U5098 Series Ultrasonic Sensors Manual
099-MF179 - Configuration Modes
Page. 13 of 40
www.madisonco.com
U5098 -
conÞ
guration
modes
RL1 PUMP SET UP (only for RL1)
A pump control functioning activation, with hysteresis, is possible two
thresholds setting is required:
upper and lower threshold.
1.
-
UPPER.
The upper threshold is expressed in mm distance from the sensor.
Represents the pump starting point, EMPTY case, or pump stopping
point, FILLING case.
Default value: 0
2.
-
LOWER
The lower threshold is expressed in mm distance from the sensor.
Represents the pump stopping point, EMPTY case, or pump starting
point, FILLING case.
Default value: 0