507861-01

Issue 2120

Page 3 of 15

Figure 1. Minimum Clearances

Exterior Wall

Wall Sleeve

Interior Wall

Minimum

Clearances

3/4" Plywood Riser

Floor

Front of Unit

Sill Plate

4" Min.

Supply

Duct

Mounting Strap

(one each side)

Return

Duct

Unit must be supported by platform, which must be 

level with sill plate of opening in exterior wall.

Platform (field supplied) - 

Supply Duct

Opening

Clearance to

Front of Unit

Optional Front 

Return Opening

May be used with 

or without attached 

ductwork

Return Duct

Opening

1” Min.

Side Clearance

Exterior Wall

Closet Wall

Closet Wall

1” Min.

Side Clearance

Closet Door

* Minimum 30” wide

IMPORTANT

The unit must be installed with approved 

wall sleeve and louver accessories for 

safe operation. Improper installations 

could result in property damage, personal 

injury, or death.

Accessibility Clearances

The front of the unit must be accessible for 

service. A minimum clearance of 30” in front 

of unit is required for service. 

If the unit is enclosed, a door or access 

panel aligned with the front of the unit is the 

preferred method of providing access. The 

door or access panel opening must be a 

minimum of 30” wide (centered on the unit) 

and be as tall as the unit. 

If a return duct is not installed, in order to 

provide adequate return air, the minimum 

clearance required between the front of the 

unit and the door or access panel is 4” for 

43” tall cabinets and 5” for 48” and 56” tall 

cabinets. 

Supply Duct Clearances

Minimum Clearances to Combustible 

Materials 

[1]

Front

Sides

Top

0”

0”

0”

[1] Accessibility clearances take precedence.

Unit Clearances

Minimum 

Clearances 

[1]

Return Duct 

Configuration

Unit 

Height

Front Sides 

[3]

Connected to 

unit’s:
- Top Duct 

Opening, or
- Optional Front 

Return

All

See  

Note 2

1”

No Return Duct 

(Open Optional 

Front Return)

43”

4”

1”

48” or 56”

5”

1”

[1] Accessibility clearances take precedence.

[2] Clearance must accommodate field-installed condensate drain 

line / drain trap.

[3] Additional clearance required if field-installed condensate 

drain line / drain trap is routing alongside unit.

Side View

Top View

Summary of Contents for All-In-One MHP4 Series

Page 1: ...e consulted before installation is made Such applicable regulations or requirements take precedence over the general instructions in this manual CAUTION P 507861 01 P507861 01 Installation These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING General These instructions explain the recommended method of installation of th...

Page 2: ...n company If any damages are discovered and reported to the carrier do not install the unit as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and local safety codes Limitations of the unit and appropriate accessories must also be observed The outdoor fan is designed to operate against...

Page 3: ...f unit is required for service If the unit is enclosed a door or access panel aligned with the front of the unit is the preferred method of providing access The door or access panel opening must be a minimum of 30 wide centered on the unit and be as tall as the unit If a return duct is not installed in order to provide adequate return air the minimum clearance required between the front of the uni...

Page 4: ...rille Installation Refer to installation instructions included with the wall sleeve kit and the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille The sleeve is not intended as the sole support for the unit An additional support must be provided for adequate support see Figure 2 CAUTION Installing and Securing Unit to Wall Sleeve 1 Mak...

Page 5: ...ion to top and bottom corners of unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America ACCA Check unit air supply outlet for debris before making ductwork connections It is recommended that supply and return duct connections at the unit be made with flexible joints If flexible ducts are...

Page 6: ...kW TAP 4 AUX HEAT 615 93 590 97 555 101 N A N A N A N A TAP 5 AUX HEAT 715 127 685 134 655 140 630 146 600 151 5 kW TAP 4 AUX HEAT 665 110 635 114 605 118 N A N A N A N A TAP 5 AUX HEAT 750 148 725 154 700 160 675 166 650 171 7 kW TAP 4 AUX HEAT 725 137 705 144 675 150 N A N A N A N A TAP 5 AUX HEAT 825 194 800 200 780 205 755 209 725 213 10 kW TAP 4 AUX HEAT 750 148 725 154 700 161 N A N A N A N ...

Page 7: ...peed for Cooling operation Blower speed must be field adjusted to Speed Tap 3 for higher duct static applications As shipped speed for Heating operation Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications Table 3 Blower Performance 208V or 230V Air Filter All indoor return air must be filtered A washable filter is furnishedwiththeunit locatedinthereturnaircompart...

Page 8: ...e wall sleeve and louver assembly to the outside of the building Use thread sealant on the threaded fittings Install threaded fittings by hand only Do not over torque the fittings Do not thread metal condensate fittings to unit drain pans CAUTION Outdoor Ventilation Air Units are fitted with a panel that seals the return air compartment at the outdoor air duct If introduction of outdoor air is des...

Page 9: ...r inlets to flue gas terminals Improper installation could result in personal injury or death WARNING Figure 7 Auxiliary and Factory Panel for Outdoor Air Duct Factory panel Outdoor Air Duct Auxillary panel with knockouts 1 2 3 4 5 6 7 8 9 Thermostat The room thermostat should be located on an inside wall where it will not be subject to drafts sun exposure or heat from electrical fixtures or appli...

Page 10: ...fort during defrost The unit will remain in defrost until the defrost sensor has determined that the frost has been removed from the coil or a 14 minute time period has elapsed The defrost control is also equipped with a set of pins to aid in the troubleshooting of the defrost system see Figure 9 The following is a brief outline of the testing of the defrost system 1 Defrost sensor must be closed ...

Page 11: ...m cleaner Wash filter in soap or detergent water and replace after filter is dry It is not necessary to oil the filter after washing Motors The indoor and outdoor fan motors are permanently lubricated and require no maintenance Outdoor Coil Foreign material should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to ...

Page 12: ...m Color 29 Height ALVRAL 1P Extruded Aluminum Louver Kit 33 Height ALVRAL 2 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 2P Extruded Aluminum Louver Kit 33 Height ALVRAL 7 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 7P Extruded Aluminum Louver Kit 45 Height ALVRAL 3 Extruded Aluminum Louver Kit Custom Color 45 Height ALVRAL 3P Extruded Aluminum Louver Kit 45 Height ALV...

Page 13: ... Louver ASLEEVE8 2 8 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE8 5 8 45 16 16 5 8 45 1 8 10 Wall Sleeve Kit for 29 Louver ASLEEVE10 1 10 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE10 2 10 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE10 5 10 45 16 16 5 8 45 1 8 12 Wall Sleeve Kit for 29 Louver ASLEEVE12 1 12 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE12 2 12 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASL...

Page 14: ...Page 14 of 15 507861 01 Issue 2120 Wiring Diagrams Figure 11 Connection Diagram MHP With Single Circuit and Hard Start Enabled ...

Page 15: ...507861 01 Issue 2120 Page 15 of 15 Figure 12 Connection Diagram MHP With Dual Circuit and Hard Start Enabled ...

Reviews: