
Range
Default
B03.03
Stop Method
Determines stop method.
00–02, 04
*
00 Decel to Stop
Used to stop when motion is traverse
(
and
01 Coast to Stop
Used to stop when motion is hoist
(
and
02 DC Injection
and
04 Decel w/ Timer
(traverse only)
, and
WARNING
Because of the potential hazards that are introduced when any VFD is operated locally, Magnetek advises the
user to avoid operating it this way. If the user does operate the VFD locally, be aware that the crane or hoist will
move when the RUN button is pressed. Contact Magnetek with any questions.